Vinotemp VINO-2500SSW, WM-25SFCW, WM-15SFCW, VINO-1500SSW manual Manual Defrost

Page 14

2.The value of the set point will be displayed and the “°C” or “°F” LED starts blinking;

3.To change the Set value, push the o or n arrows within 10s.

4.To memorize the new set point value, push the SET key again or wait 10s.

4) Humidity Adjustment

The parameter Fon is used to adjust the humidity in the wine cabinet. The higher value of Fon, the higher relative humidity will be.

1.Press the Set + keys for 3 sec until the “°C” or “°F” LED starts blinking.

2.Release the keys, then push again the Set + keys for more than 7sec, the Pr2 label will be displayed.

3.Release the keys, select the required parameter Fon by up or down keys.

4.Press the “SET” key to display its value.

5.Use up or down keys to change its value.

6.The default value is 0, change high or low value to maintain high or low humidity.

7.Press “SET” to store the new value.

8.To exit: Press SET + or wait 15sec without pressing a key.

5) Regulation Differential

The parameter Hy is used as intervention differential for set point. Compressor cut-in is the set-point + Hy, and compressor cut-out is the set-point.

1.Press the Set + keys for 3 sec until the “°C” or “°F” LED starts blinking.

2.Release the keys, then push again the Set + keys for more than 7sec, the Pr2 label will be displayed.

3.Release the keys, HY will display immediately.

4.Press the “SET” key to display its value.

5.Use up or down keys to change its value.

6.The default value is 4, change high or low value to result in long high or short running cycle.

7.Press “SET” to store the new value.

8.To exit: Press SET + or wait 15sec without pressing a key.

6) Defrost Cycle

The parameter IdF is used as interval between defrost cycles.

1.Press the Set + keys for 3 sec until the “°C” or “°F” LED starts blinking.

2.Release the keys, then push again the Set + keys for more than 7sec, the Pr2 label will be displayed.

3.Release the keys, select the required parameter IdF by up or down keys.

4.Press the “SET” key to display its value.

5.Use up or down keys to change its value.

6.7. Press “SET” to store the new value.

8.To exit: Press SET + or wait 15sec without pressing a key.

7) Manual Defrost

Push the DEF key for more than 2 seconds and a manual defrost will start.

- 13 -

Image 14
Contents WINE-MATESplit System Installation, Operation & Care Manual Table of Contents Important Safety Information Feature Description CFM Cond UnitWM15-25SFCW Evaporator Unit Cellar Construction Evaporator Unit Installer’s InstructionCondensing Unit Pressure, Superheat and Subcooling Readings Air SensorRefrigeration Piping and Charging Valve Operation Complaint Possible CausesElectrical Wiring VINO1500-2500SSW Wiring Diagram Digital ControllerUse of the adjustable low pressure control if applicable Temperature Control & Humidity Adjustment Temperature SettingPage Manual Defrost Moisture Removing Coil CleaningCare Guide User’s Troubleshooting Evaporator Unit runningToo long or IcingCustomer Support Service under Warranty WarrantyLimited Warranty Limitation of Implied Warranty