OPERATION INDICATOR
Lighted · Flashing of OPERATION INDICATOR lamp (all lamps) indicates abnormality.
Blinking
Not lighted
NOTE : Before taking measures, make sure that the symptom reappears for accurate troubleshooting. Self check table
No. | Abnormal | Operation indicator lamp | Symptom | Detection method | Check point |
| point |
|
|
|
|
| Attachment | All lamps flash at the same time. | Indoor unit |
|
|
| When the electricity is not conducted to the | • Refer to | |||
| of the | and outdoor | |||
1 | installation of the horizontal | ||||
| horizontal |
| unit do not | interlock switch (Fan) of the horizontal vane. | vane". |
| vane |
| operate. |
| |
|
|
| |||
|
|
|
|
| |
|
|
|
|
|
|
OPERATION INDICATOR Lighted
Blinking
Not lighted
·Flashing of OPERATION INDICATOR lamp
·OPERATION INDICATOR lamp
No. | Abnormal | Operation indicator lamp | Symptom | Detection method | Check point |
| point |
|
|
|
|
| MXZ type | Right lamp flash | Outdoor unit | When the operation mode of the each indoor | • Unify the operation mode. |
| Operation |
| operates but | unit is differently set to COOL(includes DRY) | |
1 |
| Refer to service manual | |||
| indoor unit | and HEAT at the same time, the operation | |||
mode |
| ||||
| OB377. | ||||
| does not | mode of the indoor unit that has operated at | |||
| setting | ||||
|
| ||||
|
|
| operate. | first has the priority. |
|
NOTE : When the indoor unit has started operation and the above detection method has detected an abnormality (the first detection after the power ON), the indoor electronic control P.C. board turns OFF the indoor fan motor with OPERATION INDICATOR lamp flashing.
9-5. Trouble criterion of main parts
MSZ-GA22VA - E1 MSZ-GA25VA - E1
Part name
Room temperature thermistor(RT11)
Indoor coil thermistor (RT12(MAIN), RT13(SUB))
Indoor fan motor(MF)
Check method and criterion | Figure |
Measure the resistance with a tester. (Part temperature 10˚C ~ 30˚C)
Normal | Abnormal |
8 k" ~ 20 k" | Open or |
Check |
|
Horizontal vane motor(MV)
Measure the resistance between the terminals with a tester. (Part temperature 10°C ~ 30°C)
Color of the lead wire | Normal | Abnormal |
235 " ~ 255 " | Open or |
RED
ROTOR
YLW
BRN
ORN GRN