APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Application 2284 – Heating and DX Cooling, ASHRAE Cycles I and II
In Application 2284, the Unit Vent Controller⎯0 to 10V output controls a unit ventilator equipped with a DX coil for cooling, and/or a heating coil, which may be hot water, steam, or electric, for ASHRAE Cycles I and II. A
Other features available in this application include morning
NOTE: The use of a low temperature detection thermostat (LTDT) is strongly recommended for hot water and steam systems.
While in heating, this application controls room temperature by resetting the discharge air temperature. While in cooling, this application controls room temperature by cycling the DX unit. This application also controls an outdoor air damper according to the schedules as defined by ASHRAE Cycles l and II. The
Figure 14. Application 2284 Control Drawing.
16 | Siemens Building Technologies. Inc. |