Carrier HFC-134A installation instructions Rated DRY Weight and Refrigerant Capacity, A23-1634

Page 28

RATED DRY WEIGHT AND REFRIGERANT CAPACITY

ENGLISH (lb)

TANK

 

TANK OD

 

DRY

R-134a MAXIMUM REFRIGERANT CAPACITY (lb)

 

 

WEIGHT*

 

 

SIZE

 

 

(in.)

 

ANSI/ASHRAE 15

UL 1963

 

 

 

(lb)

 

 

 

 

 

 

 

 

0428

 

 

24.00

 

 

2334

1860

1716

0452

 

 

27.25

 

 

3414

3563

3286

 

 

 

 

 

 

 

SI (kg)

 

 

 

 

 

 

 

 

 

 

TANK

 

TANK OD

 

 

DRY

R-134a MAXIMUM REFRIGERANT CAPACITY (kg)

SIZE

 

 

(mm)

 

 

WEIGHT*

ANSI/ASHRAE 15

UL 1963

 

 

 

(kg)

 

 

 

 

 

 

 

 

0428

 

 

610

 

 

1059

844

778

0452

 

 

692

 

 

1549

1616

1491

 

 

 

LEGEND

 

 

 

ANSI

American National Standard Institute

 

 

ASHRAE — American Society of Heating, Refrigeration,

 

 

 

 

and Air Conditioning Engineers

 

 

 

OD

Outside Diameter

 

 

 

UL

Underwriters Laboratories

 

 

 

*The above dry weight includes the pumpout condensing unit weight of 164 lb (75 kg).

COOLER INLET

COOLER REFRIGERANT

COOLER CHARGING

ISOLATION VALVE 11

PUMPOUT VALVE

7

VALVE 1b

 

 

 

COOLER

CONDENSER

CHARGING

VALVE 1a

 

CONTROL CENTER

 

 

 

 

 

 

 

DISCHARGE ISOLATION

 

 

 

 

 

 

VALVE (OPTIONAL)

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

RELIEF SAFETY

 

 

 

 

 

VALVE

 

 

 

 

 

 

 

 

STORAGE

 

 

 

 

 

10

TANK LIQUID

 

 

 

 

 

 

VALVE

 

 

 

 

 

 

OIL

 

 

 

 

 

 

SEPARATOR

 

 

PUMPOUT

 

 

 

PUMPOUT

 

= SERVICE VALVE ON

COMPRESSOR

 

 

 

CONDENSER

 

= SERVICE VALVE ON

2

3

 

PUMPOUT

 

PUMPOUT UNIT

CHILLER (FIELD

 

 

 

SUPPLIED)

 

 

 

CONDENSER

 

 

4

5

 

WATER SUPPLY

 

= MAINTAIN AT LEAST 2 FT (610mm) CLEARANCE AROUND

 

 

 

 

 

AND RETURN

a23-1634

STORAGE TANK FOR SERVICE AND OPERATION WORK.

 

 

6 STORAGE TANK

 

 

 

 

 

VAPOR VALVE

 

 

 

 

 

 

Fig. 39 — Optional Pumpout System Piping Schematic with Storage Tank

(Configured to Push Liquid into Storage Tank)

28

Image 28
Contents Installation Instructions Contents Model Number Identification Typical 23XRV Components A23-155051A23-1551 A23-1553Control Center Components A23-1555 A23-155623XRV Dimensions Nozzle-In-Head Waterbox A23-155723XRV Dimensions Marine Waterbox 23XRV Compressor Weights23XRV Component Weights TR Compressor 23XRV Waterbox Nozzle Sizes23XRV Heat Exchanger Data 23XRV Additional Data for Cooler Marine Waterboxes23XRV Waterbox Cover Weights SI kg 23XRV Waterbox Cover Weights English lb23XRV Additional Data for Condenser Marine Waterboxes Electrical Cable Routing Top View Cooler/Discharge Pipe Assembly Removal A23-1563 A23-1635A23-1564 A23-1567 A23-1565A23-1570 A23-1571 Cables A23-1561Control Panel Inputs A23-1568 A23-1569Compressor Fastener Identification A23-1572Oil Concentrator Removal A23-1573Oil Reclaim Piping Motor Terminal Box A23-1576A23-1578 A23-1579COUPLINGSA23-46 A23-1534A19-1109 A19-1110 A23-1537 A23-1580 A23-1538 A23-1581A23-1539 A23-1540A23-1541 A23-1543Rated DRY Weight and Refrigerant Capacity A23-1634A23-1544 A23-1545Pumpout Unit Relief Valve ArrangementsRelief Valve Locations Close the door to the control centerTypical Field Wiring Schematic A23-1585A23-1586 Typical Field Wiring Schematic Lug Capacity A23-1587PIC III Control Component Layout A23-1584Page 23XRV Controls Schematic A23-1588A23-1589 A23-1591 A23-1590 A23-1592CCN Communication Wiring For Multiple Chillers Typical A23-159323XRV with Unit-Mounted VFD/Control Center A23-1594A23-1595 Cable ManufacturersA23-1596 Install Field Insulation and Lagging Insulator CodesLead/Lag Control Wiring A23-1597A23-1598 23XRV Insulation Area A23-1599Page Page Copyright 2006 Carrier Corporation Installation START-UP Request Checklist Testing YES/NO Date to be Completed