Desa FVF18P, FVF30P, FVF24P Troubleshooting, Observed Problem Possible Cause Remedy

Page 17

OWNER’S MANUAL

TROUBLESHOOTING

Note: For additional help, visit DESA International’s Technical Service web site at www.desatech.com.

Note: All troubleshooting items are listed in order of operation.

WARNING: Turn off and un- plug heater and let cool before servicing. Only a qualified ser- vice person should service and repair heater.

CAUTION: Never use a wire, needle, or similar object to clean ODS/pilot. This can damage ODS/ pilot unit.

OBSERVED PROBLEM

POSSIBLE CAUSE

REMEDY

When ignitor button is pressed, there is no

1.

Ignitor electrode not connected to igni-

1.

Reconnect ignitor cable

spark at ODS/pilot

 

tor cable

 

 

 

2.

Ignitor cable pinched or wet

2.

Free ignitor cable if pinched by any

 

 

 

 

metal or tubing. Keep ignitor cable dry

 

3.

Piezo ignitor nut is loose

3.

Tighten nut holding piezo ignitor to base

 

 

 

 

panel of log set. Nut is located behind

 

 

 

 

base panel.

 

4.

Broken ignitor cable

4.

Replace ignitor cable

 

5.

Bad piezo ignitor

5.

Replace piezo ignitor

 

6.

Ignitor electrode positioned wrong

6.

Replace ignitor

 

7.

Ignitor electrode broken

7.

Replace ignitor

 

 

 

 

 

When ignitor button is pressed, there is

1.

Gas supply turned off or manual shutoff

1.

Turn on gas supply or open manual

spark at ODS/pilot but no ignition

 

valve closed

 

shutoff valve

 

2.

Control knob not in PILOT position

2.

Turn control knob to PILOT position

 

3.

Control knob not pressed in while in

3.

Press in control knob while in PILOT

 

 

PILOT position

 

position

 

4.

Air in gas lines when installed

4.

Continue holding down control knob.

 

 

 

 

Repeat igniting operation until air is re-

 

 

 

 

moved

 

5.

Depleted gas supply

5.

Contact local propane/LP gas company

 

6.

ODS/pilot is clogged

6.

Clean ODS/pilot (see Cleaning and

 

 

 

 

Maintenance, page 20) or replace ODS/

 

 

 

 

pilot assembly

 

7.

Gas regulator setting is not correct

7.

Replace gas regulator

 

 

 

 

 

ODS/pilot lights but flame goes out when

1.

Control knob not fully pressed in

1.

Press in control knob fully

control knob is released

2.

Control knob not pressed in long enough

2.

After ODS/pilot lights, keep control

 

 

 

 

knob pressed in 30 seconds

 

3.

Safety interlock system has been triggered

3.

Wait one minute for safety interlock sys-

 

 

 

 

tem to reset. Repeat ignition operation

 

4.

Manual shutoff valve not fully open

4.

Fully open manual shutoff valve

 

5.

Pilot flame not touching thermocouple,

5.

A) Contact local propane/LP gas company

 

 

which allows thermocouple to cool,

 

 

 

 

causing pilot flame to go out. This prob-

 

B) Clean ODS/pilot (see Cleaning and

 

 

lem could be caused by one or both of

 

Maintenance, page 20 ) or replace ODS/

 

 

the following:

 

pilot assembly

 

 

A) Low gas pressure

 

 

 

 

B) Dirty or partially clogged ODS/pilot

 

 

 

6.

Thermocouple connection loose at con-

6.

Hand tighten until snug, then tighten 1/4

 

 

trol valve

 

turn more

 

7.

Thermocouple damaged

7.

Replace thermocouple

 

8.

Control valve damaged

8.

Replace control valve

www.desatech.com

Continued

 

105192

17

Image 17
Contents Patent Pending OWNER’S Operation and Installation ManualWhat to do if YOU Smell GAS Safety Information Product Identification Product FeaturesLocal Codes UnpackingProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation Air From Inside Ventilation AIRBuilding Ventilation Air From OutdoorsInstallation InstallationCheck GAS Type Minimum Wall and Ceiling Clearances see FigureMinimum Noncombustible Material Clearances If Using MantelIf Not Using Mantel Mantel Clearances Determining Minimum Mantel Clearance When Using a HoodFloor Clearances Determining Minimum Mantel ClearanceChimney Minimum Permanent Height ft Flue Opening sq. ins Installing Damper Clamp Accessory for Vented OperationInstalling Heater Base Assembly Attaching Flexible Gas Hose to Heater Gas Regulator Installation Items NeededA. Design-Certified Manual Shutoff Valve With 1/8 NPT Tap Connecting to GAS SupplyPressure Testing Gas Supply Piping System Pressure Testing Heater Gas ConnectionsChecking GAS Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Heat Majic One- Piece Log Set Installing LogsLighting Instructions For Your Safety Read Before LightingOperating Heater Inspecting Burners Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at TopService Hints Cleaning and MaintenanceTechnical Service Cleaning Burner Injector Holder and Pilot AIR Inlet HoleSpecifications AccessoriesReplacement Parts ODS Pilot Illustrated Parts BreakdownHeat Majic FVF18P FVF24P FVF30P FVF18P FVF24P FVF30P Parts ListWarranty Information

FVF30P, FVF18P, FVF24P specifications

Desa FVF24P, FVF18P, and FVF30P are innovative products in the heating and ventilation sector, designed to meet diverse customer needs while optimizing performance. Each model has unique features and technologies that cater to various applications whether residential, commercial, or industrial.

Starting with the FVF24P, this model is renowned for its high efficiency and compact design. It is equipped with advanced modulation technology which allows the unit to adjust its output based on real-time demand. This results in reduced energy consumption and lower operating costs. The FVF24P also boasts an integrated smart control system that enables users to monitor and manage settings remotely via smartphone applications. This feature not only enhances convenience but also maximizes comfort by ensuring optimal temperature levels at all times.

Moving on to the FVF18P, this model is specifically engineered for smaller spaces or apartments where heating efficiency is paramount without compromising on space. It incorporates a unique heat exchanger that significantly increases heat transfer efficiency. Additionally, the FVF18P features a quiet operation mode, making it suitable for bedrooms or any noise-sensitive environments. Its compact size does not detract from its performance, as it offers a balanced air distribution system ensuring every corner receives adequate warmth.

The FVF30P, on the other hand, is a powerhouse designed for larger areas requiring robust heating capabilities. It supports a wider range of airflow settings and has an impressive BTU rating, making it ideal for vast commercial spaces or industrial applications. The inclusion of multiple safety features, such as overheat protection and automatic shut-off, underscores its design philosophy focused on user safety and reliability. Furthermore, the FVF30P is built to work with renewable energy sources, aligning with modern sustainability goals and reducing the environmental impact associated with traditional heating solutions.

In summary, the Desa FVF series presents a range of efficient heating solutions with the FVF24P, FVF18P, and FVF30P models catering to different power requirements and space constraints. With advanced technologies such as smart controls, enhanced heat exchangers, and safety features, these models are a testament to Desa’s commitment to quality, efficiency, and customer satisfaction in the heating market.