Ice-O-Matic VRC manual Remote Condenser, General Information, Page

Page 9
Manual background

Remote Condenser

General Information

The VRC remote condensers incorporate the mixing valve in the condenser. This configuration allows up to a 100 foot calculated remote line set run. Reference the diagram below to calculate the maximum 100 foot line set run.

Limitations for new remote machines that have the mixing valve mounted in the condenser.

Maximum Rise is 35 feet.

Maximum Drop is 15 feet.

Maximum equivalent run is 100 feet.

Formula for figuring maximum equivalent run is as follows:

Rise x 1.7 + Drop x 6.6 + horizontal run = equivalent run.

Examples: 35 ft. rise x 1.7 + 40 ft. horizontal = 99.5 equivalent feet line run

40 ft. horizontal

35 ft. rise

Verify the ICE machine is compatible with the remote condenser. Some ice machines and some remote condensers may or may not have a Mixing Valve (Head Master). Only one valve is required per system. Kits are available to modify the remote condenser for compatibility. For more information contact your Ice-O-Matic Distributor.

34 ft. horizontal

10 ft. drop

10 ft. drop x 6.6 + 34 ft horizontal = 100 equivalent feet line run

Page 3

Image 9
Contents MODELS VRC INSTALLATION AND PARTS MANUAL REMOTE CONDENSERSIce-O-Matic 11100 East 45th AvePage Introduction Remote CondenserTable of Contents Freight Claims Important Inspect Promptly Freight Claim ProcedureVisible Loss or Damage Concealed Loss or DamageDomestic & International Limited Warranty WarrantyIce-O-Matic Parts and Labor GOVERNING LAWGeneral Information Introduction General DescriptionCondenser Location Remote Condenser Remote Refrigeration System Component Description ReceiverCondenser Fan Motor Installation INSTALLATION NOTICEWITH COMPATIBLE ICE-O-MATICICE MAKERS Support Leg Installation-VRC Vertical Air Flow Page Proper Tubing Routing Remote Condenser Service PartsDescription VRC1001Remote Condenser Service Parts