Greenheck Fan dimensions Pressure Drop Data SMD-302M, Amca Test Figures

Page 2

Pressure Drop Data

SMD-302M

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All data has been corrected to represent standard air at a density of .075 lb/ft3 (1.201 kg/m3).

Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC system.

AMCA Test Figures

Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper.

Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high entrance and exit losses due to the sudden changes of area in the system.

5D

Figure 5.3

5D

6D

D4 (W) (H)

3.14

Figure 5.2

Figure 5.5

Image 2
Contents UL 555S Leakage Rating Optional FeaturesModel SMD-302M Smoke Dampers Standard ConstructionPressure Drop Data SMD-302M Amca Test FiguresAmca 5.2 Pressure Drop SMD-302M In. wgAmca 5.3 Pressure Drop SMD-302M Amca 5.5 Pressure Drop SMD-302M Application Data Damper Sideplate and Sleeve Dimensional DataAccessories Space Envelopes Required for ActuatorsDamper Sizing Information Transitioned Damper DimensionsSpecifications