8-3. Troubleshooting check table
•The following indication applies regardless of shape of the indicator.
•Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and the following detection method has detected an abnormality
(the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with the OPERATION INDICATOR lamp flashing.
Operation Indicator
Lighted Not lighted
·Flashing of the OPERATION INDICATOR lamp (on the
·The OPERATION INDICATOR lamp (on the
No. | Abnormal | Operation indicator lamp | Symptom | Condition | Correspondence |
| point |
|
|
|
|
|
| Outdoor unit | 3 minutes after power supply turns ON, when | • Refer to | |
|
|
| |||
1 |
| does not | serial signal is not received. | ||
|
| operate. |
|
| |
|
|
|
|
| |
| Indoor coil |
| Detect Indoor coil/room temperature | • Refer to the characteristics of | |
|
| main indoor coil thermistor, | |||
| thermistor |
| Outdoor unit | thermistor short or open circuit every 8 | |
|
| sub indoor coil thermistor, | |||
2 |
|
| does not | seconds during operation. | |
|
| and room temperature | |||
Room |
| operate. |
| ||
|
|
| thermistor in | ||
| temperature |
|
| ||
|
|
|
| ||
| thermistor |
|
|
| |
|
|
|
|
| |
|
| Indoor fan repeats | When rotational frequency feedback signal is | • Refer to | |
| Indoor fan |
| 12 seconds ON | indoor fan motor". | |
3 |
| and 3minutes OFF. | not emitting during |
| |
motor |
| When the indoor | operation. |
| |
|
| fan breaks, the fan |
|
| |
|
| keeps stopping. |
|
| |
|
|
|
|
| |
| Indoor | Outdoor unit | When it cannot properly read data in the | • Check the indoor electronic | |
|
| nonvolatile memory of the indoor electronic | control P.C. board. | ||
|
| does not | |||
4 | control |
| control P.C. board. |
| |
| operate. |
| |||
| system |
|
|
| |
|
|
|
|
| |
|
|
|
|
| |
|
|
|
| <Thermistor short> | • Shortage of refrigerant |
|
|
| Thermistors are abnormal when they short | • Check the deicer P.C. | |
|
|
| after compressor | board. | |
|
|
|
| ||
5 | Outdoor |
| Outdoor unit | <Thermistor open> | Refer to "Check of outdoor |
thermistor |
| Thermistors are abnormal when they open | thermistor". | ||
| does not | ||||
|
|
| after compressor | Refer to outdoor unit service | |
|
| operate. | |||
|
| However, discharge temperature thermistor is | manual. | ||
|
|
|
| ||
|
|
|
| abnormal when open circuit is detected more |
|
|
|
|
| than 10 minutes after compressor |
|
| Outdoor | Outdoor unit | When it cannot properly read data in the | • Check the deicer P.C. board. | |
|
| nonvolatile memory of the deicer P.C. board, | Refer to outdoor unit service | ||
| control |
| |||
6 |
| does not | outdoor unit stops. | manual. | |
system |
| ||||
| operate. |
|
| ||
|
|
|
| ||
|
|
|
|
| |
|
|
|
|
|
12