3 . Functions

3-1 Specifications

Item

Source power requirement

Environmental condition

Dimensions

Weight

System condition

Number of control unit *3

User operating function

 

 

 

Specification

 

 

 

DC24V,0.02A(Maximum loading)

 

Input voltage

Power received from PAC-SC50KUA Power Supply Unit via M-NET transmission line.

DC12V,0.2A(Maximum loading)

 

 

 

 

 

 

Power is received from the PAC-SC50KUA Power Supply Unit via the DC power line.

Temperature

Operating

0 ˚C

+40 ˚C / 32 ˚F

+104 ˚F

Non operating

-20 ˚C

+60 ˚C / – 4 ˚F

+140 ˚F

 

 

Humidity

30 90%RH (No condensation)

 

mm

120(H)

300(W) 80[*19](D)

*[ ] : indicate the thickness from the

in

4-3/4(H) 11-13/16(W)

3-1/8[*3/4](D) wall.

 

Kg

1.0

 

 

 

 

lb

2-1/4

 

 

 

 

Indoor unit or independent OA processing unit or LOSSNAY : 50 units maximum (50 groups maximum)

Number of units (indoor or independent OA processing unit or LOSSNAY) in one group : 1-16 units

*Note Indoor unit, independent OA processing unit and LOSSNAY can not register to the same group.

Number of remote controllers in one group : 1-2

Number of system controllers in one group

:0-4 (including the number of remote controller in one group)

:0-3 for groups which have one remote controller.

Number of indoor units interlocked with one OA processing unit or LOSSNAY

:0-16 (some types of OA processing unit can only be operated when inter- locked to a maximum of 9 units)

Operation

ON/OFF

Operation

mode *1

Fan speed *1

Air direction and swing operation *1

Temperature setting

The ON/OFF operation can be performed as a collective or per group.

The switch operation for the operation mode setting can be performed as a collective or per group.

[ Selectable operation mode for the indoor unit ] Cool/Dry/Fan/Auto/Heat

[ Selectable operation mode for the independent ventilation ] Heat recovery/By-pass/Auto

The switch operation to set the High and Low speed can be performed as a collective or per group.

( The 4 fan speed setting is available to the indoor that has 4 levels )

The air flow direction can be switched to 4 directions and swing operation as a collec- tive or per group

Temperature setting can be performed collectively or per group.

[Setting temperature range]

 

 

Cool (Dry) operation

: 19

30 ˚C / 67

87 ˚F

Heat operation

: 17

28 ˚C / 63

83 ˚F

Auto operation

: 19

28 ˚C / 67

83 ˚F

-4-

Image 6
Contents Central Controller Mitsubishi Electric Air-conditioner Network SystemPage Safety Weekly Schedule Product FeaturesOperation Operating status monitorCollective ON/OFF switch Setup for system configurationInterlocked group setting Power supply wiringFunctions Specifications ON/OFFSpecification 50A management range Group Display Screen DisplayLAN changeover switch User operation Returning to the user operation menu screenDisplay contents Operation MethodHeat Operation settingCOOL/DRY AutoOFF Local remote control operation prohibition setting Using the function area 50A operation prohibitionMON. Monitor PROH. Prohibit COL. Collective 2 Collective operation setting Collective operation settingCollective prohibit setting Switch to set Remote Control Prohibit Shifting to the schedule setting screen Timer operationSchedule setting function summary Schedule SettingSchedule pattern P1 P3 setting Schedule pattern setting P1 P3, P4Set-back values and setting temperature setting Weekly schedule settingCopying schedule content to other groups memory,memory read Malfunction reset operation Shifting to the malfunction monitor screenChange operation Current time setting Sifting to the current time setting screenCurrent Time Setting Initial setting Shifting to initial setting menu NET address settingFunction setting SelectGroup configuration setting NETAdditions Interlocked operation setting Switch Group name setting Setting methodGroup name cursor Group name cursor movement mark Group name copy User setting IP address setting Initial setting tool connection functionMaintenance Refrigerant system monitor Malfunction log monitor External input/output function External input function2Specification of external output interface External output function1The function of external output Appendix 1 Initial setting abridged Function setting Appendix 2 User operation abridged 22-09-2002 SUN Mitsubishi Electric Corporation