Chapter 2: Functional Description
2-1 Models Covered in This Manual
This manual provides operation, installation, and maintenance instructions for
Our portable chiller models are designated by approximate compressor horsepower (5,7 1/2, 10, 13 and 15 etc) and the cooling method used:
2-2 General Description
Our portable chillers are reliable, accurate, and easy to use process cooling units. They are available in
Standard range of operation is 20ºF to 80ºF
A factory installed crankcase pressure regulating valve option is available for processes requiring a leaving water temperature over 80ºF (30ºC).
Chilled Water Circuit
Cooling water “To Process” and “From Process” connections are made at the female NPT couplings provided outside the unit. Warm coolant (water and glycol mixture) returns from the process and goes into the reservoir tank. The coolant is then pumped through the evaporator where it is cooled. The coolant flows to the process and returns to repeat the cycle.
A (manual) pressure actuated process water bypass valve located between the supply line and reservoir tank (single pump models only) allows minimal flow through the unit during the intermittent fluctuating flow conditions. It is not intended to provide continuous full bypass flow.
This minimal flow allows the temperature sensor to signal the controller to shut down the compressor because of the drop in process water temperature. Typically the flow switch shuts down the chiller in this low flow condition. This valve allows enough flow for the chiller to function when the flow is shut off to process.
Refrigeration Circuit
Liquid refrigerant from the condenser heat exchanger flowing in the liquid line passes through a