Chapter 6: Troubleshooting
Problem | Possible cause | |
| No power. | |
|
| |
| Wrong voltage supplied to unit. | |
|
| |
| Defective on/off switch. | |
Unit does not run. | Control circuit fuse blown. | |
| ||
|
| |
| Defective control transformer. | |
| Piping flow switch circuit open. | |
|
| |
| Pump motor off on overload. | |
| Leaving fluid setpoint set higher | |
| than temperature of liquid in | |
| system. | |
| Defective leaving fluid sensor | |
| High/Low thermostat. | |
| Compressor internal overload or | |
| fuses are open. | |
Pump runs; compressor does not. |
| |
| Compressor contactor holding coil | |
| open. | |
| Defective compressor auxiliary | |
| contact. | |
| Broken wire in the compressor | |
| control circuit. | |
|
| |
| Plugged | |
Pump runs, compressor cycles at | Hot gas not coming on | |
short intervals. |
| |
Low water flow | ||
| ||
|
| |
| Water/glycol mixture inadequate | |
| for process. | |
Water temperature is too high. | Improperly set leaving fluid | |
temperature, warning, or fault set | ||
| ||
| point | |
| Refrigerant charge is low. | |
|
|
Solution
Check main disconnect, fuses, wiring, and power lead to unit.
Voltage must be within plus or minus 10% of nameplate rating.
Replace.
Replace control circuit fuse. Check transformer.
Check for a short circuit. Replace.
Add water or water/glycol solution as required.
Reset and test.
Lower the leaving fluid temperature below the leaving temperature you desire.
Replace.
Allow time to cool and reset, then check for high/low
Check for open fuses and loose compressor electrical connections.
Repair or replace.
Repair or replace.
Locate and repair.
Clean
Replace relay board on control bed hot gas coil
Install bypass between
Make sure that the water/glycol mixture protection is right for the process.
Adjust.
Call service to find and repair the leak, then have refrigerant added.
GP Series Portable Chillers | Chapter 6: Troubleshooting | 34 of 44 |