AquaStar 125B NGS GAS Line Sizing For Natural GAS, For LP GAS, Maximum Capacity of Semi-Rigid

Page 10

GAS CONNECTIONS and Gas Regulator

NOTE: The Aquastar 125 B”S” is supplied with a gas pressure regulator that must be installed on the heater before attaching the gas supply line. See figure 5. Failure to install the gas regulator as shown in figure 5 will be a violation of CSA certification of the unit. The regulator supplied with the heater is preset for the gas shown on the rating plate to the correct pressure. It is an appliance level regulator designed for (low inlet) pressure (less than 1/2 Psig or 15” W.C.) DO NOT connect to an unregulated or high pressure propane line or to a high pressure commercial natural gas line.

GAS LINE SIZING

FOR NATURAL GAS

Maximum Capacity of pipe in Cubic Feet of Gas per Hour for Gas Pressure of 0.5 Psig or less and a Pressure drop of 0.3 in Water Column.

(Based on a 0.60 Specific Gravity Gas) Btu numbers given in thousands.

Follow boxed numbers for piping just one Aquastar 125BS (example: 3/4” B.I. Natural Gas pipe for 30 ft. will handle 152,000 btu’s). For multiple appliances combine the total btu input load and then refer to applicable chart below.

Nominal

 

 

 

 

 

 

 

 

 

 

 

 

Iron

 

 

 

 

 

 

 

 

 

 

 

 

Pipe

Internal

 

 

 

 

Length of Black Iron Pipe, Feet

 

 

Size,

Diameter

 

 

 

 

 

 

 

 

 

 

 

inches

inches

10

20

30

40

50

60

70

80

90

100 125

150 175 200

1/4

3/8

1/2

3/4

1

11/4

11/2

2

21/2

3

4

0.364

0.493

0.622

0.824

1.049

1.380

1.610

2.067

2.469

3.068

4.026

32

22

18

15

72

49

40

34

132

92

73

63

 

 

 

 

278

190

152

130

520

350

285

245

1050

730

590

500

1600

1100

890

760

3050

2100

1650

1450

4800

3300

2700

2300

8500

5900

4700

4100

17,500

12,000

9,700

8,300

14

12

11

11

10

9

8

8

7

6

30

27

25

23

22

21

18

17

15

14

56

50

46

43

40

38

34

31

28

26

115

105

96

90

84

79

72

64

59

55

215

195

180

170

160

150

130

120

110

100

 

 

 

 

 

 

 

 

 

 

440

400

370

350

320

305

275

250

225

210

670

610

560

530

490

460

410

380

350

320

1270

1150

1050

990

930

870

780

710

650

610

2000

1850

1700

1600

1500

1400

1250

1130

1050

980

3600

3250

3000

2800

2600

2500

2200

2000

1850

1700

7,400

6,80

6,200

5,800

5,400

5,100

4,500

4,100

3,800

3500

FOR LP GAS

Maximum Capacity of Pipe in Thousands of BTU per Hour of Undiluted Petroleum Gases (at 11 inches Water Column Inlet Pressure) (Based on a Pressure Drop of 0.5 Inch Wa- ter Column).

Fig. 4

nominal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Iron Pipe

 

 

 

 

 

Black Iron Pipe

 

 

 

 

 

 

Size,

 

 

 

 

 

Length of Pipe, Feet

 

 

 

 

 

Inches

10

20

30

40

50

60

70

80

90

100

125

150

 

 

 

 

 

 

129

114

103

96

89

83

78

69

63

 

 

1/2

275

189

152

 

 

3/4

567

693

315

 

 

 

 

 

 

 

 

 

 

 

 

267

237

217

196

185

173

162

146

132

 

 

1

107

732

590

 

504

448

409

378

346

322

307

275

252

 

1 1/4

220

149

121

103

913

834

771

724

677

630

567

511

 

1 1/2

330

229

185

155

141

127

118

108

102

976

866

787

 

2

622

433

346

299

264

239

220

204

192

1811

1606

1496

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside

 

 

 

 

 

Copper

 

 

 

 

 

 

 

Diameter,

 

 

 

 

Length of Tubing, Feet

 

 

 

 

 

Maximum Capacity of Semi-Rigid

Inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

20

30

40

50

60

70

80

90

100

 

Tubing in Thousands of BTU per Hour of

 

 

 

 

 

 

 

 

 

 

 

 

3/8

39

26

21

19

_

_

_

_

_

_

 

Undiluted Liquified Petroleum Gases (at 11

1/2

92

62

50

41

37

35

31

29

27

26

 

inches Water Column Inlet Pressure)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5/8

 

199

131

107

90

79

72

67

62

59

55

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Based on a Pressure Drop of 0.5 Inch Water

 

3/4

329

216

 

181

145

131

121

112

104

95

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7/8

501

346

277

233

198

187

164

155

146

138

 

Column)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Source National Fuel Gas Code NFPA 54, ANSI Z223.1 - No Additional Allowance is necessary for an ordinary number of fittings

10

6 720 606 518

Image 10
Contents For Your Safety Table of ContentsUnpacking the Aquastar Heater FeaturesRequired Natural Gas Pressure at inlet tap Model 125BS Front View Side ViewTOP a Front B Back Sides Floor C Vent Diameter Proper Location for Installing Your Heater General Rules to Follow For Safe OperationCombustion AIR Requirements ClearancesMounting Installation Aquastar 125 B S is design certified for mounting on a wallVenting Figure aMasonry Chimneys Figure C 720 606Vent Adaptor for High Altitude Installations 6 Adaptor Used on High AltitudeMaximum Capacity of Semi-Rigid GAS Line Sizing For Natural GASFor LP GAS ColumnWater Connections Maximum Inlet GAS Flow Pressure SettingGAS Line Sizing Above 4.500 ft consult your local gas supplierWhat to do if YOU Smell GAS For Your Safety Read Before Lighting the PilotOperating Instructions To Turn OFF GAS to ApplianceMaintenance and Service Pilot burner with air screen/ pilot orificePilot Light will not Light Pilot Lights but Flame Goes OUT When Button is ReleasedAir in the Gas Line Water is TOO HOT Burners do not Ignite When HOT Water is Turned onGas pressure too low Water is not HOT EnoughHOT Water Temperature Fluctuates / Unit Deactivated Unbalanced pressure in waterlinesDiagram of AquaStar 125 BS Interior Components Diagram and Parts List Interior Components Diagram Parts List 125BS Flow chart of Aquastar 125 BS Limited Warranty General720 606 720 606 Bosch Group BBT North AMERICA, Waitsfield, VT all rights reserved