MENU |
HOME |
Manual Index
TROUBLESHOOTING
CAUTION ! Always disconnect the pump from the electrical power source before handling.
If the system fails to operate properly, carefully read instructions and perform maintenance recommendations. If operating problems persist, the following chart may be of assistance in identifying and correcting them:
MATCH "CAUSE" NUMBER WITH CORRELATING "CORRECTION" NUMBER.
NOTE: Not all problems and correction will apply to each pump model.
PROBLEM |
| CAUSE | CORRECTION | |
Pump will not run. | 1. | Poor electrical connection, blown fuse, | 1. Check all electrical connections for | |
| tripped breaker or other interruption of | security. Have electrician measure current | ||
| power; improper power supply. | in motor leads, if current is within ±20% of | ||
| 2. | Motor or switch inoperative (to isolate | locked rotor Amps, impeller is probably | |
| cause, go to manual operation of pump). | locked. If current is 0, overload may be | ||
| 2a. Float movement restricted. | tripped. Remove power, allow pump to | ||
| 2b. Switch will not activate pump or is | cool, then recheck current. | ||
| defective. | 2a. Reposition pump or clean basin as | ||
| 2c. Defective motor. | required to provide adequate clearance for | ||
| 3. | Insufficient liquid level. | float. | |
Pump will not turn off. | 2a. Float movement restricted. | 2b. Disconnect level cont rol. Set | ||
ohmmeter for a low range, such as 100 | ||||
| 2b. Switch will not activate pump or is | |||
| ohms full scale and connect to level control | |||
| defective. | |||
| leads. Actuate level control manually and | |||
| 4. | Excessive inflow or pump not properly | ||
| check to see that ohmmeter shows zero | |||
| sized for application. | |||
| ohms for closed switch and full scale for | |||
| 9. | Pump may be airlocked. | ||
| open switch. (Float Switch). | |||
| 14. Switch is in "HAND" position. | |||
| 2c. Check winding insulation (Megger | |||
Pump hums but doesn’t run. | 1. | Incorrect voltage. | ||
Test) and winding resistance. If check is | ||||
| 8. Impeller jammed or loose on shaft, worn | out side of range, dry and recheck. If still | ||
| or damaged, impeller cavity or inlet | defective, replace per service instructions. | ||
| plugged. | 3. Make sure liquid level is at least equal to | ||
Pump delivers insufficient capacity. | 1. | Incorrect voltage. | suggested | |
| 4. | Excessive inflow or pump not properly | 4. Recheck all sizing calculations to | |
| determine proper pump size. | |||
| sized for application. | |||
| 5. | Discharge restricted. | 5. Check discharge line for restrictions, | |
| including ice if line passes through or into | |||
| 6. | Check valve stuck closed or installed | ||
| backwards. | cold areas. | ||
| 6. Remove and examine check valve for | |||
| 7. | |||
| 8. Impeller jammed or loose on shaft, worn | proper installation and freedom of | ||
| operation. | |||
| or | damaged, impeller cavity or inlet | ||
| plugged. | 7. Open valve. | ||
| 8. Check impeller for freedom of operation, | |||
| 9. | Pump may be airlocked. | ||
| 10. Pump running backwards. | security and condition. Clean impeller | ||
Pump cycles too frequently or runs | 6. | Check valve stuck closed or installed | cavity and inlet of any obstruction. | |
9. Loosen union slightly to allow trapped air | ||||
periodically when fixtures are not in use. | backwards. | |||
to escape.Verify that | ||||
| 11. Fixtures are leaking. | |||
| is set so that impeller cavity is always | |||
| 15. Ground water entering basin. | |||
| flooded. Clean vent hole. | |||
Pump shuts off and turns on independent | 1. | Incorrect voltage. | 10. Check rotation. If power supply is three | |
of switch. (trips thermal overload | 4. | Excessive inflow or pump not properly | phase, reverse any two of three power | |
protector). CAUTION! Pump may start | sized for application. | supply leads to ensure proper impeller | ||
unexpectedly. Disconnect power supply. | 8. Impeller jammed, loose on shaft, worn | rotation. | ||
| or damaged, impeller cavity or inlet | 11. Repair fixtures as required to eliminate | ||
NOTE: Some pumps DO NOT have | plugged. | leakage. | ||
thermal overload protection on the motor. | 12. Excessive water temperature | 12. Check pump temperature limits & fluid | ||
Check pump specifications to determine. | (internal protection only). | temperature. | ||
Pump operates noisily or vibrates | 2c. Worn bearings, motor shaft bent. | 13. Replace portion of discharge pipe with | ||
flexible connector. | ||||
excessively. | 8. | Debris in impeller cavity or broken | ||
14. Turn to automatic position. | ||||
| impeller. | |||
| 15. Check for leaks around basin inlet and | |||
| 10. Pump running backwards. | |||
| outlets. | |||
| 13 . Piping attachments to building | |||
|
| |||
| structure too rigid or too loose. |
|
9