A.O. Smith 315456-002, GAHH-40, GAHH-50 Clearances and Accessibility, State of California

Page 8

IMPORTANT: The water heater should be located in an area where leakage of the tank or connections will not result in damage to the area adjacent to the water heater or to lower floors of the structure. Due to the normal corrosive action of water, the tank will eventually leak after an extended period of time. Also any external plumbing leak, including those from improper installation, may cause early failure of the tank due to corrosion if not repaired. If the homeowner is uncomfortable with making the repair a qualified technician should be contacted. A suitable metal drain pan should be installed under the water heater as shown below, to help protect the property from damage which may occur from condensate formation or leaks in the piping connections

or tank. The pan must limit the water level to a maximum depth of 1-3/4” and be two inches wider than the heater and piped to an adequate drain. Locate the water heater near a suitable indoor drain. Outside drains are subject to freezing temperatures which can obstruct the drain line. The piping should be at least 3/4” ID and pitched for proper drainage.

FIGURE 1B.

Pipe to an

 

adequate drain

1-3/4”

max.

At least 2” greater

than the water heater.

Water heater life depends upon water quality, water usage, water temperature and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a metal drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped metal drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:

EXHAUST FAN

REVERSE FLOW

OF GASES

FIGURE 2.

Clearances and Accessibility

NOTE: Minimum clearances from combustible materials are stated on the label on the front of the heater adjacent to the gas control valve/thermostat of the water heater.

The water heater is certified for installation on a combustible floor.

IMPORTANT: If installing over carpeting, the carpeting must be protected by a metal or wood panel beneath the water heater. The protective panel must extend beyond the full width and depth of the water heater by at least five inches (127mm) in any direction; or if in an alcove or closet installation, the entire floor must be covered by the panel.

Figure 2A may be used as a reference guide to locate the specific clearance locations. A minimum of 5 inch- es of front clearance should be provided for inspection and service.

 

 

 

6” min. at

 

 

 

Single Wall

12” min.

 

 

Vent Pipe

 

 

 

 

 

Top to

 

 

 

 

 

 

Ceiling

 

 

0” min. Back

0” min. Sides

0” min. Air Inlet Chamber

5” min.

Front

Top View

• Sensors mounted in the metal drain pan that trigger an

alarm or turn off the incoming water to the water heater

Minimum Clearance Locations

when water is detected.

 

Sensors mounted in the metal drain pan that turn off the water supply to the entire home when water is detected in the metal drain pan.

Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater.

Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply.

FIGURE 2A.

State of California

NOTE: The water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area, visit http:// www.dsa.dgs.ca.gov, or call 1-916-445-8100 and request instructions.

8

Image 8
Contents Residential GAS Water Heaters Table of Contents Safe INSTALLATION, USE and Service Safety PrecautionsFire or Explosion Hazard Typical Installation GET to Know Your Water Heater GAS ModelsInstalling Your GAS Water Heater Unpacking the Water Heater Excessive Weight HazardImportant Information About This Water Heater Consumer InformationCarbon Monoxide Poisoning Hazard Location RequirementsSite Location Clearances and Accessibility State of CaliforniaGas Pressure Testing GAS SupplyGas Requirements Gas PipingGas Pipe Capacity Table Combustion AIR & Ventilation Unconfined SpaceConfined Space Minimum Btuh InputLouvers and Grilles All Air from Inside the BuildingAll Air from Outdoors Draft Hood Installation Vent Pipe SystemVent Connectors Vent Pipe SizeChimney Connection Vertical Exhaust Gas VentPiping Installation Water System PipingTemperature and Pressure Relief Valve Closed System/Thermal ExpansionTemperature & Pressure Relief Valve Relief Valve and Pipe InsulationCombination Space Heating/Potable Water System Discharge LineElectrical Connections Solar InstallationWiring Diagram Installation Checklist Important Information about this Water HeaterOperating Your Water Heater Operating InstructionsBurn Hazard Water Heater OperationChecking the Draft Emergency Shut Down Water Temperature RegulationBurner Flames Safety Shut-off Operational ConditionsCondensation Water Heater SoundsDraining and Flushing Routine Preventive MaintenancePowered Anode Operation Maintenance of Your Water Heater Replacement PartsRemoving the Manifold/Burner Assembly Removing the Burner from the Manifold/ Burner AssemblyReplacing the Manifold/Burner Assembly Replacing the Flame Sense/Hot Surface igniter AssemblyCleaning the Combustion Chamber and Air Diverter Assembly Replacing the Gas Valve Removing and Replacing the Gas Control Valve/ThermostatRemoving the Gas Control Valve/Thermostat Pressurized Combustion Chamber System Operational Checklist Troubleshooting ChartCont Control Display Troubleshooting Control Display Status Problem SolutionControl Display Status Problem Solution FV-SENSE and Open Flashing Troubleshooting Flowchart YESRepair Parts List Repair Parts IllustrationListed Parts Kits and Illustrations Page Page Page Limited Residential GAS Warranty YearImportant Information