AquaStar 125HX LP, 125HX NG specifications Masonry Chimneys, Existing Interior Masonry Chimney

Page 8

MASONRY CHIMNEY: Masonry chimneys shall be built and installed in accordance with NFPS 211 or local codes. A minimum 5” diameter gas vent pipe (metal double wall Type B), or an approved clay flue liner or a listed chimney lining system must be used when venting into a naturally drafting, internal masonry chimney. 6 inch is required in elevations greater than 2000 feet, see Fig. 4. Local codes may require the use of both gas vent and an approved lining system when venting into a masonry chimney. The Commonwealth of Massachusetts requires the use of a listed liner. Lining systems include approved clay flue lining, a listed chimney lining system or other approved material that will resist corrosion, erosion, softening, or cracking from exhaust flue gases at temperatures up to 1800 degrees F. The lining system must be listed for use with naturally drafting, draft hood equipped gas appliances. Follow local codes and refer to NFGC 54 and NFPA 58.

When connecting the water heater to a masonry chimney the following connector guidelines must be followed for safe and proper operation: An approved gas vent connector must be attached to the top of the water heater and rise vertically at least 12” before entering into an approved gas vent connector elbow. Any gas vent section that is greater than 45 degrees from the vertical is considered horizontal. If a horizontal vent connector is to be used to connect the vertical gas vent connector on the top of the water heater to the masonry chimney, that approved horizontal gas vent connector must be kept as short as possible and must be sloped upwards at least ¼” per foot of its length. This connector must be supported throughout its horizontal length. This horizontal gas vent connection may be no greater than 75% of the total vertical gas flue vent within the chimney. Also, an approved thimble or collar must be used when penetrating a masonry chimney.

A) Existing INTERIOR Masonry Chimney

The metal gas vent pipe should be permanently mounted inside the masonry chimney. Double wall Type B gas vent is recommended. The masonry chimney may have to be tile or metal lined before the insertion of the gas vent pipe; check local codes for clarification. The lining material must be listed for use only with naturally drafting, draft hood equipped gas appliances. Follow manufactures instructions for installation of listed lining material. You may not vent any other fuel burning appliances into any free space remaining in the chimney. The minimum vertical gas vent length within the masonry chimney should be no less than 5 ft (1.5 m); the vent terminator should extend at least 3 feet (0.9 m) above where the chimney meets the roofline and at least 2 feet (0.6 m) higher than any vertical wall or similar obstruction within 10 feet (3.1 m). The top of the gas vent should have an approved vent terminator. See Figure C.

B) Tile Lined INTERIOR Masonry Chimney

The masonry chimney must have an approved liner, ceramic tile, clay or metal. The masonry chimney must be able to accommodate the spent fuel gasses; consult a venting HVAC contractor for chimney capacity. A common venting like-fuel appliance into this lined masonry chimney is permissible. The chimney’s diameter must be large enough to adequately draft the spent fuel gasses. A venting HVAC contractor will be required to spec a chimney system. The

minimum vertical chimney length should be no less than 5 ft (1.5 m); the termination point should extend at least 3 feet (0.9 m) above where the chimney meets the roofline and at least 2 feet (0.6 m) higher than any vertical wall or similar obstruction within 10 feet (3.1 m). See Figure C.

C) EXTERIOR masonry Chimney

Refer to the National Fuel Gas Code and consult a local venting HVAC contractor.

MASONRY CHIMNEYS

Listed vent cap

Gas vent

Vent connector

Establish a one foot rise before any elbows

Figure C

To check the draft:

Close all doors and windows to the outside.

Turn on all appliances that force air out of the building. These include all exhaust/ventilation fans, furnaces, clothes dryers, wood burning stoves, etc.

Open all doors between the 125 HX and these other appliances.

With the control knob set fully clockwise and strong hot water flow rate, run the unit for at least 10 minutes. The 125 HX is equipped with a Flue Gas Sensor; it’s mounted on the right side of the draft diverter (Flue Gas Sensor #34 on page 17). If the main burners shut off during this test it is because the Flue Gas Sensor has detected inadequate venting. This is a serious health hazard and must be corrected. Poor venting can result in soot building up inside the heater, overheating of the heater and freezing of the heat exchanger in a freezing environment, which is all a result of negative air flow. Additional combustion air and/or improved venting will be necessary to correct this.

WARNING

Note: The burners of an instantaneous “on demand” water heater such as the 125 HX are only on at the time that hot water is actually being used, the vent pipe is therefore cold except for the short durations when hot water is being used, it is therefore very important that the venting and air supply be adequate to provide a good positive draft as soon as the burners turn on.

The 125 HX instantaneous water heaters have built-in draft diverters and are designed for indoor installation only. The

8

6 720 606 804

Image 8
Contents What to do if YOU Smell GAS For Your SafetyTable of Contents 720 606 Features Unpacking the 125 HX HeaterPrinciple of Operation Required Natural Gas Pressure at inletModel 125HX Proper Location for Installing Your Heater General Rules to Follow For Safe OperationClearances Mounting InstallationCombustion AIR Requirements Vent pipe connection VentingPlasterboard, can cause failure of mounting Tile Lined Interior Masonry Chimney Masonry ChimneysExisting Interior Masonry Chimney 6 Adaptor Used on High Altitude GAS ConnectionsGAS Line Sizing Source National Fuel Gas Code Nfpa 54, Ansi Z223.1 For Natural GASFor LP GAS Water Connections Operating InstructionsTo Turn OFF GAS to Appliance Setting the Water TemperatureLighting and Operating Instructions Maintenance and Service Trouble ShootingReview Maintenance Table on the Back of this Manual Not enlarge the orificeNo Spark AT the Pilot Ground water temperature is very warm Pilot Lights but Burners will not Come onMain Burners GO OUT During HOT Water USE Water is TOO HOTHOT Water Temperature Fluctuates / Unit Deactivated Diagram of 125 HX Interior Components Diagram and Parts List Interior Components Diagram Parts List 125 HX Flow chart of 125 HX Twelve Year Limited Warranty General720 606 720 606 Maintenance Table see BBT North America

125HX LP, 125HX NG specifications

The AquaStar 125HX NG and 125HX LP are highly efficient gas tankless water heaters designed to meet the demands of modern households. With their compact size and advanced technology, these units provide an endless supply of hot water while maintaining energy efficiency. Both models cater to natural gas and propane applications, making them versatile options for various installations.

One of the standout features of the AquaStar 125HX series is its ability to deliver a powerful output of up to 199,000 BTUs, ensuring that multiple hot water outlets can operate simultaneously without a drop in temperature. Users can enjoy the convenience of hot showers, laundry, and dishwashing all at once, making it an ideal choice for busy families or households with high hot water needs.

These models incorporate a sophisticated modulating gas valve that adjusts the gas flow based on the demand for hot water. This technology not only optimizes energy consumption but also contributes to extended unit life by minimizing wear and tear on the components. The AquaStar 125HX units also come equipped with a patented electronic ignition system, which eliminates the need for a standing pilot light and reduces gas consumption.

Furthermore, the AquaStar 125HX NG and 125HX LP feature a durable heat exchanger constructed from high-grade copper, which enhances thermal efficiency and prevents corrosion. This ensures a longer lifespan and increased reliability for homeowners. Additionally, the units are compact and wall-mounted, allowing for flexible installation in various spaces, including tight utility closets or outside walls.

Safety is also a top priority, with built-in overheat protection and a freeze protection feature that ensures the unit remains operational even in colder climates. The AquaStar 125HX series operates quietly, allowing users to enjoy the benefits of hot water without the disruptive noise commonly associated with traditional water heaters.

In summary, the AquaStar 125HX NG and 125HX LP are leading choices in the tankless water heater market, combining efficiency, reliability, and innovation. Their impressive output, advanced technologies, and compact design make them suitable for modern living, ensuring homeowners have access to hot water whenever they need it. With these features, AquaStar continues to set a high standard in water heating solutions.