AquaStar 125B NGS GAS Line Sizing, Water Connections, Maximum Inlet GAS Flow Pressure Setting

Page 11

GAS INLET PIPE

PRESSURE TAP

PLASTIC VENT CAP

PRESSURE REGULA- TOR

(with directional arrow on reverse side pointing upward)

Fig. 5 - Installation of Gas Pressure Regulator

The pressure regulator provided with the heater is adjusted to deliver the proper gas pressure (as indicated on the rating plate and in the manual for altitude up to 2000 feet (660 meters) above sea level. On appliances being installed above 2000 ft (660 meters) elevation, the inlet gas pressure should be set at installation to the value shown below.

NOTE: The gas pressures specified below refer to pressures taken at the test pressure tap on the gas inlet pipe just above the regulator (See Fig 5). These readings should be taken while the heater is operating at full input

i.e. maximum water flow with the temperature dial selector turned all the way clockwise.

MAXIMUM INLET GAS FLOW PRESSURE SETTING

Altitude

Natural Gas

Liquid Propane

 

inches W.C:

inches W.C:

0' - 2.000 ft

5.7"

10.5"

2.000 ft - 4.500 ft

4.6"

8.4"

Above 4.500 ft consult your local gas supplier.

GAS LINE SIZING

-It is strongly recommended that the Natural Gas pipe be Black Iron pipe the entire distance from the outside meter to the inlet of the Aquastar regulator. 1/2” Black Iron pipe up to 10 feet, 3/4” Black Iron pipe up to 40 feet and 1” Black Iron pipe up to 150 feet distances. Flex line tubing is NOT recommended, but if used then oversize it.

-It is strongly recommended that the LP Gas pipe be semi-rigid copper or Black Iron pipe from the outside regulator to the inlet of the Aquastar regulator. For semi- rigid copper piping: 5/8” up to 20 feet and 3/4” up to 60 feet distances. For Black Iron piping: 1/2” up to 45 feet and 3/4” up to 160 feet distances. Flex line tubing is NOT recommended, but if used then oversize it.

THESE FIGURES ARE FOR AQUASTAR SUPPLY ONLY, ALL OTHER APPLIANCES IN THE BUILDING WILL NEED TO BE INCLUDED IN THE PIPE SIZING.

National Fuel Gas Code requires that a sediment trap (drip leg) be installed on gas appliances not so equipped. The drip leg must be accessible and not subject to freezing conditions. Install in accordance with the recommendations of the serving gas supplier.

WARNING: The heater must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 0.5 psig.

The water heater must be isolated from the gas supply piping system by closing the manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or more than 0.5 psig.

The water heater, including the pressure regulator provided with it, must not be operated at gas supply pressures in excess of 0.5 psig. If overpressure has occurred, such as through improper testing of the gas lines or malfunction of the supply system, the gas valve and regulator must be checked for safe operation. Make sure that the regulator vent is protected against blockage.

When your connections are made, check for gas leaks at all joints (not just the ones you made). Apply some soapy water to all gas fittings and gas valve. Soap bubbles are a sign of a leak.

NOTE: Do not apply soap solution to pilot filter screen or pilot orifice area. If you have a leak, shut off the gas. After verifying that required gaskets are in place, tighten appropriate fittings to stop leak. Turn the gas on and check again with a soapy solution. Never test for gas leaks using a match or flame.

WATER CONNECTIONS

Install the heater centrally in the building if possible and make hot water piping runs as short as possible When facing the heater, the cold water inlet will be on the right and the hot water outlet on the left..

Although water piping throughout the building may be other than copper, copper or galvanized piping should be used when connecting to the heaters ½” male NPT flex connectors (follow local codes if more stringent). Plastics or other PEX type plumbing line materials are not suitable for connecting directly to the water heater. Keep water inlet pipe to no less than ½” (19.05mm) diameter to allow the full flow capacity. If the cold and hot connections to the heater are reversed, the heater will not function.

The Aquastar 125BS is provided with two flexible type connectors that must be connected to the fittings of the water valve as shown in Fig. 6. The union end of the flexible connectors should be attached to the rear inlet ports of the water valve with the supplied washer gaskets. No pipe dope or thread tape is to be used at these joints.

Be certain there are no loose particles or dirt in the piping. Blow out or flush the lines before connecting to the water heater. Full port valves should be installed on both the cold water supply and hot water outlet lines to facilitate servicing the heater (see Fig. 7). For installation on a private well system with the use of a pressure tank, the lowest pressure range setting recommended is 30-50 psi (2.07-3.45 bar).

INLET

WASHER

WATER FILTER

WATER VALVE

FLEX

CONNEC-

TORS

WASHER

OUTLET

Fig. 6 - Water valve and water connectors, top view

6 720 606 518

11

Image 11
Contents Table of Contents For Your SafetyRequired Natural Gas Pressure at inlet tap FeaturesUnpacking the Aquastar Heater TOP a Front B Back Sides Floor C Vent Diameter Front View Side ViewModel 125BS General Rules to Follow For Safe Operation Proper Location for Installing Your HeaterClearances Combustion AIR RequirementsAquastar 125 B S is design certified for mounting on a wall Mounting InstallationFigure a VentingFigure C 720 606 Masonry Chimneys6 Adaptor Used on High Altitude Vent Adaptor for High Altitude InstallationsColumn GAS Line Sizing For Natural GASFor LP GAS Maximum Capacity of Semi-RigidAbove 4.500 ft consult your local gas supplier Maximum Inlet GAS Flow Pressure SettingGAS Line Sizing Water ConnectionsTo Turn OFF GAS to Appliance For Your Safety Read Before Lighting the PilotOperating Instructions What to do if YOU Smell GASPilot burner with air screen/ pilot orifice Maintenance and ServiceAir in the Gas Line Pilot Lights but Flame Goes OUT When Button is ReleasedPilot Light will not Light Water is not HOT Enough Burners do not Ignite When HOT Water is Turned onGas pressure too low Water is TOO HOTUnbalanced pressure in waterlines HOT Water Temperature Fluctuates / Unit DeactivatedDiagram of AquaStar 125 BS Interior Components Diagram and Parts List Interior Components Diagram Parts List 125BS Flow chart of Aquastar 125 BS General Limited Warranty720 606 720 606 BBT North AMERICA, Waitsfield, VT all rights reserved Bosch Group