in an alcove or closet, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard.

Minimum clearances between the water heater and combustible construction are 0 inch at the sides and rear, 5.5" (14.0 cm) from the front and 12" (30.5 cm) from the top. (Standard clearance.) If clearances stated on the heater differ from standard clearances, install water heater according to clearances stated on the heater.

Adequate clearance 24" (61.0 cm) for servicing this appliance should be considered before installation, such as changing the anodes, etc.

A minimum clearance of 5.5" (14.0 cm) must be allowed for access to replaceable parts such as the thermostats, drain valve and relief valve.

When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.

FIGURE 4.

A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confined area such as a closet, unless you provide air as shown in the “Locating The New Water Heater” section. Never obstruct the flow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fire or explosion and cause death, serious bodily injury, or property damage.

FIGURE 5.

If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater or water heaters be installed so that combustion and ventilation air be taken from outside these areas.

Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly flammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.

INSULATION BLANKETS

Insulation blankets are available to the general public for external use on gas water heaters but are not necessary with these products. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. Your water heater meets or exceeds the Energy Policy Act standards with respect to insulation and standby loss requirements, making an insulation blanket unnecessary.

Should you choose to apply an insulation blanket to this heater, you should follow these instructions (For identification of components mentioned below, see Figure 1). Failure to follow these instructions can restrict the air flow required for proper combustion, potentially resulting in fire, asphyxiation, serious personal injury or death.

Do not apply insulation to the top of the water heater, as this will interfere with safe operation of the blower assembly.

Do not cover the outer door, thermostat or temperature & pressure relief valve.

Do not allow insulation to come within 2" (5.1 cm) of the floor to prevent blockage of combustion air flow to the burner.

Do not cover the instruction manual. Keep it on the side of the water heater or nearby for future reference.

Do obtain new warning and instruction labels from the manufacturer for placement on the blanket directly over the existing labels.

Do inspect the insulation blanket frequently to make certain it does not sag, thereby obstructing combustion air flow.

COMBUSTION AIR AND VENTILATION FOR APPLIANCES LOCATED IN UNCONFINED SPACES

UNCONFINED SPACE is space whose volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfined space.

In unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in “Combustion Air and Ventilation for Appliances Located in Confined Spaces.”

COMBUSTION AIR AND VENTILATION FOR APPLIANCES LOCATED IN CONFINED SPACES

CONFINED SPACE is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input rating of all appliances installed in that space.

When drawing combustion air from inside a conventionally constructed building to a confined space, such a space shall be provided with two permanent openings. ONE WITHIN 12 INCHES (30 cm) OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES (30 cm) OF THE ENCLOSURE BOTTOM. Each opening shall have a free

10

Image 10
Contents Power Vented GAS Models W/HOT Surface Ignition Residential GAS Water HeatersSafe INSTALLATION, USE and Service Important DefinitionsGeneral Safety General Safety Table of Contents IntroductionReplacement Parts and Deliming Products Typical InstallationRelief Valve Elbow Access Door Condensate Hose and Drain PAN Mixing Valve Usage Locating the NEW Water Heater Facts to Consider about the LocationInsulation Blankets ALL AIR from Inside Buildings See ALL AIR from Outdoors See Figures 7, 8Installing the NEW Water Heater Water PipingTEMPERATURE-PRESSURE Relief Valve Valve and Pipe Insulation if suppliedGAS Piping with Flexible Connector GAS PipingFilling the Water Heater Vent Pipe AssemblySediment Traps VentingCanadian Horizontal Vent Clearances Vent Pipe Termination Horizontal Vent ClearancesVent Hoods MAY be Extremely HOT During Operation Planning the Vent System CondensateInstallation of Vent System Blower Assembly InstallationVent Terminal INSTALLATION, Sidewall Power Vent Wiring Schematic Figure Vent Termination FigureInstallation of Vent SYSTEM, Sidewall Installation of Vertical Vent SystemVent Attenuation Assembly Installation Vertical VAA Installations RecommendedInch vent Vertical VAA Installations Inch vent Horizontal VAA InstallationsVent Pipe Preparation Recommended BRUSH* Size for Primer Cement ApplicationsStep F Step BStep E Step GWhat to do if YOU Smell GAS Power Before ServicingBurner. Do not try to light the burner by hand Do not TRY to Light the Burner by HandDisplay Temperature RegulationTemperature Indicators Temperature Adjustment Buttons D E FStart UP Conditions For Your InformationOperational Conditions Venting System Inspection Periodic MaintenanceBurner Cleaning Burner Operation and InspectionAnode ROD Inspection TEMPERATURE-PRESSURE Relief Valve OperationDraining Service Leakage CheckpointsRepair Parts List Troubleshooting Guidelines Trouble ShootingBurner flame, ensure flame is steady see #8 below Troubleshooting Guidelines Conditions and Exceptions Service and Labor ResponsibilityClaim Procedure Limitation on Implied Warranties

ARGSS02708 specifications

The A.O. Smith ARGSS02708 is a standout product in the realm of water heating solutions, designed with a focus on efficiency, durability, and user convenience. This particular model exemplifies the cutting-edge technology that A.O. Smith is known for, making it a preferred choice for both residential and commercial applications.

One of the main features of the ARGSS02708 is its high efficiency. The unit employs advanced insulation techniques, which minimize heat loss and ensure that energy is utilized effectively. With an Energy Factor that meets or exceeds industry standards, this water heater can significantly reduce energy bills, making it an environmentally friendly choice that doesn't compromise on performance.

Another notable characteristic of the A.O. Smith ARGSS02708 is its robust construction. Built with high-quality materials, this water heater is designed to withstand the wear and tear of daily use. The units are manufactured with a coating that helps resist corrosion, which not only prolongs the lifespan of the heater but also ensures that it operates safely and reliably over time.

The ARGSS02708 also incorporates smart technology that enhances user experience. It features an intelligent electronic control panel that allows for easy monitoring and adjusting of temperature settings, ensuring optimal comfort. This user-friendly interface provides real-time feedback, making it straightforward for users to manage their hot water needs efficiently.

Moreover, the model supports faster recovery rates compared to traditional water heaters. With its powerful heating elements, the ARGSS02708 can provide a steady supply of hot water at consistent temperatures, catering to households or businesses with high hot water demands.

Safety is another critical aspect that A.O. Smith prioritizes in the design of the ARGSS02708. The unit is equipped with multiple safety features, including thermal cut-off switches and pressure relief valves, which ensure safe operation under varying conditions.

In summary, the A.O. Smith ARGSS02708 emerges as an excellent option for those seeking a reliable, efficient, and user-friendly water heating solution. Its combination of advanced technology, durable construction, high efficiency, and safety features make it a commendable investment for anyone looking to enhance their water heating experience.