Tamron operation manual Calibration of the MST2000, Output mA Calibration, Output Gain

Page 32

OPERATION MANUAL

Cal i bra tion of the MST2000

15.5Notes for MST2000 I.S. Installation Draw ing SC37-4000-00

1.For I.S. In stal la tions, field wir ing shall be in stalled in ac cor dance with Ca na dian Elec t ri cal Code and/or Na tional Elec tri cal code ANSI/NFPA 70, Ar ti cle 504-30

2.Wiring ca ble shall be 24 AWG or heavier, sep a rate shielded pairs.

3.The ground ing con nec tion be tween the safety bar rier and earth ground must be less than 1 ohm.

4.Con trol room equip ment must not gen er ate more than 250 Volts rms.

5.Safety Bar riers must be of ap proved types and used in an ap proved con fig u ra tion where the transmitterVmax value is greater than the bar rier Voc rat ing and the trans mit ter Imax value is greater than the Bar rier Isc rat ing.

6.The trans mit ter in put ca pac i tance (Ci) plus the to tal ca ble ca pac i tance for each loop must not ex ceed the bar rier Ca rat ing.

7.The trans mit ter in put in duc tance (Li) plus the to tal ca ble in duc tance for each loop must not ex ceed the bar rier La rat ing.

8.Trans mit ter en clo sure must be grounded to earth ground us ing the pro vided ground lug on the enclosure.

9.The MST2000 Trans mit ter is In trin sically Safe for:

!Class I, Di vi sion 1, Groups C and D

!Class II, Di vi sion 1 Groups E, F and G.

10.Loop en tity pa ram e ters per cir cuit are:

!Vmax = 40 VDC

!Imax = 165mA

!Ci = 0uF

!Li = 240uH

11.Use only CSA ap proved I.S. Pres sure trans mit ters where the Vmax and Imax of the trans mit ter is greater than the Voc and Isc of the bar rier. The Ci and Li of the trans mit ter must be in cluded in sys tem to tal ca pac i tance and in duc tance cal cu la tion and must be less than bar rier Ca and La Rat ings.

12.Ap proved meth ods for sep a ra tion of each loop are:

!Run ning Loops in sep a rate ca bles

!Run ning Loops in sep a rate shields

13.When con nect ing HART com mu ni ca tor the Vmax and Imax of the com mu ni ca tor must be greater than the Voc and Isc of the bar rier. Voc of com mu ni ca tor plus Voc of bar rier must be less than Vmax of trans mit ter, ISC of Com mu ni cator plus Isc of Bar rier must be less than Imax of Trans mit ter. Li of Trans mit ter plus Li of Com mu ni ca tor must be less than La of Bar rier, Ciof trans mit ter plus Ci of Com mu ni ca tor must be less than Ca of Bar rier.

14.Use only listed and ap proved dust tight seal for Class II and Class III Haz ard ous Lo ca tions.

15.Other wire ter mi nals not avail able for use on In trin sically Safe ver sion

16.No re vi sions shall be made with out no ti fi ca tion of Ap proval Agency(s).

16. Calibration of the MST2000

Ba sic cal i bra tion of the MST2000 Se ries trans mit ters is done in two parts: 1) set ting the 4-20 mA out put from the dig i tal to an a log con verter and 2) set ting the 0 & 100% val ues of the dis played DP. Both parts are done by the set ting of pa ram e ters, en tered via the in te gral key pad.

16.1 OUTPUT mA CALIBRATION

A.ZERO and SPAN of the mA out put are set by the OUTPTO and OUTPTG pa ram e ters, re spec tively. You do not need to apply any DP sig nal for the mA cal i bra tion, only an ac cu rate mA test me ter is re- quired.

B.Fol low ing the pro ce dures of Sec tion 7, en ter the PROGRAMMING Mode and se lect the OUTPTO parameter. The existing value of OUTPUT OFFSET will be displayed.

C.Press the EDIT/SAVE key once to force the dig i tal to an a log con verter to its 0% out put value and to allow you to adjust the output to exactly 4.00mA as read on a mA test me ter. Use the INCREMENT & DECREMENT keys as needed.

D.Press the EDIT/SAVE key to exit the edit mode and save the OUTPUT OFFSET value (even if there was no adjustment made). Now step to the OUTPTG pa ram e ter to dis play the ex ist ing value of

OUTPUT GAIN.

E.Press the EDIT/SAVE key once to force the dig i tal to an a log con verter out put to its 100% value and to al low you to ad just the out put to ex actly 20.00mA as read on a mA test me ter. Use the INCREMENT & DECREMENT keys as needed.

F.Press the EDIT/SAVE key to exit the edit mode and save the OUTPUT GAIN value. This completes the out put mA cal i bra tion.

G.Exit the PROGRAMMING Mode, by pressing the MODE key, or con tinue with the DP cal i bra tion.

Brandt Instruments, Inc.

MST2000 Multivariable SMARTFLOW ® Transmitter

Page 33

Image 32
Contents MST2000 Series MST2100, Nema Thermo Brandt Instruments, IncTable of Contents Product OverviewSeries Loop Powered Multivariable Smartflowtm Transmitter Model NumberSpecifications Functional SpecificationsDimensions Mounting and Process Connections Continuous Purge OptionMST2100 Nema 1 Enclosure MST2400 Nema 4X EnclosureIntegral High Pressure Blowdown System Bal ancing the Purge if the Pro cess is in Op er a tionBal ancing the Purge if the Pro cess is not in Op er a tion Integral 5 MicronCoalescentFilterTe gral Power Sup ply Op tion Electrical ConnectionsLCD Display and Integral KEY PAD CanadianStandardsAssociationHazardousAreaApprovalsStartup MST2000 Operational Modes and Start UPLCD Display Editing of a Hardware/Operating Mode Parameter ProgrammingProgramming Se lect the Pa ram e ter to EditProgram Parameters LcdconFspan Stdden Tmpsrc Tmpcon Rtdcal Extpz Tpzcal Program ParametersApzcal Exaps Extps TpscalAprsrc Aprcon Exapz Outpto ApscalInputo Inputg Outptg AvgfacDefdsp DspresPword Bdenb HtenbAlarm Programming Information Alarm ‘ENABLE’ Word DefinitionLow Byte ‘BIT’ Definitions High Byte ‘BIT’ DefinitionsAlarm Sta tus ‘BIT’ Def i ni tions Alarm Programming InformationAlarm ‘STATUS’ Word Definition Alarm ‘ENABLE’ Word Decimal CalculationExamples LCD Icon, Fail-low, RTD Fault and Under-rangeAlarm ‘STATUS’ Word Decimal Decode Examples Alarm ‘STATUS’ Word =Formulas & Conversion Factors Alarm ‘STATUS’ Word = Formulas & Conversion FactorsScfm = Ae × 23972..677 × DP × P ÷T Metric Conversion FactorsOptional Module Installation Test JackIs removed for all I.S. and Division 2 approved MST2000’s Isolated 4-20mA Input Mod ules ISO Mod uleCalibrating the ISO Module Optional Module InstallationProgramming the MST2000 to recognize the ISO Modules Digital Input / Output Module Installation Hart CommunicationsModulePower and Loop Conditions MST2000 Hart Communications InformationMST2000 Hart Communications Information Hart ConnectionsPower Supply Requirements Hart Communication DistancePv = primary variable Intrinsic Safety ConsiderationsHart Command Information Wiring Diagrams Power Sup ply & Ab so lute Pres sure Trans mit terWiring Diagrams Power Sup ply and Ab so lute Pres sure Trans mit terMST2000 Hazardous Area Installation MST2000HazardousAreaInstallationIntrinsicallySafeInstallations Division 2 And Other InstallationsApproved Options MST2000 Hazardous Area Installation15.4 MST2000 I.S. Installation Drawing SC37-4000-00 Output Gain Calibration of the MST2000Output mA Calibration Cal i bra tion of the MST2000 DP Calibration

MST2000 specifications

The Tamron MST2000 is a groundbreaking optical device that showcases the company's commitment to innovation and quality in the world of photography and imaging. Designed for both professional photographers and enthusiastic hobbyists, the MST2000 delivers exceptional image quality, versatility, and ease of use.

One of the standout features of the Tamron MST2000 is its superior optical design. It incorporates advanced lens element configurations that minimize aberrations and distortion, ensuring sharp and vibrant images across the entire frame. The lens construction includes high-grade glass elements that enhance light transmission, resulting in crystal-clear images even in low-light conditions. This is particularly beneficial for night photography or indoor settings where lighting may be challenging.

The MST2000 also boasts an impressive zoom range, allowing photographers to capture a wide variety of subjects with ease, from breathtaking landscapes to intimate close-ups. Its robust zoom mechanism enables seamless transitions between focal lengths, helping users to adapt to different shooting environments quickly. The zoom is complemented by a fast and accurate autofocus system that ensures subjects are sharply focused, allowing photographers to capture fleeting moments with confidence.

In terms of build quality, the Tamron MST2000 is constructed with durability in mind. The lens features a weather-sealed body, making it resistant to moisture and dust. This design consideration allows photographers to shoot in diverse conditions without fear of damage, ensuring that the MST2000 is a reliable companion in any situation.

Another notable technology featured in the MST2000 is the vibration compensation system, which helps to reduce the effects of camera shake. This is particularly beneficial when shooting at slower shutter speeds or using longer focal lengths, allowing for clearer images without the need for a tripod.

For those who appreciate creative control, the MST2000 includes various customizable settings that enhance the user experience. Photographers can fine-tune parameters such as focus and aperture easily, providing them with the flexibility to achieve their desired artistic effects.

In summary, the Tamron MST2000 offers a sophisticated combination of advanced optical technologies, versatility, and user-friendly features. Whether capturing sweeping panoramas or intricate details, this lens is designed to meet the demands of today's photographers while inspiring creativity and exploration in every shot.