Ariston Unvented Hot Water Storage Cylinders manual Worked Example, Maximum

Page 11

www.tradeplumbing.co.uk Call Sales On 08708034288

connected. If unvented hot water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings occupied by the blind, infirm or disabled people, consideration should be given to the installation of an electronically operated device to warn when discharge takes place. Note: The discharge will consist of scalding water and steam. Asphalt, roofing felt and non-metallic rainwater goods may

Temperature & pressure

Metal discharge pipe (D1) from

relief valve

temperature & pressure relief valve.

 

to tundish.

Tundish

500mm Max.

300mm

Min.

Metal discharge pipe (D2) from tundish with continuous fall. See Table 2 and worked example.

FIG. 2.9

Discharge below fixed grating. (see page 10 for alternative points of discharge).

Fixed grating

Trapped gulley

TABLE 2. Sizing of copper discharge pipe “D2” for common temperature valve outlet sizes.

Valve outlet size

Minimum size of

Minimum size of

Maximum

Resistance created

 

discharge pipe D1*

discharge pipe D2*

resistance allowed,

by each elbow or

 

 

from tundish

expressed as a

bend

 

 

 

length of pipe (i.e.

 

 

 

 

no elbow or bends)

 

 

 

 

 

 

G 1/2

15mm

22mm

Up to 9m

0.8m

 

 

28mm

Up to 18m

1.0m

 

 

35mm

Up to 27m

1.4m

G 3/4

22mm

28mm

Up to 9m

1.0m

 

 

35mm

Up to 18m

1.4m

 

 

42mm

Up to 27m

1.7m

G 1

28mm

35mm

Up to 9m

1.4m

 

 

42mm

Up to 18m

1.7m

 

 

54mm

Up to 27m

2.3m

be damaged by such discharges.

WORKED EXAMPLE

The example below is for a G 1/2 temperature & pressure relief valve with a discharge pipe (D2) having 4 no. elbows and length of 7m from the tundish to the point of discharge.

From TABLE 2;

Maximum resistance allowed for a straight length of 22mm copper discharge

pipe (D2) from G 1/2 temperature & pressure valve is 9m. Subtract the resistance www.tradeplumbing.forco4 no.uk. 22mmCallelbowsSalesat 0.8m eachOn= 3.2m08708034288. Therefore the maximum permitted length equates to: 5.8m. As 5.8m is less than the actual length of 7m therefore

11

Image 11
Contents Unvented Hot Water Storage Cylinders Table of Contents Ariston range is available in the following options Information personnelInstallation Overall Dimensions STD Protech STD/STD PROTECH/ITD 125-150-210-300 Direct For floor standing modelsPlease check this before making any connection to the unit ST ProtechSTD Protech STI/STI PROTECH/ITI 125-150-210-300 IndirectSTI Protech Expansion relief valve must be accounted for Call Sales On Secondary Return Discharge Pipework Maximum Worked Example240V~ Protech Electronic ANTI-CORROSION SystemDirect Systems Information for the END UserThermostat Indirect Systems Wiring Scheme for 2 X 2 Port Motorised ValvesVaillant Caradon IdealGlowworm Keston PottertonPage Trouble-shooting MaintenanceImmersion Heaters Magneisum Anodes Classico model onlyThermal Cut-outs Thermostats Unvented ControlssFault Possible Causes Remedy Fault FindingTechnical Information CallPage Manufacturer MTS Benelux sa/nv Belgium Technical Service Hot Line 0870 241