Trane CG-PRC007-EN manual Selection Procedure, Given

Page 14

Selection Procedure

The chiller capacity tables presented in the “Performance Data” section cover the most frequently encountered leaving water temperatures.The tables reflect a 10°F temperature drop through the evaporator. For temperature drops other than 10°F, fouling factors other than 0.0001 (in accordance with ARI Standard 550/590-98) and for units operating at altitudes that are significantly greater than sea level, refer to the “Performance Adjustment Factors” section and apply the appropriate adjustment factors. For chilled brine selections, refer to the “Performance Adjustment Factors” section for ethylene glycol adjustment factors.

To select aTrane air-cooled chiller, the following information is required:

1

Design system load (in tons of refrigeration).

2

Design leaving chilled water temperature.

3

Design chilled water temperature drop.

4

Design ambient temperature.

5

Evaporator fouling factor.

Evaporator chilled water flow rate can be determined by using the following formula:

Tons x 24

GPM = Temperature Drop (Degrees F)

NOTE: Flow rate must fall within the limits specified in the “General Data” section of this catalog.

SELECTION EXAMPLE

Given:

Required System Load = 53 tons

Leaving ChilledWaterTemperature (LCWT) = 45°F

ChilledWaterTemperature Drop = 10°F

Design AmbientTemperature = 95°F

Evaporator Fouling Factor = 0.0001

1

To calculate the required chilled waterflow rate we use the formula:

GPM = Tons x 24

T

From the 60 ton unit table in the “Performance Data” section of this catalog, a CGAF-C60 at the given conditions will produce 57.3 tons with a system power input of 70.2 kw and a unit EER of 9.8

GPM = 56.8 Tons x 24 = 137.5

10°F

2

To determine the evaporator water pressure drop we use the flow rate (gpm) and the evaporator water pressure drop curves found in the “Performance Adjustment Factors” section of this catalog. Entering the curve at 137.5 gpm, the pressure drop for a nominal 60 ton evaporator is 16.5 feet.

3

For selection of chilled brine units or applications where the altitude is significantly greater than sea level or the temperature drop is different than 10°F, the performance adjustment factors should be applied at this point.

For example:

Corrected Capacity = Capacity

(unadjusted) x Appropriate Adjustment

Factor

Corrected Flow Rate = Flow Rate

(unadjusted) x Appropriate Adjustment

Factor

Corrected KW Input = KW Input

(unadjusted) x Appropriate Adjustment

Factor

4

Verify that the selection is within design guidelines.The final unit selection is:

Quantity (1) CGAF-C60

Cooling Capacity = 57.3Tons

Entering/Leaving ChilledWater

Temperatures = 55/45°F

ChilledWaterflow Rate (GPM) = 137.5

EvaporatorWater Pressure Drop = 16.5 ft.

System Power Input = 70.2 KW

Unit EER = 9.8

MINIMUM LEAVING CHILLEDWATER TEMPERATURE SET POINTS

The minimum leaving chilled water temperature set point for water is listed in the following table:

Table SP-1 — Minimum Leaving Chilled WaterTemperature Set points forWater1

Evaporator

Minimum Leaving Chilled Water

Temperature

Temperature Set point (°F)

Difference

CGAF-

CGAF-

(Degrees F)

C20,C25,C30

C40,C50,C60

6

40

39

8

41

39

10

42

40

12

43

40

14

44

41

16

45

41

18

46

42

1These are for units without HGBP, for units with HGBP, add 2°F to each minimum temperature in the table.

For those applications requiring lower set points, a glycol solution must be used. The minimum leaving chilled water set point for a glycol solution can be calculated using the following equation:

LCWS (Minimum) = GFT + 5 + T (Evap)

# of stages of capacity.

LCWS =

Leaving ChilledWater

 

 

Set point (F)

GFT

=

Glycol Freezing

T

 

Temperature (F)

=

DeltaT (the difference

between the temperature of the water entering and leaving the evaporator)

Solution freezing point temperatures can be found in the Performance Data section and the number of stages of capacity in the General Data section. For selection assistance, refer to the CGA Chiller Selection program.

14

CG-PRC007-EN

Image 14
Contents Air-Cooled Liquid Chillers Introduction 10, 15Tons 20-60TonsContents Benefits Features10-60Ton 10-15Ton FlexibilityOptional Features Standard FeaturesOther Standard Features 20-60TonEnhanced Controls Tracer control points for IntelliPak ChillersSimple Design with 70% Fewer Parts Proven DesignThroughTesting and ResearchTrane 3-D Scroll Compressor LowTorqueVariationServicing SettingThe UnitIsolation and Sound Emission Unit Location GeneralProvide Lateral Clearance Walled Enclosure InstallationsProvideVertical Clearance Provide Sufficient Unit-to-Unit ClearanceLow Ambient Operation Temperature ControllerLeaving SolutionTemperature range High Ambient OperationGallon Minimum LoopVolume SupplyWaterTemperature DropExample CGAFC50 with 100 gpm. Minimum LoopVolume = Series Operation20-60Ton Application Considerations10, 15Ton Selection Procedure Given20-60Tons Model Number Description10, 15Tons General Data Table GD-1 General Data 10-60Ton UnitsPerformance Adjustment Factors ∆ TWater Drop Pressure Performance Adjustment Factors Performance Adjustment Factors Full Load PerformanceData 60 HZ Table PD-1 10 Ton CGATable PD-4 25Ton CGAF-C25 20-25TonTable PD-3 20Ton CGAF-C20 Table PD-6 40Ton CGAF-C40 30-40TonTable PD-5- 30Ton CGAF-C30 Table PD-8- 60Ton CGAF-C60 50-60TonTable PD-7- 50Ton CGAF-C50 10-30Ton Data 50 HZTable PD-16 50Ton CGAF-C50 40-60TonTable PD-15 40Ton CGAF-C40 Table PD-17- 60Ton CGAF-C60Table PD-18 Part Load Data,ARI Points 10-60Tons Part LoadTable PD-18- Part Load Data,ARI Points 10-60Tons Table PD-21 20Ton CGAF-C20 Table PD-19 10Ton CGATable PD-20 15Ton CGA Table PD-22 25Ton CGAF-C25Table PD-26- 60Ton CGAF-C60 Table PD-24- 40Ton CGAF-C40Table PD-25- 50Ton CGAF-C50 Controls Systems Required FeaturesInterface with Other Control Trane Integrated Comfort System InterfaceControls 10, 15TonTon Operation Field Installed Head Pressure Control Accessory10, 15 Ton Controls 20-60 Ton Safety ControlsMonitoring and Diagnostics Customized ControlHuman Interface HI Panel Standard Control Features20-60Ton Controls Interface Main Menu of the Human Interface panelOptional Control Features One binary output can be assigned to 5 binary outputs can be assigned4 analog outputs can be assigned to Table ED-1 Electrical Data Electrical 10-60Ton Data 60 HZLoad Definitions Electrical 10-60Ton Data 50 HZ Table ED-2 Electrical DataDimensional 10Ton Data Figure DD-1 CGA-120B Unit DimensionsDimensional 15Ton Data Figure DD-2 CGA-180B Unit DimensionsDimensional 20Ton Data Figure DD-3 CGAF-C20 Unit DimensionsDimensional 25Ton Data Figure DD-4 CGAF-C25 Unit DimensionsDimensional 30Ton Data Figure DD-5 CGAF-C30 Unit DimensionsDimensional 40Ton Data Figure DD-6 CGAF-C40 Unit DimensionsDimensional 50Ton Data Figure DD-7 CGAF-C50 Unit DimensionsDimensional 60Ton Data Figure DD-8- CGAF-C60 Unit DimensionsTableW-2 Approximate CornerWeights lbs 15-Ton Unit WeightsTableW-1 Approximate CornerWeights lbs 10-Ton Unit Table W-3 Cgaf Unit Weights lbsMechanical 10-15TonSpecifications Mechanical 20-60TonSpecifications Compressor Current Sensing CSM Zone Sensor Chilled Solution ResetIce Building Unit Mounted DisconnectCG-PRC007-EN Trane

CG-PRC007-EN specifications

The Trane CG-PRC007-EN is a robust product within the Trane line of commercial rooftop units, designed to meet the heating and cooling needs of various commercial applications. This unit showcases advanced technologies and features aimed to enhance efficiency, reliability, and user comfort.

One of the standout characteristics of the CG-PRC007-EN is its commitment to energy efficiency. The unit incorporates high-efficiency compressors and a variable-speed fan motor, ensuring that the system can adjust its operation based on the demand, thus optimizing energy consumption. This is particularly advantageous in commercial settings, where climate control requirements can fluctuate throughout the day.

Additionally, the unit is engineered with a smart control system that allows for easy integration with building management systems. This feature enables real-time monitoring and adjustments, helping facility managers maintain optimal comfort levels while also minimizing operational costs. Users are able to access performance data and system diagnostics remotely, promoting proactive maintenance and reducing downtime.

Durability and longevity are critical factors for commercial HVAC systems, and the CG-PRC007-EN is designed with this in mind. The unit features a corrosion-resistant cabinet and components that withstand harsh weather conditions, ensuring reliability in outdoor installations. Its robust construction helps mitigate noise levels, resulting in a quieter operation that is ideal for noise-sensitive environments.

Another key technology within this unit is its advanced airflow management system. This system is designed to provide consistent airflow, enhancing indoor air quality and ensuring that every corner of the space benefits from appropriate heating or cooling. The CG-PRC007-EN also offers a variety of customization options for air filters, ensuring that the specific needs of each application are met.

Furthermore, the unit is compliant with the latest environmental regulations, including those set forth by the EPA. It utilizes eco-friendly refrigerants that minimize environmental impact without sacrificing performance. This makes the CG-PRC007-EN an excellent choice for companies committed to sustainability and energy efficiency.

In summary, the Trane CG-PRC007-EN combines innovative technology, energy efficiency, and reliability, making it an ideal solution for commercial heating and cooling needs. Its advanced features, durability, and eco-friendly design position it as a leader in the commercial rooftop unit market.