Carrier 16DF013-050 installation instructions Installation Instructions, Safety Considerations

Page 1

16DF013-050 Hermetic Absorption Liquid Chiller/Heaters

Installation Instructions

SAFETY CONSIDERATIONS

Absorption liquid chiller/heaters provide safe and reliable service when operated within design speci®cations. When operating this equipment, use good judgment and safety pre- cautions to avoid damage to equipment and property or in- jury to personnel.

Be sure you understand and follow the procedures and safety precautions contained in the machine instructions as well as those listed in this guide.

DO NOT USE OXYGEN or air to purge lines, leak test, or pressurize a machine. Use nitrogen.

NEVER EXCEED speci®ed test pressures. For the 16DF ma- chine, the maximum pressure is 12 psig (83 kPa). For the chilled/hot water and condensing water piping, the maxi- mum pressure is stamped on the machine.

WEAR goggles and suitable protective clothing when han- dling lithium bromide, octyl alcohol, inhibitor, lithium hy- droxide, and hydrobromic acid. IMMEDIATELY wash any spills from the skin with soap and water. IMMEDIATELY FLUSH EYES with water and consult a physician.

DO NOT USE eyebolts or eyebolt holes to rig maching sec- tions or the entire assembly.

DO NOT work on high-voltage equipment unless you are a quali®ed electrician.

DO NOT WORK ON electrical components, including con- trol panels or switches, until you are sure ALL POWER IS OFF and no residual voltage can leak from capacitors or solid- state components.

LOCK OPEN AND TAG electrical circuits during servic- ing. IF WORK IS INTERRUPTED, con®rm that all circuits are deenergized before resuming work.

NEVER DISCONNECT safety devices or bypass electric in- terlocks and operate the machine. Also, never operate the machine when any safety devices are not adjusted and func- tioning normally.

DO NOT REPEAT unsuccessful ignition attempts or restart after ¯ame failure without assurance that post-purge and pre- purge have eliminated combustible gas or oil vapors from the combustion chamber. DO NOT EVER ATTEMPT IG- NITION of a burner if there is shutdown leakage of gas or oil through the fuel shutoff valves or from the fuel lines.

DO NOT syphon lithium bromide or any other chemical by mouth.

BE SURE all hydrogen has been exhausted before cutting into pure chambers. Hydrogen mixed with air can explode when ignited.

WHEN FLAMECUTTING OR WELDING on an absorp- tion machine, some noxious fumes may be produced. Ven- tilate the area thoroughly to avoid breathing concentrated fumes.

DO NOT perform any welding or ¯amecutting to a machine while it is under a vacuum or pressurized condition.

NEVER APPLY an open ¯ame or live steam to a refrigerant cylinder. Dangerous overpressure can result. When necesary to heat a cylinder, use only warm (110 F [43 C]) water.

DO NOT REUSE disposable (nonreturnable) cylinders or at- tempt to re®ll them. It is DANGEROUS AND ILLEGAL. When cylinder is emptied, bleed off remaining gas pressure, loosen the collar and unscrew and discard the valve stem.

DO NOT INCINERATE.

DO NOT ATTEMPT TO REMOVE ®ttings, covers, etc., while machine is under pressure or while machine is running. DO NOT OPERATE or pressurize a machine without all cover plates or bolts in place.

DO NOT climb over a machine. Use platform, catwalk, or staging. Follow safe practices when using ladders.

DO NOT STEP ON machine piping. It might break or bend and cause personal injury.

USE MECHANICAL EQUIPMENT (crane, hoist, etc.) to lift or move inspection covers or other heavy components. Even if components are light, use such equipment when there is a risk of slipping or losing your balance.

VALVE OFF AND TAG steam, water, or brine lines before opening them.

DO NOT LOOSEN water box cover bolt until the water box has been completely drained.

DO NOT VENT OR DRAIN water boxes containing indus- trial brines, liquid, gases, or semisolids without permission of your process control group.

BE AWARE that certain automatic start arrangements can engage starters. Open the disconnects ahead of the starters in addition to shutting off the machine or pump.

INVESTIGATE THE CAUSE of ¯ame failure or any other safety shutdown before attempting a restart.

KEEP EYES sufficiently away from sight tubes or burner openings, and wear a protective shield or safety glasses when viewing a burner ¯ame.

USE only repaired or replacement parts that meet the code requirements of the original equipment.

DO NOT ALLOW UNAUTHORIZED PERSONS to tamper with burner equipment or machine safeties, or to make ma- jor repairs.

PERIODICALLY INSPECT all valves, ®ttings, piping, and relief devices for corrosion, rust, leaks, or damage.

PROVIDE A DRAIN connection in the vent line near each pressure relief device to prevent a build-up of condensate or rain water.

IMMEDIATELY wipe or ¯ush the ¯oor if lithium bromide or octyl alcohol is spilled on it.

BE SURE combustion air inlets to the equipment room are open and clear of any blockage.

Manufacturer reserves the right to discontinue, or change at any time, speci®cations or designs without notice and without incurring obligations.

Book

2

 

PC 211

Catalog No. 531-602

Printed in U.S.A.

Form 16DF-1SI

Pg 1

3-92

Replaces: New

Tab

5b

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Image 1
Contents Safety Considerations Installation InstructionsIntroduction ContentsReceiving the Machine and Burner Rigging 2-Piece Units Rigging and Positioning16DF Views Typical Flamecutting and Welding Detail Rigging 2-Piece Units, Sizes 16DF023-050 Assemble 2-Piece Units Machine AssemblyAuxiliary Evacuation Device Mounting the BurnerDescription Field PipingPage Fusible Plug Drain Piping Fig Electrical Connections Initial Solution and Refrigerant ChargingInsulation and Paint

16DF013-050 specifications

The Carrier 16DF013-050 is an advanced air conditioning unit designed for superior performance and efficiency in residential and light commercial applications. Renowned for its reliable cooling capabilities, this model incorporates state-of-the-art technologies and features that enhance user comfort while minimizing energy consumption.

One of the standout characteristics of the Carrier 16DF013-050 is its high SEER (Seasonal Energy Efficiency Ratio) rating, which guarantees efficient cooling during the peak summer months. This unit is designed to operate at optimal efficiency, thereby reducing energy bills and providing substantial savings over time. Its innovative design minimizes energy use while delivering consistent comfort throughout the space.

The Carrier 16DF013-050 utilizes advanced scroll compressor technology, which ensures quiet operation and reduces vibrations, enhancing overall durability. This technology allows the unit to effectively modulate its cooling output according to demand, ensuring that the environment remains comfortable without wasting energy. Additionally, the unit is equipped with advanced diagnostics that make it easier for technicians to identify any maintenance issues promptly, reducing downtime and repair costs.

Another notable feature of this model is the inclusion of Carrier’s proprietary Infinity® control system, which provides users with the ability to manage their indoor climate through a user-friendly interface. The system enables remote control capabilities via smartphone apps, allowing for seamless integration into smart home systems. This means users can monitor and adjust their air conditioning settings even when they are not at home, ensuring optimal comfort at all times.

Durability is another hallmark of the Carrier 16DF013-050. The unit is built with high-quality materials that withstand harsh weather conditions, ensuring longevity and reliable operation. The cabinet is galvanized and powder-coated, providing an added layer of protection against rust and corrosion.

The Carrier 16DF013-050 is also designed with eco-conscious considerations in mind, utilizing R-410A refrigerant, which is less harmful to the environment compared to older refrigerants. This aligns with Carrier’s commitment to sustainability and energy efficiency.

In summary, the Carrier 16DF013-050 is an exemplary model in the realm of air conditioning systems. With its high efficiency, state-of-the-art compressor technology, advanced control options, and eco-friendly features, it offers an excellent solution for maintaining comfortable indoor climates while being mindful of energy consumption and environmental impact.