Vinotemp VINO-1500SSW, WM-25SFCW manual Use of the adjustable low pressure control if applicable

Page 11

8.Use of the adjustable low pressure control (if applicable)

Cut out = 5 psig; Cut in = 25 psig; Differential = 20 psig

It may need to adjust the setting in the field to get the right cycle time.

Fig. 2.3 Adjustable Pressure Control

9. Condensing Unit Troubleshooting

Unit not running

a.

Incorrect power supply

a.

Check for proper voltage

b.

Incorrect or loose wirings

b.

Check all wirings and connections

c.

Failed components

c.

Check start relay, start capacitor, overload

 

 

 

protector, compressor.

d.

Liquid refrigerant in the compressor

d.

Call service for OEM information

e.

Low pressure switch shutting down the system

e.

Check for system restriction or low

 

 

 

refrigerant

- 10 -

Image 11
Contents WINE-MATESplit System Installation, Operation & Care Manual Table of Contents Important Safety Information CFM Cond Unit Feature DescriptionWM15-25SFCW Evaporator Unit Cellar Construction Evaporator Unit Installer’s InstructionCondensing Unit Pressure, Superheat and Subcooling Readings Air SensorRefrigeration Piping and Charging Complaint Possible Causes Valve OperationVINO1500-2500SSW Wiring Diagram Digital Controller Electrical WiringUse of the adjustable low pressure control if applicable Temperature Setting Temperature Control & Humidity AdjustmentPage Manual Defrost Moisture Removing Coil CleaningCare Guide User’s Troubleshooting Icing Unit runningToo long or EvaporatorCustomer Support Service under Warranty WarrantyLimited Warranty Limitation of Implied Warranty