Trane CG-PRC007-EN manual 20-25Ton, Table PD-3 20Ton CGAF-C20, Table PD-4 25Ton CGAF-C25

Page 22

Performance

(20–25Ton)

Data — 60 HZ

Full Load

 

 

 

 

Table PD-3 — 20Ton — CGAF-C20

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

75.0

 

85.0

 

 

95.0

 

105.0

 

115.0

 

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

(Deg F)

Glycol

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

20

28

12.0

15.6

9.2

11.4

17.3

8.0

 

10.8

19.2

6.8

10.1

21.3

5.7

9.4

23.8

4.8

25

24

13.4

16.0

10.0

12.7

17.7

8.6

 

12.1

19.6

7.4

11.3

21.8

6.2

10.6

24.3

5.2

30

19

14.8

16.4

10.8

14.1

18.1

9.4

 

13.4

20.1

8.0

12.6

22.3

6.8

11.8

24.9

5.7

35

14

16.4

16.9

11.6

15.6

18.6

10.1

14.8

20.6

8.6

14.0

22.9

7.3

13.1

25.4

6.2

40

0

18.1

17.4

12.5

17.3

19.2

10.9

16.4

21.2

9.3

15.5

23.5

7.9

14.5

26.1

6.7

42

0

18.8

17.6

12.8

18.0

19.4

11.1

17.0

21.4

9.6

16.1

23.7

8.1

15.1

26.3

6.9

44

0

19.5

17.8

13.2

18.6

19.6

11.4

17.7

21.6

9.8

16.7

24.0

8.3

15.6

26.5

7.1

45

0

19.8

17.9

13.3

18.9

19.7

11.5

18.0

21.7

9.9

17.0

24.1

8.5

15.9

26.7

7.1

46

0

20.1

18.0

13.5

19.2

19.8

11.7

18.3

21.8

10.0

17.3

24.2

8.6

16.2

26.8

7.2

48

0

20.8

18.2

13.8

19.9

20.0

11.9

18.9

22.1

10.3

17.9

24.4

8.8

16.7

27.0

7.4

50

0

21.5

18.4

14.1

20.6

20.2

12.2

19.5

22.3

10.5

18.5

24.7

9.0

17.3

27.3

7.6

55

0

23.3

18.9

14.8

22.3

20.8

12.9

21.2

22.9

11.1

20.0

25.3

9.5

18.8

27.9

8.1

60

0

25.2

19.4

15.5

24.0

21.4

13.5

22.9

23.5

11.7

21.6

26.0

10.0

20.3

28.6

8.5

Table PD-4 — 25Ton — CGAF-C25

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

 

 

 

75.0

 

85.0

 

95.0

 

105.0

 

115.0

 

 

 

 

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

 

(Deg F)

Glycol

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

 

 

20

28

15.6

20.9

8.9

14.8

22.9

7.8

14.0

25.2

6.7

13.2

27.8

5.7

12.3

30.7

4.8

 

 

25

24

17.4

21.4

9.7

16.5

23.4

8.5

15.7

25.8

7.3

14.7

28.4

6.2

13.8

31.4

5.3

 

 

30

19

19.3

21.9

10.6

18.4

24.0

9.2

17.4

26.4

7.9

16.4

29.1

6.8

15.4

32.1

5.8

 

 

35

14

21.3

22.5

11.4

20.4

24.6

9.9

19.3

27.0

8.6

18.2

29.8

7.4

17.1

32.8

6.3

 

 

40

0

23.7

23.1

12.3

22.6

25.3

10.7

21.5

27.8

9.3

20.3

30.6

8.0

19.1

33.7

6.8

 

 

42

0

24.6

23.3

12.6

23.5

25.5

11.0

22.3

28.0

9.5

21.1

30.8

8.2

19.8

34.0

7.0

 

 

44

0

25.4

23.6

13.0

24.3

25.8

11.3

23.1

28.3

9.8

21.9

31.1

8.4

20.6

34.3

7.2

 

 

45

0

25.9

23.7

13.1

24.7

25.9

11.5

23.5

28.4

9.9

22.3

31.3

8.5

21.0

34.4

7.3

 

 

46

0

26.3

23.8

13.3

25.2

26.0

11.6

23.9

28.6

10.0

22.7

31.4

8.7

21.3

34.6

7.4

 

 

48

0

27.3

24.1

13.6

26.0

26.3

11.9

24.8

28.9

10.3

23.5

31.7

8.9

22.1

34.9

7.6

 

 

50

0

28.2

24.3

13.9

26.9

26.6

12.2

25.6

29.2

10.6

24.3

32.0

9.1

22.9

35.2

7.8

 

 

55

0

30.6

25.0

14.7

29.2

27.3

12.9

27.8

29.9

11.2

26.4

32.8

9.6

24.9

36.1

8.3

 

 

 

60

0

33.0

25.6

15.5

31.6

28.0

13.5

30.1

30.7

11.8

28.6

33.7

10.2

27.0

36.9

8.8

 

 

Notes:

1.Data based on 0.0001 fouling factor at sea level.

2.Interpolation between points is permissible.

3.Extrapolation beyond points is not permissible.

4.EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power.

5.Ratings based on evaporator drop of 10°F.

6.Rated in accordance with ARI Standard 550/590-98.

7.Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°F.

8.Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

22

CG-PRC007-EN

Image 22
Contents Air-Cooled Liquid Chillers Introduction 10, 15Tons 20-60TonsContents 10-60Ton FeaturesBenefits 10-15Ton FlexibilityOptional Features Standard FeaturesOther Standard Features 20-60TonEnhanced Controls Tracer control points for IntelliPak ChillersSimple Design with 70% Fewer Parts Proven DesignThroughTesting and ResearchTrane 3-D Scroll Compressor LowTorqueVariationServicing SettingThe UnitIsolation and Sound Emission Unit Location GeneralProvide Lateral Clearance Walled Enclosure InstallationsProvideVertical Clearance Provide Sufficient Unit-to-Unit ClearanceLow Ambient Operation Temperature ControllerLeaving SolutionTemperature range High Ambient OperationGallon Minimum LoopVolume SupplyWaterTemperature DropExample CGAFC50 with 100 gpm. Minimum LoopVolume = Series Operation10, 15Ton Application Considerations20-60Ton Selection Procedure Given10, 15Tons Model Number Description20-60Tons General Data Table GD-1 General Data 10-60Ton UnitsPerformance Adjustment Factors ∆ TWater Drop Pressure Performance Adjustment Factors Performance Adjustment Factors Full Load PerformanceData 60 HZ Table PD-1 10 Ton CGATable PD-3 20Ton CGAF-C20 20-25TonTable PD-4 25Ton CGAF-C25 Table PD-5- 30Ton CGAF-C30 30-40TonTable PD-6 40Ton CGAF-C40 Table PD-7- 50Ton CGAF-C50 50-60TonTable PD-8- 60Ton CGAF-C60 10-30Ton Data 50 HZTable PD-16 50Ton CGAF-C50 40-60TonTable PD-15 40Ton CGAF-C40 Table PD-17- 60Ton CGAF-C60Table PD-18- Part Load Data,ARI Points 10-60Tons Part LoadTable PD-18 Part Load Data,ARI Points 10-60Tons Table PD-21 20Ton CGAF-C20 Table PD-19 10Ton CGATable PD-20 15Ton CGA Table PD-22 25Ton CGAF-C25Table PD-25- 50Ton CGAF-C50 Table PD-24- 40Ton CGAF-C40Table PD-26- 60Ton CGAF-C60 Controls Systems Required FeaturesInterface with Other Control Trane Integrated Comfort System InterfaceControls 10, 15Ton10, 15 Ton Field Installed Head Pressure Control AccessoryTon Operation Controls 20-60 Ton Safety ControlsMonitoring and Diagnostics Customized ControlHuman Interface HI Panel Standard Control Features20-60Ton Controls Interface Main Menu of the Human Interface panelOptional Control Features 4 analog outputs can be assigned to 5 binary outputs can be assignedOne binary output can be assigned to Load Definitions Electrical 10-60Ton Data 60 HZTable ED-1 Electrical Data Electrical 10-60Ton Data 50 HZ Table ED-2 Electrical DataDimensional 10Ton Data Figure DD-1 CGA-120B Unit DimensionsDimensional 15Ton Data Figure DD-2 CGA-180B Unit DimensionsDimensional 20Ton Data Figure DD-3 CGAF-C20 Unit DimensionsDimensional 25Ton Data Figure DD-4 CGAF-C25 Unit DimensionsDimensional 30Ton Data Figure DD-5 CGAF-C30 Unit DimensionsDimensional 40Ton Data Figure DD-6 CGAF-C40 Unit DimensionsDimensional 50Ton Data Figure DD-7 CGAF-C50 Unit DimensionsDimensional 60Ton Data Figure DD-8- CGAF-C60 Unit DimensionsTableW-2 Approximate CornerWeights lbs 15-Ton Unit WeightsTableW-1 Approximate CornerWeights lbs 10-Ton Unit Table W-3 Cgaf Unit Weights lbsMechanical 10-15TonSpecifications Mechanical 20-60TonSpecifications Compressor Current Sensing CSM Zone Sensor Chilled Solution ResetIce Building Unit Mounted DisconnectCG-PRC007-EN Trane

CG-PRC007-EN specifications

The Trane CG-PRC007-EN is a robust product within the Trane line of commercial rooftop units, designed to meet the heating and cooling needs of various commercial applications. This unit showcases advanced technologies and features aimed to enhance efficiency, reliability, and user comfort.

One of the standout characteristics of the CG-PRC007-EN is its commitment to energy efficiency. The unit incorporates high-efficiency compressors and a variable-speed fan motor, ensuring that the system can adjust its operation based on the demand, thus optimizing energy consumption. This is particularly advantageous in commercial settings, where climate control requirements can fluctuate throughout the day.

Additionally, the unit is engineered with a smart control system that allows for easy integration with building management systems. This feature enables real-time monitoring and adjustments, helping facility managers maintain optimal comfort levels while also minimizing operational costs. Users are able to access performance data and system diagnostics remotely, promoting proactive maintenance and reducing downtime.

Durability and longevity are critical factors for commercial HVAC systems, and the CG-PRC007-EN is designed with this in mind. The unit features a corrosion-resistant cabinet and components that withstand harsh weather conditions, ensuring reliability in outdoor installations. Its robust construction helps mitigate noise levels, resulting in a quieter operation that is ideal for noise-sensitive environments.

Another key technology within this unit is its advanced airflow management system. This system is designed to provide consistent airflow, enhancing indoor air quality and ensuring that every corner of the space benefits from appropriate heating or cooling. The CG-PRC007-EN also offers a variety of customization options for air filters, ensuring that the specific needs of each application are met.

Furthermore, the unit is compliant with the latest environmental regulations, including those set forth by the EPA. It utilizes eco-friendly refrigerants that minimize environmental impact without sacrificing performance. This makes the CG-PRC007-EN an excellent choice for companies committed to sustainability and energy efficiency.

In summary, the Trane CG-PRC007-EN combines innovative technology, energy efficiency, and reliability, making it an ideal solution for commercial heating and cooling needs. Its advanced features, durability, and eco-friendly design position it as a leader in the commercial rooftop unit market.