Siemens 125-5033 owner manual Point Database, Address Descriptor Description

Page 25

Point Database

3

Point Database

Chapter 3 presents a description of the Fume Hood Controller point database including point descriptors, point addresses, and a listing of applications in which each point is found.

Address

Descriptor

Description

 

 

 

01

CTLR ADDRESS

Identifies the controller on the FLN trunk. Valid values: 0 through 98.

 

 

 

02

APPLICATION

The identification number of the Application running in the controller.

 

 

 

05

LOW ALM

This point displays an ON or OFF status. When the exhaust flow goes below the

 

 

value specified at LOW ALM LMT for the time specified in ALARM TIME, the

 

 

point goes into an alarm state (ON); the red LED is illuminated, the alarm

 

 

sounds, and the message “FLOW LOW” displays at the ODP.

06

HIGH ALM

This point displays an ON or OFF status. When the exhaust flow goes above the

 

 

value specified at HI ALM LMT for the item specified in ALARM TIME, the point

 

 

goes into an alarm state (ON); the red LED is illuminated, the alarm sounds, and

 

 

the message “FLOW HI“ displays at the ODP.

07

EMER ALM

This point displays an ON or OFF status that indicates if the EMERGENCY

 

 

PURGE button on the ODP has been pressed. When the operator presses the

 

 

EMERGENCY PURGE button, the point is ON, the red LED is illuminated, the

 

 

alarm sounds, and EEE and EMERGENCY MODE display at the ODP. If pressed

 

 

again, then the point is OFF. This point can be commanded by a field panel.

08

GEN FAILURE

Indicates a hardware failure (e.g., the pressure sensor) with an ON or OFF

 

 

status. The red LED is illuminated; the alarm sounds, and FFF and GENERAL

 

 

FAILURE display at the ODP.

10

HI ALM LMT

The value above FLOW STPT, in percent, at which the red LED and audible

 

 

alarm are activated on the ODP. This point is the setpoint for HIGH ALM. Valid

 

 

values: 100 through 255%.

 

 

 

11

HI WARN LMT

The value above FLOW STPT, in percent, at which the yellow LED is illuminated

 

 

on the ODP. Valid values: 100 through 255%.

 

 

 

12

LOW WARN LMT

The value below FLOW STPT, in percent, at which the yellow LED is illuminated

 

 

on the ODP. Valid values: 0 through 100%.

13

LOW ALM LMT

The value below FLOW STPT, in percent, at which the red LED and audible

 

 

alarm are activated on the ODP. This point is the setpoint for LOW ALM. Valid

 

 

values: 0 through 100%.

14

EMER TIMER

When EMER ALM is set to ON, the time set for EMER TIMER is used as the

 

 

length of time the EXH FLOW is commanded to full flow (the exhaust flow control

 

 

device is full open). After the time in EMER TIMER times out, the EXH FLOW is

 

 

controlled to the value set in EMER STPT. Valid values: 0 through 32, 767

 

 

seconds.

Siemens Building Technologies, Inc.

17

Image 25
Contents 125-5033 Rev. AA, September Two-State Constant Volume Fume Hood ControllerPage Service Statement Page Table of Contents High and Low Exhaust Flow Control Manual Organization How To Use This ManualManual Conventions Convention ExampleWhere To Send Comments Manual SymbolsNotation Symbol Meaning Datamate SoftwareRelated Equipment Product OverviewElectronic Actuation Pneumatic ActuationApplication Description Ordering NotesCommunication Wiring Power WiringHardware Inputs Hardware OutputsOperator Display Panel ODP Controller LED IndicatorsLED Type IndicationOperator Display Panel Laboratory Exhaust Air TerminalLaboratory Exhaust Air Terminal Venturi Air ValvesHigh Speed Electronic Actuation Pneumatic Actuation Low Speed Electronic ActuationPneumatic Actuator Analog Output-Pneumatic AO-P ModuleAirflow Sensor Differential Pressure TransmitterCables Applications Fume Hood Controller 2-Position Constant VolumeCalibration High and Low Exhaust Flow ControlControl Loops ElectronicDO3 Output Functionality Alarm OperationAlarm Strategies Emergency Purge FeatureEmergency Purge Operation Emergency Purge Strategies Fail-safe Operation Address Descriptor Description Point DatabaseFlow Coeff Flow P Gain Basic Service Information TroubleshootingPreventive Maintenance Controller LEDs Safety FeaturesAlgorithm GlossaryCentralized control Control loopEnglish units OCC modeEquipment controller Field panelSlave mode Override switchOn text Portable Operator’s TerminalTerminal Equipment Controller Unocc modeApplication IndexIndex

125-5033 specifications

The Siemens 125-5033 is a highly regarded circuit breaker in the world of electrical engineering and power distribution. Known for its robust design and versatile applications, this device offers a host of features that make it suitable for both commercial and industrial use.

One of the main features of the Siemens 125-5033 is its compact size. This allows for easy integration into existing systems without occupying excessive space, making it an ideal choice for facilities with limited room for electrical infrastructure. Its ability to handle high current ratings, typically around 125 amps, ensures that it can support a variety of electrical loads, making it versatile across different applications.

The Siemens 125-5033 employs advanced technologies, such as thermal-magnetic trip mechanisms. This allows for reliable protection against overloads and short circuits. The thermal component of the trip mechanism is designed to react to sustained overcurrent conditions, while the magnetic component responds instantaneously to short circuits. This dual-functionality ensures that the circuit breaker can effectively protect both the conductors and the connected equipment.

In terms of safety, the Siemens 125-5033 comes with advanced arc suppression technologies that minimize the risk of arcing during the circuit interrupting process. This not only enhances the longevity of the breaker but also safeguards personnel working near electrical installations. Additionally, the device features a clear, accessible reset mechanism, making it user-friendly and easy to operate in case of an interruption.

Another notable characteristic of the Siemens 125-5033 is its built-in ground fault protection option. This capability provides an added layer of safety, ensuring that any ground faults are detected and addressed promptly. It is particularly useful in environments where moisture or dust can compromise electrical safety.

The Siemens 125-5033 also boasts compatibility with various monitoring and control systems, enabling seamless communication and integration into smart building management systems. This feature allows facility managers to monitor power usage, identify potential issues, and optimize energy consumption effectively.

Overall, the Siemens 125-5033 circuit breaker is a reliable, safe, and technically advanced choice for those looking to enhance their electrical systems. Its compact size, dual-trip mechanism, ground fault protection, and compatibility with modern technologies make it a valuable asset for any facility looking to improve its electrical safety and efficiency.