2. Indoor unit failure mode table
NOTE:Blinking patterns of this mode differs from the ones of Troubleshooting check
Left lamp of | Abnormal point | Detection method | Check point | |
OPERATION | ||||
(Failure mode) | ||||
INDICATOR lamp |
|
| ||
|
|
| ||
Not lighted | Normal | – | – | |
|
|
|
| |
Room temperature | When the room temperature thermistor | Refer to the characteristics of the room | ||
short or open circuit is detected every 8 | ||||
every | thermistor | temperature thermistor | ||
seconds during operation. | ||||
|
|
| ||
|
|
|
| |
| When the indoor coil thermistor short or | Refer to the characteristic of the main | ||
Indoor coil thermistor | open circuit is detected every 8 seconds | indoor coil thermistor, the sub indoor coil | ||
| during operation. | thermistor | ||
|
| |||
|
|
|
| |
Serial signal error | When the serial signal from the outdoor unit is | Refer to | ||
not received for a maximum of 6 minutes. | and serial signal error". | |||
| ||||
|
|
|
| |
| When the rotational frequency feedback | Refer to | ||
Indoor fan motor | signal is not emitted during | |||
motor". | ||||
| indoor fan operation. | |||
|
|
| ||
|
|
|
| |
| When it cannot properly read data in the | Replace the indoor electronic control | ||
Indoor control system | nonvolatile memory of the indoor electronic | |||
P.C. board. | ||||
| control P.C. board. | |||
|
|
| ||
|
|
|
|
13