Understanding Modbus device update times and system performance

Subject: GE Multilin Modbus TCP/IP/RTU device update times

Applies to: All GE Multilin Modbus devices and most generic (third party) modbus devices

Perquisites: A basic understanding of Modbus devices, polling, Multilin devices and the Enervista product line (and its associated Modbus masters). Since Modbus TCP/IP and Modbus RTU are, from a polling standpoint, identical the term “MODBUS” in this appnote will be used to describe both types. Exceptions to this will be noted.

Objective: There are many misunderstandings about Modbus, both how it operates and how to calculate update times. This appnote will help both the integrator and end user understand the Modbus protocol and help them to calculate update times.

Basic Modbus Operation: The Modbus protocol is a master/slave transaction where a master device generates a query and a slave device generates a response. A slave should never give a response unless queried by the master. The time it takes for the device to answer is the "device response time". The "device update time" is how quickly a specific queried data set is updated in the master for that specific device.

Note: Network baud rates (both serial and Ethernet) account for only a small percentage of the device response time. Internal processing of the Modbus command by the device takes up the majority of the time.

The nature of Modbus is that only one device can be queried at a time on the same network. For Modbus RTU the ‘same network’ is defined as a specific serial line (RS485/232) and all the devices on that line. For Modbus TCP/IP the ‘same network’ is defined as a specific IP address (UR, Multinet, etc.) and the IPport associated with that IP address. If the ‘same network’ has only one device on it than the "device response time" and the "device update time" should be roughly equal. What if there are multiple devices on the ‘same network’? If the master needs to query all the devices it must query them one at a time. Let's suppose a network has 3 devices on it (device A, B and C) and the master needs data from all three. To get this data the master MUST do the following:

1.Query device A for data,

2.Listen for the response

3.receives the response from device A

4.Query device B for data,

5.Listen for the response

6.Receives the response from device B

7.Query device C for data,

8.Listen for the response

9.Receives the response from device C

The whole process is then repeated as needed. From the steps outlined above it can be seen that the "device update time" is dependent on how fast the other devices on the same network can respond. Let's suppose that each device has a device update time of 1 second. This means that the master will see fresh data from each device every three seconds (1+1+1=3). The more devices added to the network the longer each device's update time! Ten devices on the same network means an update time of 10 seconds (assuming each device takes 1 second to respond). The complete update cycle on the same network is also called the ‘round robin’ time. The more devices on a serial line the longer the overall device update time on that line (assuming each device is polled for data).

20

Image 20
Contents GE Multilin TM Table Of Contents Minimum system requirements IntroductionSystem Requirements GE IEDs IEDs Supported SummaryRecommended system requirements Basic steps to configure a system Supported Firmware VersionsVersions ProductIntroduction to EnerVista Pmcs Toolkit GroupToolkit group Device Setup Introduction to Device SetupAdding a Device To add a new device, perform the following stepsSerial Site Only parameters Other features of Configurator are Returning to the Main MenuAlarms and Events EventsWhat’s on the EventViewer Screen? Toolkit group Waveforms Waveform AvailabilityIntroduction to Comtrade Viewing waveforms of Comtrade FormatFAQ EnerVista Pmcs 6.15 Quick Start Guide Viewing waveforms of CSV Format EnerVista System Tray Tool Understanding Enervista Pmcs Architecture HardwareEnerVista Pmcs 6.15 Quick Start Guide GEMultinet or Modbus TCP/IP/RTU bridge Device update times using Multilin Enervista softwareModbus TCP/IP vs. Modbus RTU Test Case FAQ Testing Conclusion

PMCS 6.15 specifications

GE PMCS 6.15, or General Electric's Power Management Control System version 6.15, represents a significant advancement in the management and control of electrical power systems. This software solution is tailored for utility companies, industrial plants, and commercial facilities, allowing them to optimize their energy usage, improve reliability, and enhance their overall operational efficiency.

One of the main features of GE PMCS 6.15 is its integrated system for monitoring and managing power quality. This includes real-time data acquisition and trend analysis, enabling users to keep a close watch on voltage levels, frequency, harmonic distortion, and other key power quality metrics. This capability helps organizations to reduce downtime and minimize the risks of equipment failure due to power quality issues.

Another critical technology incorporated in PMCS 6.15 is advanced predictive analytics. By utilizing machine learning algorithms, the system can detect anomalies in power usage patterns, forecast potential outages, and suggest preventive measures. This proactive approach significantly enhances system reliability and allows for better planning and response strategies.

In terms of user experience, PMCS 6.15 features an intuitive interface that simplifies navigation and enhances operational efficiency. Its customizable dashboards provide at-a-glance insights into system performance, allowing operators to quickly identify issues and implement corrective actions. Additionally, the system supports mobile accessibility, enabling users to monitor and control power management functions remotely from smartphones or tablets.

The platform is also designed for scalability and integration with existing infrastructure. Whether an organization is upgrading from an earlier version or implementing power management solutions for the first time, PMCS 6.15 can be tailored to fit specific needs. Its compatibility with third-party applications and equipment ensures that users can leverage additional technologies without undergoing a complete overhaul of their systems.

Moreover, security is a paramount concern in today's interconnected world, and PMCS 6.15 addresses this with robust cybersecurity measures. The system employs encryption, multi-factor authentication, and other security protocols to safeguard sensitive data and protect against unauthorized access.

In summary, GE PMCS 6.15 stands out in the realm of power management solutions, offering advanced features such as real-time monitoring, predictive analytics, user-friendly interfaces, scalable integration, and enhanced security protocols. These characteristics make it an invaluable tool for optimizing electricity management, enhancing equipment reliability, and driving operational excellence in various sectors. As energy demands continue to evolve, leveraging solutions like GE PMCS 6.15 will be essential in achieving sustainable and efficient power management.