Carrier HFC-134A installation instructions 23XRV Dimensions Nozzle-In-Head Waterbox, A23-1557

Page 8

TUBE REMOVAL SPACE FOR EITHER END SIZES 30-32, 40-42, 50-52

12’-7½” (3848 mm) SIZES 35-37, 45-47, 55-57

14’-4” (4369 mm)

0’-3”

4’-10”

0’-3”

0’-5”

MOTOR SERVICE

 

CLEARANCE

 

1’ - 10” (559 mm)

FRAME R COMPRESSOR 3’ - 0” (915mm)

 

 

RECOMMENDED OVERHEAD SERVICE CLEARANCE

C

2’ MIN

(610 mm)

B

 

A

(WIDEST POINT)

 

 

SERVICE AREA

 

4’ - 10” MIN

a23-1557

 

(1219 mm)

 

 

Fig. 9 — 23XRV Dimensions (Refer to Tables 2 and 3)

Table 1 — Drive Assembly and Power Module Ratings

 

 

ENCLOSURE

INPUT

MAX INPUT

MAX OUTPUT

CARRIER PART NUMBER

FRAME SIZE

VOLTAGE (V)

CURRENT

CURRENT* at 4kHZ

TYPE

 

 

RANGE

(AMPS)

(AMPS)

 

 

 

23XRA2AA_ _ _ _ _ _ _ _ _ _ _

Frame 2AA

NEMA 1

380 to 460

440

442

23XRA2BA_ _ _ _ _ _ _ _ _ _ _

Frame 2BA

NEMA 1

380 to 460

520

442

23XRA2BB_ _ _ _ _ _ _ _ _ _ _

Frame 2BB

NEMA 1

380 to 460

520

520

23XRA2CC_ _ _ _ _ _ _ _ _ _ _

Frame 2CC

NEMA 1

380 to 460

608

608

*110% output current capability for one minute, 150% output current for 5 seconds.

Table 2 — 23XRV Dimensions (Nozzle-In-Head Waterbox)

HEAT EXCHANGER

 

A (Length, with Nozzle-in-Head Waterbox)

 

 

B (Width)

C (Height)

1 Pass

2-Pass*

3 Pass†

 

SIZE

 

 

 

 

 

 

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

ft-in.

mm

30 to 32

14- 31/4

4350

13- 81/4

4172

14- 31/4

4350

6-

4

1930

7-25/8

2200

35 to 37

15-113/4

4870

15- 43/4

4693

15-113/4

4870

6-

4

1930

7-25/8

2200

40 to 42

14- 9

4496

14- 31/8

4347

14- 6

4420

6- 8½

2045

7-6½

2299

45 to 47

16- 51/2

5017

15-115/8

4867

16- 21/2

4940

6- 8½

2045

7-6½

2299

50 to 52

14-10

4521

14- 41/2

4382

14- 61/2

4432

6-113/4

2127

7-63/4

2305

55 to 57

16- 61/2

5042

16- 1

4902

16- 3

4953

6-113/4

2127

7-63/4

2305

*Assumes both cooler and condenser nozzles on same end of chiller.

†1 or 3 pass length applies if either (or both) cooler or condenser is a 1 or 3 pass design.

NOTES:

1.Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.

2.Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.

3.Certified drawings available upon request.

4.Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.

5.‘A’ length dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/or flanges will add length. See certified drawings.

6.Dished head waterbox covers not available for 3 pass design.

8

Image 8
Contents Installation Instructions Contents Model Number Identification Typical 23XRV Components A23-155051 A23-1551 A23-1553Control Center Components A23-1555 A23-155623XRV Dimensions Nozzle-In-Head Waterbox A23-155723XRV Dimensions Marine Waterbox 23XRV Compressor Weights23XRV Component Weights TR Compressor 23XRV Waterbox Nozzle Sizes23XRV Heat Exchanger Data 23XRV Additional Data for Cooler Marine Waterboxes23XRV Additional Data for Condenser Marine Waterboxes 23XRV Waterbox Cover Weights English lb23XRV Waterbox Cover Weights SI kg Electrical Cable Routing Top View Cooler/Discharge Pipe Assembly Removal A23-1564 A23-1635A23-1563 A23-1570 A23-1565A23-1567 A23-1571 Cables A23-1561Control Panel Inputs A23-1568 A23-1569Compressor Fastener Identification A23-1572Oil Concentrator Removal A23-1573Oil Reclaim Piping Motor Terminal Box A23-1576A23-1578 A23-1579COUPLINGSA19-1109 A19-1110 A23-1534A23-46 A23-1537 A23-1580A23-1538 A23-1581A23-1539 A23-1540A23-1541 A23-1543Rated DRY Weight and Refrigerant Capacity A23-1634A23-1544 A23-1545Pumpout Unit Relief Valve ArrangementsRelief Valve Locations Close the door to the control centerTypical Field Wiring Schematic A23-1585A23-1586 Typical Field Wiring Schematic Lug Capacity A23-1587PIC III Control Component Layout A23-1584Page 23XRV Controls Schematic A23-1588A23-1589 A23-1591 A23-1590 A23-1592CCN Communication Wiring For Multiple Chillers Typical A23-159323XRV with Unit-Mounted VFD/Control Center A23-1594A23-1596 Cable ManufacturersA23-1595 Install Field Insulation and Lagging Insulator CodesLead/Lag Control Wiring A23-1597A23-1598 23XRV Insulation Area A23-1599Page Page Copyright 2006 Carrier Corporation Installation START-UP Request Checklist Testing YES/NO Date to be Completed