3 . Functions
3-1 Specifications
Item
Source power requirement
Environmental condition
Dimensions
Weight
System condition
Number of control unit *3
User operating function
|
|
| Specification |
| ||
|
| DC24V,0.02A(Maximum loading) |
| |||
Input voltage | Power received from | |||||
DC12V,0.2A(Maximum loading) |
| |||||
|
|
| ||||
|
| Power is received from the | ||||
Temperature | Operating | 0 ˚C | +40 ˚C / 32 ˚F | +104 ˚F | ||
Non operating | +60 ˚C / – 4 ˚F | +140 ˚F | ||||
|
| |||||
Humidity | 30 90%RH (No condensation) |
| ||||
mm | 120(H) | 300(W) 80[*19](D) | *[ ] : indicate the thickness from the | |||
in |
| |||||
Kg | 1.0 |
|
|
|
| |
lb |
|
|
|
|
Indoor unit or independent OA processing unit or LOSSNAY : 50 units maximum (50 groups maximum)
Number of units (indoor or independent OA processing unit or LOSSNAY) in one group :
*Note Indoor unit, independent OA processing unit and LOSSNAY can not register to the same group.
Number of remote controllers in one group :
Number of system controllers in one group
:
:
Number of indoor units interlocked with one OA processing unit or LOSSNAY
:
Operation
ON/OFF
Operation
mode *1
Fan speed *1
Air direction and swing operation *1
Temperature setting
The ON/OFF operation can be performed as a collective or per group.
The switch operation for the operation mode setting can be performed as a collective or per group.
[ Selectable operation mode for the indoor unit ] Cool/Dry/Fan/Auto/Heat
[ Selectable operation mode for the independent ventilation ] Heat
The switch operation to set the High and Low speed can be performed as a collective or per group.
( The 4 fan speed setting is available to the indoor that has 4 levels )
The air flow direction can be switched to 4 directions and swing operation as a collec- tive or per group
Temperature setting can be performed collectively or per group.
[Setting temperature range] |
|
| |
Cool (Dry) operation | : 19 | 30 ˚C / 67 | 87 ˚F |
Heat operation | : 17 | 28 ˚C / 63 | 83 ˚F |
Auto operation | : 19 | 28 ˚C / 67 | 83 ˚F |