APOGEE Unit Vent Controller0 to 10 V Output Owner’s Manual

Application 2284 – Heating and DX Cooling, ASHRAE Cycles I and II

In Application 2284, the Unit Vent Controller0 to 10V output controls a unit ventilator equipped with a DX coil for cooling, and/or a heating coil, which may be hot water, steam, or electric, for ASHRAE Cycles I and II. A face-bypass damper can be controlled, replacing the modulating (0-10V) heating actuator, but will modulate only in heating mode. If a face-bypass damper is used, two-position valves on the coils may be controlled. Cooling only units can also be controlled with this application by overriding HEAT.COOL (Point 5) to COOL.

Other features available in this application include morning warm-up/cool-down, night mode override, free cooling and auxiliary radiation in heating mode.

NOTE: The use of a low temperature detection thermostat (LTDT) is strongly recommended for hot water and steam systems.

While in heating, this application controls room temperature by resetting the discharge air temperature. While in cooling, this application controls room temperature by cycling the DX unit. This application also controls an outdoor air damper according to the schedules as defined by ASHRAE Cycles l and II. The free-cooling/economizer function is turned on and off by the field panel using FREE CLG (Point 23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate open in sequence with the heating actuator or the DX. The unit ventilator fan is also controlled in this application.

Figure 14. Application 2284 Control Drawing.

16

Siemens Building Technologies. Inc.

Image 26
Contents Apogee Unit Vent Controller ⎯ 125-1957 Rev. CA, JulyPage Service Statement Page Table of Contents Point Database Troubleshooting Table of Contents How To Use This Manual Manual OrganizationManual Conventions Manual SymbolsNotation Symbol Meaning Datamate SoftwareWhere To Send Comments Getting HelpOrdering Notes Product OverviewIntroduction Standard ApplicationsDigital Hardware InputsAnalog Hardware Outputs Power WiringCommunication Wiring Analog 0 toRoom Temperature Sensor Controller LED IndicatorsTemperature Sensors Damper Actuators Mixed Air/Discharge Air Temperature SensorActuators Valve ActuatorsApplications Control Temperature SetpointsDay/Night Mode Basic OperationControl Loops Valve ConfigurationHeating and Cooling Switchover Electric Heat Morning Warm-up/Cool-downON/OFF Coil Valve Control Fan OperationBasic Operation Application 2281 Control Drawing Application 2281 Control Drawing Application 2281 Control Drawing Application 2283 Control Drawing Application 2283 Control Drawing Application 2283 Control Drawing Application 2284 Heating and DX Cooling, Ashrae Cycles I Application 2284 Control DrawingApplication 2284 Heating and DX Cooling, Ashrae Cycles I Application 2286 Heating and DX Cooling, Ashrae Cycle Application 2286 Control DrawingApplication 2286 Heating and DX Cooling, Ashrae Cycle Application 2287 Heating and Cooling Nesbitt Cycle W OverviewApplication 2287 Heating and Cooling Nesbitt Cycle W Application 2299 Slave Mode Point Database Descriptor Address Application DescriptionRM Stpt MAX Wall SwitchRM Stpt MIN RM Stpt DialAUX.NOAUX Ovrd TimeNGT Ovrd Free CLGAOV2 Span AOV1SPANAOV1START AOV2 StartEhea T NGT CLG ModeEheat FANCLG P Gain CLG OutputOA Dmpr POS CLG D GainMA Loopout Switch LimitSwitch Time OA LoopoutNGT Dband Switch DbandError Status Morn DbandOverview TroubleshootingBasic Service Information Safety Features Ordering Replacement PartsPreventive Maintenance Controller LEDsCentralized control GlossaryAlgorithm Control loopField panel English unitsEquipment controller InterceptOn text Override switchSlave mode Sl unitsUnbundle DDC IndexBST LED FLNRTS TX LED