Starting desludge

This is controlled by the “Start on” function in the DESLUDGE menu. This should be set to “Time”.

Cycles will begin at “Start Time 1” and repeat at intervals “Interval 1” until “Start Time 2”. After this, cycles will repeat at intervals “Interval 2”. This allows desludging to be done at different intervals during day and night, for example.

In the example “Start Time 1” is set to 7:30 and “Interval 1” to 5 hours. This will result in desludge cycles at 7:30, 12:30, 17:30, 22:30 and 03:30

Stopping desludge

This is controlled by the “Stop on” function in the DESLUDGE menu. This should be set to “PV<level” (PV = Process Variable, normally % solids)

Cycles will stop when the PV is less than “Relay 1 Off Point” in the RELAY menu. In the example “Relay 1 Off Point” is set to 2%

Emergency stopping of desludge.

This is controlled by the “Stop if” function in the DESLUDGE menu. It should be set to “Ext Trig Xs” and the external trigger connected to the D1 trigger input. (The X indicates the number of seconds the input must be high to activate the function)

In the example “Stop if” is set to Ext Trig 2s

Related parameters.

“Relay N Max On Time” and “Relay N Min Off Time” may also be used to modify the basic commands described above.

Programming procedure.

1.From the normal display Press any key (except ESC) to access main menu (note; ensure TOGGLE RUN padlock is open).

2.Scroll down to the SETUP menu and press ENT.

SETUP

0

DUTY (Mode)

0

INPUT

OUTPUT

3.Scroll down to the DUTY (Mode) menu and press ENT.

 

DUTY (Mode)

0

 

PV CALCULATION

0

Description

Message

4.Scroll down to the DESLUDGE menu and press ENT.

 

DESLUDGE

0

 

Start On

0

Stop On

Do not start if

5.Scroll down to the Start On menu and press ENT.

6.Use key to highlight the option, scroll down to the Time option and press ENT.

 

0

Start On

0

Time

P250

7.Press ESC to return to the DESLUDGE menu.

IP258

25

Image 25
Contents Mobrey Contents Safety Precautions Display Sensor Connection IVE Neutral Earth MainsENT Product Description Product Introduction MSM400 Slurry Monitoring SystemUltrasonic Attenuation versus Suspended solids Slurry CharacteristicsMobrey Pipe Section Sensors Suspended Sensor Type MSM433Sensor Type Numbering System MSM400 Displays and Keypad Control UnitKeypad Operation Hart SPECIFICATIONS--MSM400EMC Suspended Sensor Installation Pipe Section InstallationPreliminary Checks Control Unit Sensor CablesTerminal Label Function Sensor Connections Hart Connections and Jumper SettingsRelays Current OutputInitial Power UP Safety PrecautionsMains Supply Toggle RUN Calibration Setup Monitor Main Menu Toggle RUN Calibration SetupToggle RUN EX-FACTORY System Features Diagnostic ParametersZero Setting Initial Zero Rechecking Zero Calibration Methods Auto CAL Auto CAL Zero Setting ProcedureClear Liquor Press ENT To set 23.1dB 26.2dB Autocal Span Setting ProcedureAuto CAL LAB Values Sample Press ENT to set 33.6dB 44.2dBMaximum % Solids Zero Setting ProcedureSpan CALIBRATION/GRADIENT Methods Calibration Method 1-SLURRY TypeAttenuation VALUE-METHOD No. of operation Set Default value Max value Hrs & mins Duty Mode Desludge ModeStart on Stop on Stop if Do not start if INPUT↓ Output Start Time #1 hm 730 P254 Relay Operation Outputs Current OutputMiddle Display Alarm←−−−−−−− Lower Display Display option parameter number DescriptionEngineering Frequency SET SettingsSystem Test Current Output Sensors Hart Smart CommunicationsMain Menu SUB Menu Parameter Description Appendix A1Par No Diagnostics Alarm ReportLogging EngineeringParameter Description Min Max Default ValueMSM400 Monit Parameter Description Min Max Default ValueFrom list 3.6/21mA/hold last reading Min Max Default Value Ex-Factory Manufacturer’s Code Hart Considerations Appendix A3 Hart and Psion Operating InstructionsSmart Communication with the Mobrey MSM400 Calibration adjustments at operating conditionsFurther customisation using the Smart HHC Handheld Communicator Mobrey CK Hand Held Communicator Assembly InstructionsFig DII. Loop diagram Fig D1 MOBREY-CK* HHC assembly How to connect the Smart Communicator Hand Held Communicator Operation How to drive a Psion based Smart Communicator Mobrey Find Save Diary Calc Time Notes World AlarmTAG Tank D7.0 Introduction and Function menu HelpD7.2 Program Parameters P D7.1 Monitor/Display Parameters DMode KEY Default RegisterWorking Register Safe RegisterHand Held Communicator Registers Select Data Source 10.1Alarm and Error Messages 10.0ERROR Messages on the HHCPrintout or PC transfer of MSM400 programme data Display of Parameter Data10.2Invalid Data Entry Instrument in Multidrop Mode Password not Open10.3Communication Errors Invalid Action not the Same InstrumentD0 D8 11.0Current Loop Checks and Trimming Current Output ** Set current Trim-maximum Trim-maximum12.0Unknown Instrument Current and USE ↑ & ↓ To Trim the Output13.3Use of multiple Smart Communicators D13.0 Smart Interfaces Compatibility D13.1 IntroductionEmerson Process Management Rosemount Measurement

IP258 specifications

The Emerson IP258 is an advanced industrial monitoring device designed to enhance operational efficiency and ensure optimal performance in various industrial applications. It is particularly suited for monitoring, controlling, and managing processes across diverse industries such as oil and gas, pharmaceuticals, food and beverage, and water treatment.

One of the main features of the IP258 is its robust and flexible architecture, enabling seamless integration with a wide range of field devices, sensors, and control systems. This adaptability ensures that the device can be tailored to specific operational needs, thus streamlining processes and enhancing reliability. Its modular design allows for easy upgrades and expansions, making it a cost-effective solution for companies looking to future-proof their investments.

The IP258 boasts advanced communication technologies, including support for various industrial protocols such as Modbus, Ethernet/IP, and Profibus. This versatile communication capability facilitates real-time data sharing and interoperability between different systems, promoting a cohesive operational environment. The device is equipped with multiple input and output options, which further enhances its functionality and connectivity with existing infrastructure.

Another standout characteristic of the Emerson IP258 is its user-friendly interface, which simplifies operation and minimizes training requirements. The intuitive graphical interface allows operators to easily visualize system performance, access historical data, and quickly identify anomalies. This ease of use not only ensures efficiency during normal operations but also aids in rapid troubleshooting and issue resolution.

The device is designed with high reliability and durability in mind, featuring superior environmental resistance to withstand harsh industrial conditions. Its rugged housing and advanced components ensure long-term performance, reducing the likelihood of unexpected downtime and maintenance costs.

In addition, the IP258 incorporates built-in data logging and analytics capabilities, enabling users to gather insights into operational trends and performance metrics. This feature is essential for predictive maintenance and proactive decision-making, ultimately driving productivity and minimizing operational risks.

Security is another priority in the design of the Emerson IP258. The device includes a comprehensive suite of cybersecurity measures to protect sensitive data and prevent unauthorized access, ensuring that operational integrity is maintained at all times.

Overall, the Emerson IP258 stands out as a powerful and versatile tool for industrial monitoring and control, combining advanced features, robust technology, and user-friendly design to meet the demands of modern industrial environments.