Carrier 30HXA, HXC076-186 installation instructions

Page 9

IMPORTANT: Some of the unit skids are larger than standard door openings. Be sure that the path to the unit's ®nal destination is wide enough to accommo- date unit shipping skid. Remove the skid if necessary. If skid is removed and rollers are used, attach rollers to unit tube sheets while moving unit.

Areas where unit mounting points will be located must be level to within 1¤16 in. per ft (1 mm per m) along the long axis of the unit. Once unit is in place and level, bolt unit to the ¯oor. Use isolation pads under the unit to aid in vibration isolation as required.

Step 3 Ð Piping Connections Ð See Fig. 6 and 7 for typical piping applications.

COOLER FLUID, VENT, AND DRAIN Ð The inlet (re- turn) ¯uid connection is always the lower of the 2 cooler connections. See Fig. 6 for locations. A screen strainer with a minimum of 20 mesh should be installed ahead of the cooler inlet to prevent debris from damaging internal tubes of the cooler. Outlet (supply) ¯uid connection is the upper connec- tion of the 2 cooler connections.

The cooler has weld ¯anges to connect the ®eld-supplied piping. Plan the piping arrangement in accordance with good piping practices and so that the piping does not cross in front of the cooler head. Use ¯exible connections on cooler pip- ing to reduce vibration transmission. Offset the piping to per- mit removal of the cooler head for maintenance. Install pipe hangers where needed. Make sure no weight or stress is placed on the water nozzle.

To install cooler piping:

1.Remove bolts on weld ¯anges, and remove ¯anges from cooler ¯uid heads.

Remove the weld ¯anges before welding piping to the ¯anges. Refer to Fig. 1-4 for weld ¯ange loca- tions. Failure to remove the ¯anges may damage the sensors and insulation.

2.To keep debris from entering the heat exchanger during shipping and storage, the gaskets between the weld flanges and the ¯uid heads do not have holes cut into them. The gaskets have perforations where the holes are to be cut. Carefully cut a hole along the designated perforations.

IMPORTANT: Be sure to remove ¯anges and cut holes in the gaskets between the ¯anges and the fluid heads as indicated.

3.Apply a thin coat of oil to both sides of each gasket to help ensure a good seal, and reattach each gasket to each ¯uid head.

4.Weld the ®eld-supplied piping to the weld ¯anges.

5.Bolt the weld ¯anges back onto their respective ¯uid heads.

IMPORTANT: When bolting the weld ¯anges to the ¯uid heads, be sure to locate the ¯ange such that the hole in each ¯ange lines up completely with the hole in each ¯uid head. If installed incorrectly, part of the hole in the ¯uid head will be blocked off. This will result in impaired ¯uid ¯ow in high pres- sure drop applications.

Tighten all cooler head bolts to 250 ft-lb (339 N-m) before ®lling system with water (or brine).

6.Install ®eld-supplied differential ¯ow switches in the cooler piping for protection against loss of ¯ow. The differential ¯ow switches must be installed on top of the pipe in a horizontal run and should be at least 5 pipe diameters from any bend. Install the low-pressure differential ¯ow switch into the outlet line piping, and install the high-pressure differential ¯ow switch into the inlet line piping as shown in Fig. 8.

7.Provide openings in ¯uid piping for pressure gages and thermometers (if used). These openings should be 5 to 10 pipe diameters from the unit water nozzles. For thorough mixing and temperature stabilization, wells in the leav- ing ¯uid pipe should extend at least 2 in. (50 mm) into the pipe.

Accessory Victaulic-type connections are available. Fol- low the connection directions provided with the accessory.

Although cooler has an air vent, it is recommended that a ®eld-supplied air vent be installed in the system to facilitate servicing. Field-supplied shut-off and balancing valves should also be installed to facilitate servicing and ¯ow balancing. Locate valves in return and supply ¯uid lines as close to the chiller as possible. Locate air vent at highest point of the cooler ¯uid system. See Fig. 6.

Provide drain connections at all low points to permit com- plete drainage of the system.

BRINE UNITS Ð Special factory modi®cations to the units are required to allow them to operate at ¯uid temperatures less than 34 F (1.1 C). Be sure that the ¯uid has sufficient inhibited ethylene glycol or other suitable corrosion- resistant antifreeze solution to prevent cooler freeze up.

PREPARATION FOR YEAR-ROUND OPERATION Ð In areas where the piping or unit is exposed to 32 F (0 °C) or lower ambient temperatures, freeze-up protection is recom- mended using inhibited ethylene glycol or other suitable corrosion-resistant antifreeze solution and electric heater tapes. Heater tapes should have a rating for area ambient tempera- tures and be covered with a suitable thickness of closed-cell insulation. Route power for the heater tapes from a separately- fused disconnect. Mount the disconnect within sight from the unit per local or NEC codes. Identify disconnect as heater tape power source with warning that power must not be turned off except when servicing unit.

Fill the ¯uid loop with water (or brine) and a corrosion- resistant inhibitor suitable for the water of the area. Consult the local water authority for characteristics of area water and a recommended inhibitor for the cooler ¯uid loop. It is rec- ommended that once the cooler water lines have been installed and leak checked that the cooler heads be insulated with a suitable thickness of closed-cell insulation. This will minimize the amount of condensation that will form on the cooler heads.

IMPORTANT: Before starting the unit, be sure all of the air has been purged from the system.

A drain connection is located at the bottom of the cooler head. See Fig. 3 and 4 for connection location. Install shut- off valves to the drain line before ®lling the system with fluid.

9

Image 9
Contents Installation Instructions Base Unit Dimensions, 30HXC076-146 Units Base Unit Dimensions, 30HXC161-186 Units Base Unit Dimensions, 30HXA076-146 Units Base Unit Dimensions, 30HXA161-186 Units Unit Mounting Plate no 30HXA Unit Mounting Plate no 30HXCÐ Physical Data, English Ð Physical Data, SI Page Page Saturated Pressure Discharge Temp Discharge Line 2 F 1.1 C Drop Saturated Temperature ExampleSaturated Pressure Liquid Temp 134a Psig KPa 100 37.7 124.3 857 195.936.7 120.1 828 190.2 R-134a Discharge Line Sizing, 30HXA Units Page Voltage Power Circuit Control Circuit ICF Unit Ð Unit Electrical Data, 30HXC UnitsMCA Mocp MCA Ð Unit Electrical Data, 30HXC Units*RLA 208/230 460 575 380 346²² 380/415Ð Unit Electrical Data, 30HXA Units Ð Unit Electrical Data, 30HXA Units* Ð Compressor Electrical Data, 30HXC Units Unit Size Nameplate Compressor Numbers 30HXCRLA LRA 136-WD 126-WD146-WD 161-WD186-WD Unit Size Nameplate Compressor Numbers 30HXA Ð Compressor Electrical Data, 30HXA Units460-60 115.4 820 94.8 685 NEC EquipCCN ALMComm CwfsInstall Accessories Unit Circuit a Circuit B Charge 30HXA 30HXA System Charge for Start-UpPackaged Service Training

30HXA, HXC076-186 specifications

The Carrier 30HXA and 30HXC series is a notable line of chillers designed for commercial applications, providing advanced cooling solutions for various buildings and infrastructures. These models are known for their reliability and efficiency, making them a preferred choice for building managers and facilities engineers.

One of the key features of the Carrier 30HXA and 30HXC series is their use of high-efficiency, variable-speed scroll compressors. This technology allows the chillers to adjust their cooling output based on the actual demand, resulting in significant energy savings, especially during periods of partial load. This responsiveness not only leads to lower operational costs but also reduces wear and tear on the equipment, extending its lifespan.

Another critical aspect of these chillers is their eco-friendly refrigerant options. The 30HXA and 30HXC models utilize R-410A refrigerant, which has a lower environmental impact compared to traditional refrigerants. This commitment to sustainability aligns with modern regulations and climate goals, making these chillers an environmentally responsible choice.

Both series offer a wide range of cooling capacities, from 76,000 to 186,000 BTU/h, catering to various commercial needs. The compact design and modular configurations of these chillers allow for easy installation and integration into existing systems, facilitating retrofits and upgrades without significant disruption.

The 30HXA and 30HXC chillers also feature advanced controls that enhance their operational efficiency. The integrated controls allow for easy monitoring and adjustments, enabling users to optimize performance and minimize energy consumption. Additionally, they can easily interface with building management systems (BMS), providing real-time data and improved operational insights.

Durability is another hallmark of the Carrier 30HXA and 30HXC series. Built with corrosion-resistant materials and designed to withstand harsh weather conditions, these chillers ensure reliable performance in various environments. The robust construction further enhances their longevity, providing consistent cooling solutions for years.

In summary, the Carrier 30HXA and 30HXC series chillers offer advanced technology, eco-friendly refrigerants, energy efficiency through variable-speed compressors, and durable construction. These features come together to provide a reliable and effective cooling solution for a wide range of commercial applications, ensuring comfort and performance while supporting sustainability goals.