AquaStar 125HX NG, 125HX LP Maintenance and Service, Trouble Shooting, Not enlarge the orifice

Page 13

MAINTENANCE AND SERVICE

REVIEW MAINTENANCE TABLE ON THE BACK OF THIS MANUAL.

Approximately once a year, the 125 HX should be checked and cleaned. To remove the front cover, first remove the incandescent particle tray, then pull off the temperature adjustment knob and unscrew and remove the plastic collar. Pull main cover out toward you and lift up and out. THE FOLLOWING OPERATIONS SHOULD BE PERFORMED BY A QUALIFIED SERVICE PERSON:

Vent System: Should be checked annually. Clean and repair as needed.

Water Valve (Part # 8707002649): The water valve on this heater should be serviced periodically. Lubricate component 36 on page 18 with a small amount of silicon, faucet or lithium grease every two years to keep its o rings fresh and pushrod sliding smoothly. Every 3-5 years replace component 36 on page 18. The frequency will depend on the mineral content of the water and conditions of use or whenever signs of corrosion appear at the gas and water valve joint. Periodically check that the water inlet filter (#27 on page

18)is clean as well. NOTE: If water valve is removed, be sure to also inspect the o ring seal on the end of the right hand side water pipe before re-installing. Lubricating the o ring with lithium or faucet and valve grease is recommended.

Pilot Flame: The pilot flame should burn with a clean, sharp, blue flame and should resemble the diagram in Fig. 10. If the flame is soft and yellow, the pilot burner orifice may need to be cleaned or replaced. The pilot flame should be approximately 2 inches long, extending past the flame sensor. If the flame is too small, it will not reach the flame sensor and the burners will not come on.

3mm

Correct gap between pilot burner tip and electrode tip

Piezo Electrode

Flame sensor

Piezo

Fig. 10 - Characteristic Pilot Flame

(Pilot assembly shown without pilot hood)

To clean the pilot burner and/ or the pilot orifice : Turn off the gas to the unit. Set the On/Off switch to Off (position ). Remove the cover of the heater. To do so, pull off the temperature adjustment knob and unscrew and remove the plastic collar. Pull main cover out toward you and lift up and out. The pilot orifice should be cleaned or replaced. Do

not enlarge the orifice.

Do not use any wire or sharp object to clean orifices. Natural gas orifices are large enough that you can usually clean them by blowing through them. LP orifices, on the other hand, are too small to clean and should be replaced.

To access the pilot orifice, remove 2 screws holding pilot assembly in place. Then loosen compression fittings to expose pilot orifice.

PILOT ORIFICE

Fig. 11 - Pilot burner with pilot orifice (Pilot assembly shown without pilot hood)

Main Burner Flames: The main burner flames should be blue, with a more intense blue cone in the center core. Yellow flames could be a sign of wrong size gas orifices or dirty burners, or a blockage on the heat exchangers fins. If some burners have yellow flames while others have good flames, it is likely that dust, lint or spider webs have partially clogged the burner venturis. To clean the burners, contact a gas service person.

Mineral Scale Build-up: The 125 HX heater, when operated at lower temperature settings, does not accumulate mineral build-up. If however, the heater is used at the higher temperature settings and the water has a high mineral content, periodic descaling may be necessary. The heating coils should be flushed with a descaling solution. The descaling is done only to the heat exchanger. The chemicals will damage the hydro-generator and other parts. Consult your service person.

TROUBLE SHOOTING

Introduction

The AquaStar 125 HX burners are activated by a water flow valve. Numerous water related problems can cause this water valve to malfunction such as: Insufficient water flow volume to activate the burners at its minimum flow requirement; Dirt in the water flow valve causing it to malfunction; Sediment build-up in faucet aerators, or shower heads; Uneven pressures between cold and hot. (with single lever faucets) Plumbing cross overs. These water flow related problems can cause the heater to deliver less than its full output, or to fail to ignite or to shut down completely.

6 720 606 804

13

Image 13 Contents
Table of Contents For Your SafetyWhat to do if YOU Smell GAS 720 606 Unpacking the 125 HX Heater FeaturesPrinciple of Operation Required Natural Gas Pressure at inletModel 125HX General Rules to Follow For Safe Operation Proper Location for Installing Your HeaterCombustion AIR Requirements Mounting InstallationClearances Plasterboard, can cause failure of mounting VentingVent pipe connection Existing Interior Masonry Chimney Masonry ChimneysTile Lined Interior Masonry Chimney GAS Line Sizing GAS Connections 6 Adaptor Used on High Altitude For LP GAS For Natural GASSource National Fuel Gas Code Nfpa 54, Ansi Z223.1 Operating Instructions Water ConnectionsLighting and Operating Instructions Setting the Water TemperatureTo Turn OFF GAS to Appliance Trouble Shooting Maintenance and ServiceReview Maintenance Table on the Back of this Manual Not enlarge the orificeNo Spark AT the Pilot Pilot Lights but Burners will not Come on Ground water temperature is very warmMain Burners GO OUT During HOT Water USE Water is TOO HOTHOT Water Temperature Fluctuates / Unit Deactivated Diagram of 125 HX Interior Components Diagram and Parts List Interior Components Diagram Parts List 125 HX Flow chart of 125 HX General Twelve Year Limited Warranty720 606 720 606 BBT North America Maintenance Table see