Trane YCZ035F1 manual Installation, Unit Support Placing and Rigging, Location and Clearances

Page 8

LOCATIONS AND RECOMMENDATIONS

continued from page 7

Examine all flue product-carrying areas of the furnace, its vent system, and the main burner for safe operation. A periodic inspection of the furnace should be made at the start of each heating season.

Replacement parts list for this Gas/Electric Air Conditioner may be obtained by contacting your local manufacturer representa- tive.

6.Location of the unit must allow for service clearance around it. Clearance of the unit must be given careful consideration. See Figure 4.

7.IMPORTANT: The air outlet duct must have one (1) inch clearance to combustible material downstream from the unit.

8.Exhaust vents or other sources of contaminated air should not be near the unit’s air inlet, if outside air is to be introduced as makeup air or a ventilation feature is to be used.

9.Check the handling facilities to ensure the safety of personnel and the unit(s).

10.Caution must be taken at all times to avoid personal injuries and/or damage to the equipment.

11.The unit must be mounted level for proper drainage of water through the holes in the base pan.

12.The unit must not be exposed to direct roof water runoff.

13.Flexible duct connectors must be of a flame retardant material. All duct work outside of the structure must be insulated and weatherproofed in accordance with local codes.

14.Roof flashing must be installed to seal the roof curb cavity and must conform to local building codes.

15.Access and service clearances for the unit must be given careful consideration when locating the duct entrance open- ings. Figure 4 provides unit dimensions.

16.All fabricated outdoor ducts should be as short as possible.

CLEARANCES

1.The recommended clearances for single-unit installations are illustrated in Figure 4. These minimum requirements are not only an important consideration when determining unit place- ment, but they are also essential to ensure adequate service- ability, maximum capacity, and peak operating efficiency.

2.Any reduction of the unit clearances indicated in these illustra- tions may result in condenser coil starvation or the recirculation of warm condenser air. Actual clearances which appear to be inadequate should be reviewed with a local sales engineer.

IMPORTANT:

1.Remove the Flue and Air Inlet Hood with the gasket from the return air section of the unit.

The screws that attach the flue and air inlet hood will be installed in their proper location at the factory. Therefore, they must be removed and then used to attach the flue and air inlet hood.

2.Remove the packaging material from the components and secure the Flue and Air Inlet Hood with the gasket to the unit with sheet metal screws as illustrated in Figure 16 on page 14.

NOTE: Outdoor air or other requirements during heating operation that result in supply air temperatures below 80 degrees F or return air temperatures below 50 degrees F may cause flue gas condensate to form and is to be avoided.

INSTALLATION

UNIT SUPPORT

PLACING AND RIGGING

If the unit is to be roof mounted, check the appropriate building codes for weight distribution requirements. Refer to the applicable roof curb mounting instruction. Check the unit’s nameplate for supply voltage required. Determine if adequate electrical power is available. The furnace may be installed on Class A, B, or C roofing material.

LOCATION AND CLEARANCES

Installation of the unit should conform to local building codes or, in the absence of local codes, to the National Fuel Gas Code, ANSIZ223.1, Latest Revision, and the National Electrical Code. Canadian installations must conform to CSA and local codes.

Select a location that will permit adequate combustion and ventila- tion air in accordance with Section 5.3, Air For Combustion and Ventilation, of the National Fuel Gas Code, ANSIZ223.1, Latest Revision, or applicable provisions of the local building code.

1.Before preparing the unit for lifting, check the outline drawing for center of gravity for lifting safety. Because of placement of internal components, the unit’s weight may be unevenly distrib- uted. Approximate unit weights are given in Figure 2, page 3.

NOTE: Accessory BAYLIFT002AA, a kit of four (4) lifting lugs, is required for rigging the unit for hoisting. See Figure 7, insert B.

2.Insert the four lifting lugs in the openings provided in the drip lip on the perimeter of the unit. See Figure 7, insert B. A tap or jerk to the lug will overcome the interference that arises due to the nipple on the lug.

3.Before hoisting the unit, be sure that the proper method of rigging is used, with straps or slings and spreader bars for protection during lifting. Always test-lift the unit to determine the exact unit balance and stability before hoisting it to the installa- tion location.

Page 8

Image 8
Contents ALL phases of this installation must comply with NATIONAL, State and Local CodesGeneral Information InspectionYCZ036,050,060F Models Typical Rooftop Installation with Full Perimeter CurbsTypical Rooftop Installation with BAYCURB030A,038A Model Dimensional DataYCZ036,050,060F Outline Back YCZ036,050,060F Outline Front TOPConverting Horizontal to Downflow Roof Penetration Hole Size RequiredLocations and Recommendations Horizontal Airflow ApplicationClearances Downflow Application -- Curb MountingLocation and Clearances InstallationUnit Support Placing and Rigging Placing the Unit on a Mounting Curb Typical Rooftop Application with Frame YCZ036,050,060FYCZ036,060F Models Rooftop -- UnitsCondensate Drain Piping Typical Ground Level ApplicationTypical Condensate Drain Piping Ground Level -- Horizontal UnitsPrecautionary Measures DuctworkAttaching Downflow Ductwork to Roof Curb Attaching Horizontal Ductwork to UnitGAS Piping Installation GAS Pressure Setup PrecautionsSchematic Diagram GAS Piping to Unit Pipe Delivery ScheduleManifold Pressure Burner & Valve IllustrationFlue and Hood Illustration GAS Flow in Cubic Feet PER Hour Cubic Foot Dial High Altitude InstallationInput Check and Adjustment Filter Installation Electrical WiringYCZ-F Field Wiring Diagram Start UP Starting the Unit in the GAS Heating Mode Safety SequencesSequence of Operation Heating CycleICM FAN Motor Adjustments CFM ICM FAN ControldipCooling Cycle Indoor Blower TimingCheckout Procedure System FaultsRefrigerant Circuit ElectricalMaintenance Limited Warranty Combination GAS Electric AIR Conditioner YCZ, YCY and YCXCombination GAS Electric AIR Conditioner YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC

YCZ036F1/3M0B, YCZ035F1 specifications

The Trane YCZ035F1 and YCZ036F1/3M0B are cutting-edge packaged rooftop units designed for commercial applications, delivering reliable heating, ventilation, and air conditioning (HVAC) solutions. These units exemplify state-of-the-art technology, ensuring energy efficiency, environmentally friendly operation, and superior performance.

One of the most prominent features of the Trane YCZ036F1/3M0B is its robust design that accommodates various building requirements. The flexible configurations allow for easy installation and adaptability to different applications, reducing the complexity often associated with rooftop HVAC solutions. Available in multiple capacities, these units cater to a broad range of commercial spaces, providing the necessary heating and cooling loads efficiently.

The YCZ series incorporates advanced compressor technology, utilizing variable speed compressors that adjust operation based on the actual load requirements. This ensures optimized energy consumption, making it an environmentally responsible choice. Additionally, these compressors minimize noise levels, promoting a quieter indoor environment.

Energy efficiency is a hallmark of the YCZ035F1 and YCZ036F1/3M0B. They feature high-efficiency fans and coils, maximizing airflow while minimizing energy use. These units also boast advanced control systems that enable precise temperature regulation, further driving energy savings. The integration of smart technology allows for remote monitoring and control, enhancing operational efficiency and simplifying maintenance routines.

Durability is paramount in the design of the Trane YCZ series. Constructed with high-quality materials, these units are built to withstand the rigors of outdoor environments. The corrosion-resistant finishes and robust frames contribute to a longer lifespan, reducing the total cost of ownership over time.

The YCZ series also emphasizes indoor air quality, incorporating advanced filtration systems that enhance air cleanliness. This is crucial for commercial spaces where air quality directly impacts occupant health and productivity. Furthermore, the units can be easily integrated with additional ventilation systems, ensuring compliance with stringent air quality standards.

In summary, the Trane YCZ035F1 and YCZ036F1/3M0B are exemplary examples of advanced HVAC technology, offering flexible configurations, superior energy efficiency, durability, and enhanced indoor air quality. Businesses looking for reliable and efficient HVAC solutions will find these rooftop units to be an excellent choice for their commercial applications.