Greenheck Fan dimensions Amca 5.3 Pressure Drop SMD-302M

Page 4

AMCA 5.3 Pressure Drop

SMD-302M

5D

6D

24x24

12x12

36x36

48x12

12x48

 

* Sizes are in inches.

12 in. x 12 in. (305mm x 305mm)

 

Pressure Drop

Velocity (fpm)

(in. wg)

500

0.01

1000

0.06

1500

0.13

2000

0.23

2500

0.37

3000

0.53

3500

0.73

4000

0.95

24 in. x 24 in. (610mm x 610mm)

 

Pressure Drop

Velocity (fpm)

(in. wg)

500

0.01

1000

0.02

1500

0.06

2000

0.10

2500

0.16

3000

0.23

3500

0.32

4000

0.42

36in. x 36 in. (914mm x 914mm)

 

Pressure Drop

Velocity (fpm)

(in. wg)

500

0.01

1000

0.02

1500

0.05

2000

0.09

2500

0.14

3000

0.21

3500

0.29

4000

0.38

12in. X 48 in. (305mm x 1219mm)

 

Pressure Drop

Velocity (fpm)

(in. wg)

500

0.01

1000

0.02

1500

0.06

2000

0.10

2500

0.16

3000

0.24

3500

0.33

4000

0.43

48 in. x 12 in. (1219mm x 305mm)

 

Pressure Drop

Velocity (fpm)

(in. wg)

500

0.01

1000

0.04

1500

0.10

2000

0.18

2500

0.29

3000

0.42

3500

0.57

4000

0.74

R

Greenheck Fan Corporation certifies that the model SMD-302M shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance ratings only.

Image 4
Contents Optional Features Model SMD-302M Smoke DampersUL 555S Leakage Rating Standard ConstructionPressure Drop Data SMD-302M Amca Test FiguresAmca 5.2 Pressure Drop SMD-302M In. wgAmca 5.3 Pressure Drop SMD-302M Amca 5.5 Pressure Drop SMD-302M Damper Sideplate and Sleeve Dimensional Data AccessoriesApplication Data Space Envelopes Required for ActuatorsSpecifications Transitioned Damper DimensionsDamper Sizing Information