Page 16

FILTER INSTALLATION

AIR FILTERS

Filters are to be used with the YCZ036,050,060F heating/cooling units. The basic unit does not have filters in it. However, a filter frame accessory is offered that will allow filters to be installed within the unit.

Otherwise a filter rack must be installed by the installer in the duct work.

Affix the filter label supplied with the unit adjacent to the filter area.

TABLE 4

UNIT

NOMINAL

FILTER*

FILTER

CFM

Sq.Ft.- SIZE

RESISTANCE

 

 

 

 

 

YCZ036F

1200

4

0.05

 

 

 

 

YCZ050F

1600

5.33

0.05

 

 

 

 

YCZ060F

2000

6.67

0.05

 

 

 

 

*Filters must be installed in the return air system. The above square footages are based on 300 F.P.M. face velocity. If permanent filters are used, size per mfg. recommendation with clear resistance of 0.05" WC.

ELECTRICAL WIRING

ELECTRICAL CONNECTIONS

Electrical wiring and grounding must be installed in accordance with local codes or, in the absence of local codes, with the National Electrical Code ANSI/NFPA 70, Latest Revision.

ELECTRICAL POWER

It is important that proper electrical power be available for the unit. Voltage variation should remain within the limits stamped on the unit nameplate.

DISCONNECT SWITCH

Provide an approved weatherproof disconnect either on the side of the unit or within close proximity and within sight of the unit.

OVER CURRENT PROTECTION

The branch circuit feeding the unit must be protected as shown on the unit rating plate.

POWER WIRING

The power supply lines must be run in weathertight conduit to the disconnect and into the bottom of the unit control box. Provide strain relief for all conduit with suitable connectors.

Provide flexible conduit supports whenever vibration transmission may cause a noise problem within the building structure.

Be sure all connections are made tight. See Figure 18.

NOTES: For branch circuit wiring (main power supply to unit disconnect), wire size for the length of run should be determined using the circuit ampacity found on the unit nameplate and the N.E.C.

For more than 3 conductors in a raceway or cable, see the N.E.C. for derating the ampacity of each conductor.

GROUNDING: THE UNIT MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL ELECTRIC CODE.

NOTE: Unit must be grounded for ignitor to operate prop- erly. Gas pipe to unit is not an adequate ground. Ground the unit internally as provided. See wiring diagram for location.

CONTROL WIRING (CLASS II)

Low voltage control wiring should not be run in conduit with power wiring unless Class 1 wire of proper voltage rating is used. Route the thermostat cable or equivalent single leads of No. 18 AWG colored wire from the thermostat subbase terminals through the rubber gromment on the unit. See Figures 3 and 4 for the control entry location. Make connections as shown on the unit wiring diagram and in Figure 18.

Do not short thermostat wires since this will damage the control transformer.

Recommended wire sizes and lengths for installing the unit thermo- stat are provided in Table 5. The total resistance of these low voltage wires must not exceed one (1) ohm. Any resistance in excess of 1 ohm may cause the control to malfunction because of the excessive voltage drop.

TABLE 5

THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH

WIRE SIZE

MAXIMUM LENTGH (Ft)

18

75

16

125

14

200

THERMOSTAT HEAT ANTICIPATOR

The thermostat heat anticipators should be set to .4 amps on single or two stage thermostats.

IMPORTANT: Upon completion of wiring check all electrical connections, including factory wiring within the unit, make sure all connections are tight. Replace and secure all electrical box covers and access doors before leaving the unit or turning on the power to the unit.

Page 16

Image 16
Contents ALL phases of this installation must comply with NATIONAL, State and Local CodesGeneral Information InspectionTypical Rooftop Installation with BAYCURB030A,038A Typical Rooftop Installation with Full Perimeter CurbsYCZ036,050,060F Models YCZ036,050,060F Outline Back Dimensional DataModel YCZ036,050,060F Outline Front TOPConverting Horizontal to Downflow Roof Penetration Hole Size RequiredLocations and Recommendations Horizontal Airflow ApplicationClearances Downflow Application -- Curb MountingUnit Support Placing and Rigging InstallationLocation and Clearances Placing the Unit on a Mounting Curb Typical Rooftop Application with Frame YCZ036,050,060FYCZ036,060F Models Rooftop -- UnitsCondensate Drain Piping Typical Ground Level ApplicationTypical Condensate Drain Piping Ground Level -- Horizontal UnitsPrecautionary Measures DuctworkAttaching Downflow Ductwork to Roof Curb Attaching Horizontal Ductwork to UnitGAS Piping Installation GAS Pressure Setup PrecautionsSchematic Diagram GAS Piping to Unit Pipe Delivery ScheduleFlue and Hood Illustration Burner & Valve IllustrationManifold Pressure Input Check and Adjustment High Altitude InstallationGAS Flow in Cubic Feet PER Hour Cubic Foot Dial Filter Installation Electrical WiringYCZ-F Field Wiring Diagram Start UP Starting the Unit in the GAS Heating Mode Safety SequencesSequence of Operation Heating CycleICM FAN Motor Adjustments CFM ICM FAN ControldipCooling Cycle Indoor Blower TimingCheckout Procedure System FaultsRefrigerant Circuit ElectricalMaintenance Limited Warranty Combination GAS Electric AIR Conditioner YCZ, YCY and YCXCombination GAS Electric AIR Conditioner YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC

YCZ036F1/3M0B, YCZ035F1 specifications

The Trane YCZ035F1 and YCZ036F1/3M0B are cutting-edge packaged rooftop units designed for commercial applications, delivering reliable heating, ventilation, and air conditioning (HVAC) solutions. These units exemplify state-of-the-art technology, ensuring energy efficiency, environmentally friendly operation, and superior performance.

One of the most prominent features of the Trane YCZ036F1/3M0B is its robust design that accommodates various building requirements. The flexible configurations allow for easy installation and adaptability to different applications, reducing the complexity often associated with rooftop HVAC solutions. Available in multiple capacities, these units cater to a broad range of commercial spaces, providing the necessary heating and cooling loads efficiently.

The YCZ series incorporates advanced compressor technology, utilizing variable speed compressors that adjust operation based on the actual load requirements. This ensures optimized energy consumption, making it an environmentally responsible choice. Additionally, these compressors minimize noise levels, promoting a quieter indoor environment.

Energy efficiency is a hallmark of the YCZ035F1 and YCZ036F1/3M0B. They feature high-efficiency fans and coils, maximizing airflow while minimizing energy use. These units also boast advanced control systems that enable precise temperature regulation, further driving energy savings. The integration of smart technology allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance routines.

Durability is paramount in the design of the Trane YCZ series. Constructed with high-quality materials, these units are built to withstand the rigors of outdoor environments. The corrosion-resistant finishes and robust frames contribute to a longer lifespan, reducing the total cost of ownership over time.

The YCZ series also emphasizes indoor air quality, incorporating advanced filtration systems that enhance air cleanliness. This is crucial for commercial spaces where air quality directly impacts occupant health and productivity. Furthermore, the units can be easily integrated with additional ventilation systems, ensuring compliance with stringent air quality standards.

In summary, the Trane YCZ035F1 and YCZ036F1/3M0B are exemplary examples of advanced HVAC technology, offering flexible configurations, superior energy efficiency, durability, and enhanced indoor air quality. Businesses looking for reliable and efficient HVAC solutions will find these rooftop units to be an excellent choice for their commercial applications.