Siemens 125-1957 RM Stpt MIN, RM Stpt MAX, RM Stpt Dial, AUX Temp, Disch Temp, MA Temp

Page 34

APOGEE Heat Pump Controller—Multi Stage Owner's Manual

Descriptor

Address

Application

Description

 

 

 

 

RM STPT MIN

11

2281, 2283,

The minimum temperature setpoint in degrees that the

 

 

2284, 2286,

controller can use from the setpoint dial. This overrides any

 

 

2287

temperature setpoint from the setpoint dial that falls below this

 

 

 

minimum.

 

 

 

Valid entry range: 48° to 95°F (9° to 35°C)

 

 

 

 

RM STPT MAX

12

2281, 2283,

The maximum temperature setpoint in degrees that the

 

 

2284, 2286,

controller can use from the setpoint dial. This overrides any

 

 

2287

temperature setpoint from the setpoint dial that rises above this

 

 

 

maximum.

 

 

 

Valid entry range: 48° to 95°F (9° to 35°C)

 

 

 

 

RM STPT DIAL

13

2281, 2283,

The temperature setpoint in degrees from the room temperature

 

 

2284, 2286,

sensor (not available on all temperature sensor models). This

 

 

2287, 2299

setpoint will be used for control in day mode (heating or cooling)

 

 

 

when enabled by STPT DIAL (Point 14).

 

 

 

Valid entry range: 48° to 95°F (9° to 35°C)

STPT DIAL

14

2281, 2283,

YES indicates that there is a room setpoint dial on the room

 

 

2284, 2286,

temperature sensor and it is to be used as the temperature

 

 

2287

setpoint for control in day mode. NO indicates that the

 

 

 

appropriate preset setpoint (Points 6, 7, 8 or 9) will be used as

 

 

 

the temperature setpoint for control in day heating or cooling

 

 

 

mode.

 

 

 

Valid input: YES or NO

AUX TEMP

15

2299

Actual reading from a 100K ohm thermistor connected to the

 

 

 

controller's Al 3 input. When a thermistor is connected at Al 3,

 

 

 

DI 3 is not available. Refer to Dl 3 (Point 25).

DISCH TEMP

15

2281, 2284,

Actual reading from a 100K ohm thermistor connected to the

 

 

2287

controller's AI 3 input. When a thermistor is connected at Al 3,

 

 

 

DI 3 is not available. Refer to DI 3 (Point 25).

MA TEMP

15

2283, 2286

Actual reading from a 100K ohm thermistor connected to the

 

 

 

controller's Al 3 input. When a thermistor is connected at Al 3,

 

 

 

DI 3 is not available. Refer to DI 3 (Point 25).

 

 

 

 

1 VLV HTGCLG

16

2281, 2283

YES indicates that there is one valve controlling one coil which

 

 

 

may have hot or chilled water in it. (2-pipe heat/cool). NO

 

 

 

indicates any other hardware setup.

 

 

 

Valid input: YES or NO

 

 

 

 

FBP.MODVALVE

17

2281, 2283,

FBP indicates that both heating and cooling will be modulated

 

 

2284, 2286

with a face-bypass damper. VALVE indicates all other

 

 

 

configurations.

 

 

 

Valid input: FBP or VALVE

 

 

 

 

WALL SWITCH

18

2281, 2283,

YES indicates that the controller is to monitor the status of a

 

 

2284, 2286,

wall switch that is connected to DI 2. NO indicates that the

 

 

2287, 2299

controller will not monitor the status of a wall switch, even if one

 

 

 

is connected.

 

 

 

Valid input: YES or NO

DI OVRD SW

19

2281, 2283,

Actual indication of the status of the override switch (not

 

 

2284, 2286,

physically available on all temperature sensor models) at the

 

 

2287, 2299

room temperature sensor. ON indicates that the switch is being

 

 

 

pressed. OFF indicates that the switch is released.

 

 

 

Valid input: ON or OFF

24

Siemens Building Technologies, Inc.

Image 34
Contents Apogee Unit Vent Controller ⎯ 125-1957 Rev. CA, JulyPage Service Statement Page Table of Contents Point Database Troubleshooting Table of Contents How To Use This Manual Manual OrganizationManual Conventions Manual SymbolsNotation Symbol Meaning Datamate SoftwareWhere To Send Comments Getting HelpOrdering Notes Product OverviewIntroduction Standard ApplicationsAnalog Hardware InputsDigital Hardware Outputs Power WiringCommunication Wiring Analog 0 toTemperature Sensors Controller LED IndicatorsRoom Temperature Sensor Damper Actuators Mixed Air/Discharge Air Temperature SensorActuators Valve ActuatorsApplications Control Temperature SetpointsDay/Night Mode Basic OperationHeating and Cooling Switchover Valve ConfigurationControl Loops Electric Heat Morning Warm-up/Cool-downON/OFF Coil Valve Control Fan OperationBasic Operation Application 2281 Control Drawing Application 2281 Control Drawing Application 2281 Control Drawing Application 2283 Control Drawing Application 2283 Control Drawing Application 2283 Control Drawing Application 2284 Heating and DX Cooling, Ashrae Cycles I Application 2284 Control DrawingApplication 2284 Heating and DX Cooling, Ashrae Cycles I Application 2286 Heating and DX Cooling, Ashrae Cycle Application 2286 Control DrawingApplication 2286 Heating and DX Cooling, Ashrae Cycle Application 2287 Heating and Cooling Nesbitt Cycle W Overview Application 2287 Heating and Cooling Nesbitt Cycle W Application 2299 Slave Mode Point Database Descriptor Address Application DescriptionRM Stpt MAX Wall SwitchRM Stpt MIN RM Stpt DialAUX.NOAUX Ovrd TimeNGT Ovrd Free CLGAOV2 Span AOV1SPANAOV1START AOV2 StartEhea T NGT CLG ModeEheat FANCLG P Gain CLG OutputOA Dmpr POS CLG D GainMA Loopout Switch LimitSwitch Time OA LoopoutNGT Dband Switch DbandError Status Morn DbandBasic Service Information TroubleshootingOverview Safety Features Ordering Replacement PartsPreventive Maintenance Controller LEDsCentralized control GlossaryAlgorithm Control loopField panel English unitsEquipment controller InterceptOn text Override switchSlave mode Sl unitsUnbundle DDC IndexBST LED FLNRTS TX LED