Desa VN2800BTD, VN2000BTD installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 6

®

BLUE FLAME NATURAL GAS HEATER

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see op-

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

tion 3, Figure 2). Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

12"

Figure 2 - Ventilation Air from Inside Building

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 3 - Ventilation Air from Outdoors

6

104402

Image 6
Contents Blue Flame VENT-FREE Natural GAS Heater What to do if YOU Smell GASSafety Information Blue Flame Natural GAS HeaterLocal Codes Product FeaturesProduct Identification UnpackingUnusually Tight Construction AIR for Combustion and VentilationProviding Adequate Ventilation Confined and Unconfined SpaceAIR for Combustion Ventilation Determining FRESH-AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space Ventilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationInstallation Items Locating HeaterInstalling Heater to Wall Installing Bottom Mounting Screws Attaching Mounting Bracket To WallPlacing Heater On Mounting Bracket Connecting to GAS Supply Typical Inlet Pipe DiametersPressure Testing Heater Gas Connections For Your Safety Read Before LightingPressure Testing Gas Supply Piping System Operating HeaterTo Turn OFF GAS To Appliance Manual Lighting ProcedureLighting Instructions Thermostat Control OperationCleaning and Maintenance Inspecting BurnerTroubleshooting Observed Problem Possible Cause RemedyMaintenance, Top Gas leak. See Warning statement atAccessories SpecificationsReplacement Parts Technical ServiceODS/Pilot Assembly Illustrated Parts BreakdownVN2000BTD VN2800BTD Parts List Under Replacement Parts on page 17 of this manualWarranty Information

VN2000BTD, VN2800BTD specifications

The Desa VN2800BTD and VN2000BTD are two advanced space heaters that represent the pinnacle of technology and design in the heating industry. Both models are engineered for efficiency, ensuring warmth and comfort in various settings, from homes to workshops.

One of the primary features of the VN2800BTD and VN2000BTD is their versatility in application. They are ideal for supplemental heating, capable of warming up rooms quickly and effectively with an easy-to-use design. The VN2800BTD boasts an output of 28,000 BTUs, while the VN2000BTD offers a slightly lower but still robust output of 20,000 BTUs. This makes them suitable for a diverse range of spaces and heating needs.

A key characteristic of these models is their advanced technology, which includes a forced air heating mechanism. This system allows heated air to circulate rapidly throughout the room, providing even warmth without the cold spots often found in traditional heaters. Both units are fueled by propane, making them highly efficient and eco-friendly compared to electric options.

Safety is another significant aspect of the Desa VN2800BTD and VN2000BTD. These models are equipped with automatic shut-off features that activate in case of a malfunction or if the heater tips over. Additionally, they have built-in oxygen depletion sensors that monitor air quality, ensuring safe operation in enclosed spaces. This focus on user safety reflects Desa's commitment to providing reliable heating solutions.

The design of the VN2800BTD and VN2000BTD is pragmatic and attractive, allowing them to blend seamlessly into any environment. They come with a durable construction that ensures longevity, even under demanding conditions. Portability is another benefit; both models often feature handles or wheels that make it easy to transport them from one area to another, enhancing their utility.

Easy ignition systems are another highlight, with many units incorporating a piezo ignition feature that allows for quick and reliable starts. This user-friendly approach minimizes the hassle often associated with traditional heating methods.

In summary, the Desa VN2800BTD and VN2000BTD heaters are exemplary products that combine powerful heating capabilities with safety and user convenience. Their advanced technology and thoughtful features make them an outstanding choice for anyone looking to enhance their comfort through effective space heating solutions.