Desa FVF30P Connecting to GAS Supply, A. Design-Certified Manual Shutoff Valve With 1/8 NPT Tap

Page 12

FIREPLACE MANUFACTURERS INCORPORATED

UNVENTED PROPANE/LP GAS LOG HEATER

INSTALLATION

Continued

CONNECTING TO GAS SUPPLY

WARNING: A qualified ser- vice person must connect heater to gas supply. Follow all local codes.

CAUTION: Never connect heater directly to the propane/LP supply. This heater requires an external regulator (not supplied). Install the external regulator be- tween the heater and propane/LP supply.

Installation Items Needed

Before installing heater, make sure you have the items listed below.

external regulator (supplied by installer)

piping (check local codes)

sealant (resistant to propane/LP gas)

manual shutoff valve *

test gauge connection *

sediment trap

tee joint

pipe wrench

*An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection.

External Regulator

Propane/

LP Supply

Tank

Vent Pointing Down

Figure 13 - External Regulator With Vent Pointing Down

WARNING: Never connect heater to private (non-utility) gas wells. This gas is commonly known as wellhead gas.

CAUTION: Use only new, black iron or steel pipe. Inter- nally-tinned copper tubing may be used in certain areas. Check your local codes. Use pipe of 1/2" diameter or greater to allow proper gas volume to heater. If pipe is too small, undue loss of pressure will occur.

Installation must include a manual shutoff valve, union, and plugged 1/8" NPT tap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 14).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION: Use pipe joint seal- ant that is resistant to liquid pe- troleum (LP) gas.

Install sediment trap in supply line as shown in Figure 14. Locate sediment trap where it is within reach for cleaning. Locate sedi- ment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

CAUTION: Avoid damage to regulator. Hold gas regulator with wrench when connecting it to gas piping and/or fittings.

A.G.A. Design-Certified

Manual Shutoff Valve

With 1/8" NPT Tap

The installer must supply an external regu- lator. The external regulator will reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 14 inches of water. If you do not reduce incom- ing gas pressure, heater regulator damage could occur. Install external regulator with the vent pointing down as shown in Figure

13.Pointing the vent down protects it from freezing rain or sleet.

From External

Regulator (11"

W.C.** to 14"

W.C. Pressure)

Tee Joint

Pipe 3" Minimum

Nipple

Cap

Sediment Trap

Figure 14 - Gas Connection

* Minimum inlet pressure for purpose of input adjustment.

Approved Flexible Gas Hose (if allowed by local codes)

Gas

Regulator

12

105192

Image 12
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASPatent Pending Safety Information Product Features Product IdentificationLocal Codes UnpackingAIR for Combustion and Ventilation Providing Adequate VentilationUnusually Tight Construction Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From InsideBuilding Ventilation Air From OutdoorsInstallation InstallationCheck GAS Type Minimum Wall and Ceiling Clearances see FigureIf Using Mantel If Not Using MantelMinimum Noncombustible Material Clearances Determining Minimum Mantel Clearance When Using a Hood Mantel ClearancesFloor Clearances Determining Minimum Mantel ClearanceInstalling Damper Clamp Accessory for Vented Operation Installing Heater Base AssemblyChimney Minimum Permanent Height ft Flue Opening sq. ins Installation Items Needed Attaching Flexible Gas Hose to Heater Gas RegulatorConnecting to GAS Supply A. Design-Certified Manual Shutoff Valve With 1/8 NPT TapPressure Testing Heater Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Logs Installing Heat Majic One- Piece Log SetFor Your Safety Read Before Lighting Operating HeaterLighting Instructions Inspecting Burners Troubleshooting Observed Problem Possible Cause RemedyMaintenance, Top Gas leak. See Warning statement atCleaning and Maintenance Service HintsTechnical Service Cleaning Burner Injector Holder and Pilot AIR Inlet HoleAccessories Replacement PartsSpecifications Illustrated Parts Breakdown Heat Majic FVF18P FVF24P FVF30PODS Pilot Parts List FVF18P FVF24P FVF30PWarranty Information

FVF30P, FVF18P, FVF24P specifications

Desa FVF24P, FVF18P, and FVF30P are innovative products in the heating and ventilation sector, designed to meet diverse customer needs while optimizing performance. Each model has unique features and technologies that cater to various applications whether residential, commercial, or industrial.

Starting with the FVF24P, this model is renowned for its high efficiency and compact design. It is equipped with advanced modulation technology which allows the unit to adjust its output based on real-time demand. This results in reduced energy consumption and lower operating costs. The FVF24P also boasts an integrated smart control system that enables users to monitor and manage settings remotely via smartphone applications. This feature not only enhances convenience but also maximizes comfort by ensuring optimal temperature levels at all times.

Moving on to the FVF18P, this model is specifically engineered for smaller spaces or apartments where heating efficiency is paramount without compromising on space. It incorporates a unique heat exchanger that significantly increases heat transfer efficiency. Additionally, the FVF18P features a quiet operation mode, making it suitable for bedrooms or any noise-sensitive environments. Its compact size does not detract from its performance, as it offers a balanced air distribution system ensuring every corner receives adequate warmth.

The FVF30P, on the other hand, is a powerhouse designed for larger areas requiring robust heating capabilities. It supports a wider range of airflow settings and has an impressive BTU rating, making it ideal for vast commercial spaces or industrial applications. The inclusion of multiple safety features, such as overheat protection and automatic shut-off, underscores its design philosophy focused on user safety and reliability. Furthermore, the FVF30P is built to work with renewable energy sources, aligning with modern sustainability goals and reducing the environmental impact associated with traditional heating solutions.

In summary, the Desa FVF series presents a range of efficient heating solutions with the FVF24P, FVF18P, and FVF30P models catering to different power requirements and space constraints. With advanced technologies such as smart controls, enhanced heat exchangers, and safety features, these models are a testament to Desa’s commitment to quality, efficiency, and customer satisfaction in the heating market.