TUBE REMOVAL SPACE FOR EITHER END SIZES
MOTOR SERVICE |
|
CLEARANCE |
|
1’ - 10” (559 mm) | FRAME R COMPRESSOR 3’ - 0” (915mm) |
| |
| RECOMMENDED OVERHEAD SERVICE CLEARANCE |
C
2’ MIN
(610 mm)
B
| A | (WIDEST POINT) |
|
| |
SERVICE AREA |
| 4’ - 10” MIN |
|
| (1219 mm) |
|
|
Fig. 9 — 23XRV Dimensions (Refer to Tables 2 and 3)
Table 1 — Drive Assembly and Power Module Ratings
|
| ENCLOSURE | INPUT | MAX INPUT | MAX OUTPUT | |
CARRIER PART NUMBER | FRAME SIZE | VOLTAGE (V) | CURRENT | CURRENT* at 4kHZ | ||
TYPE | ||||||
|
| RANGE | (AMPS) | (AMPS) | ||
|
|
| ||||
23XRA2AA_ _ _ _ _ _ _ _ _ _ _ | Frame 2AA | NEMA 1 | 380 to 460 | 440 | 442 | |
23XRA2BA_ _ _ _ _ _ _ _ _ _ _ | Frame 2BA | NEMA 1 | 380 to 460 | 520 | 442 | |
23XRA2BB_ _ _ _ _ _ _ _ _ _ _ | Frame 2BB | NEMA 1 | 380 to 460 | 520 | 520 | |
23XRA2CC_ _ _ _ _ _ _ _ _ _ _ | Frame 2CC | NEMA 1 | 380 to 460 | 608 | 608 |
*110% output current capability for one minute, 150% output current for 5 seconds.
Table 2 — 23XRV Dimensions (Nozzle-In-Head Waterbox)
HEAT EXCHANGER |
| A (Length, with |
|
| B (Width) | C (Height) | |||||
1 Pass | 3 Pass† |
| |||||||||
SIZE |
|
|
|
|
| ||||||
|
| mm | mm | mm | mm | mm | |||||
30 to 32 | 14- 31/4 | 4350 | 13- 81/4 | 4172 | 14- 31/4 | 4350 | 6- | 4 | 1930 | 2200 | |
35 to 37 | 4870 | 15- 43/4 | 4693 | 4870 | 6- | 4 | 1930 | 2200 | |||
40 to 42 | 14- 9 | 4496 | 14- 31/8 | 4347 | 14- 6 | 4420 | 6- 8½ | 2045 | 2299 | ||
45 to 47 | 16- 51/2 | 5017 | 4867 | 16- 21/2 | 4940 | 6- 8½ | 2045 | 2299 | |||
50 to 52 | 4521 | 14- 41/2 | 4382 | 14- 61/2 | 4432 | 2127 | 2305 | ||||
55 to 57 | 16- 61/2 | 5042 | 16- 1 | 4902 | 16- 3 | 4953 | 2127 | 2305 |
*Assumes both cooler and condenser nozzles on same end of chiller.
†1 or 3 pass length applies if either (or both) cooler or condenser is a 1 or 3 pass design.
NOTES:
1.Service access should be provided per American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 15, latest edition, National Fire Protection Association (NFPA) 70, and local safety code.
2.Allow at least 3 ft (915 mm) overhead clearance for service rigging for frame R compressor.
3.Certified drawings available upon request.
4.Marine waterboxes may add 6 in. to the width of the machine. See certified drawings for details.
5.‘A’ length dimensions shown are for standard 150 psi design and victaulic connections. The 300 psi design and/or flanges will add length. See certified drawings.
6.Dished head waterbox covers not available for 3 pass design.
8