Controls | (10, 15Ton) |
|
|
|
|
ELECTRICAL CONTROL SYSTEM
The controls used on CGA 10 and
Refer to the following control descriptions for control settings.
UNIT SAFETY CONTROLS
Low Pressure Cutout (LPC01, LPC02)
Mounted below the unit control box are two low pressure cutouts that open and stop compressor operation if the operating pressure drops below 38.5 + 1 psig.The cutout automatically resets when the pressure reaches 44.5 + 2 psig. The LPCO is a SPDT device. If it opens at low ambient
High Pressure Cutout (HPC01, HPC02)
These units have high pressure cutouts that open and stop compressor operation if the discharge pressure reaches 400 + 10 psig.The cutout automatically resets when pressure drops to 250 + 15 psig.
Reset Relays (RRS, RR2)
If the unit is shut down by the low pressure cutout (or high pressure cutout), the reset relay locks out the compressor contactor (CCS, CC2).This prevents the system from recycling until the condition that caused the low (or high) pressure cutout to trip is determined and corrected.
CAUTION:To prevent unit damage, do not reset the control circuit until the cause of the safety lockout is identified and corrected.
To reset RR1 and RR2, open and reclose the unit disconnect switch.
LowTemperature Cutout (LTC)
The LTC is designed to disable the unit if the leaving water temperature falls too low.The LTC’s remote sensing bulb is
mounted at the outlet end of the evaporator, where it monitors leaving water temperature.
During normal unit operation, if the low temperature cutout (LTC) senses a temperature falling to 36°F + 3.0°F, the LTC will open to interrupt compressor operation. (Manual reset is required.)
Motor Overloads
These units have internal compressor and condenser fan motor overloads. These overloads protect the motors from overcurrent and overheating conditions and automatically reset as soon as they cool sufficiently.
UNIT OPERATIONAL CONTROLS
WaterTemperatureThermostat (WTT)
System operation for 10 and
Low Ambient StartTimer (LAST)
When one of the two timers energizes, the low pressure control is bypassed for four minutes, this allows time for suction pressure to build sufficiently for the low pressure cutout contacts to close.
Hot Gas BypassTimer, Solenoid (HGBT, HGBS)
The hot gas bypass option is factory- installed only, and is used in a chilled water system to keep the first stage compressor
The adjustable hot gas bypass valve is factory set at 70 psig.
Note: Hot gas bypass is available only on the lead compressor circuit.
Anti-Short CycleTimers (ASCT1,ASCT2)
An
Delay Between Compressors (DBC)
The delay between compressors prevents both compressors from starting at the same time by delaying compressor number two for 30 seconds.
Definition of Abbreviations:
ASCT | — | |
CC | — | Compressor Contactor |
CWFIR | — | ChilledWater Flow |
|
| Interlock Relay |
CWPS | — | ChilledWater Pump |
|
| Starter |
DBC | — | Time Delay Between |
|
| Compressors |
HGBT | — | Hot Gas BypassTimer |
HPCO | — | High Pressure Cutout |
LAST | — | Low Ambient Start |
|
| Timer |
LPCO | — | Low Pressure Cutout |
LTC | — | LowTemperature |
|
| Cutout |
ODF | — | Outdoor Fan |
RR | — | Reset Relay |
SPDT | — | Single Pole, Double |
|
| Throw |
WTT | — | WaterTemperature |
|
| Thermostat |
31 |