Refrigerator Safety
IMPORTANT– Please Read and Follow
A GFI shall be used if required by NFPA- 70 (National Electric Code), federal/state/local laws, or local ordinances.
•The required use of a GFI is normally related to the location of a receptacle with respect to any significant sources of water or moisture.
•Viking Range Corporation will NOT warranty any problems resulting from GFI outlets which are not installed properly or do not meet the requirements below.
If the use of a GFI is required, it should be:
•Of the receptacle type (breaker type or portable type NOT recommended)
•Used with permanent wiring only (temporary or portable wiring NOT recommended)
•On a dedicated circuit (no other receptacles, switches or loads in the circuit)
•Connected to a standard breaker of appropriate size (GFI breaker of the same size NOT recommended)
•Rated for Class A (5 mA +/- 1 mA trip current) as per UL 943 standard)
•In good condition and free from any
•Sheltered from moisture (water, steam, high humidity) as much as reasonably possible
4 | 5 |