Maintenance

Weekly: Inspect for bacterial growth and general operation conditions. Bacterial growth should be reported to your water treatment expert for immediate attention.

Monthly (Weekly at start up): Observe, touch, and listen to the fluid cooler. Become accustomed to its normal appearance, sound, and level of vibration. Abnormal aspects relating to the rotating equipment should be considered reason to shut down the fluid cooler until the problem can be located and corrected. Observe operation of the motor, coupling (or drive shaft), Geareducer, if equipped and fan. Become familiar with the normal operating temperature of the motor(s), as well as the sight and sound of all components as a whole.

If equipped, check for Geareducer oil leaks. Check the Geareducer as well as any optional oil lines to external oil dipstick/sight glass.

Inspect louvers, drift eliminators and basin trash screens and remove any debris or scale which may have accumulated. Replace any damaged or worn out components. Use of high-pressure water may damage the eliminator and louver material.

Clean the Thermal Equalizer™ trays above the coil removing any accu- mulated debris or scale.

Observe operation of the float valve. Depress the operating lever to make sure that the valve is operating freely. Inspect the suction screen for plug- ging. Remove any debris that may have accumulated.

Check for any buildup of silt on the floor of the collection basin. Mentally make note of the amount, if any, so future inspections will enable you to determine the rate at which it is forming.

Every 3 months: If equipped, lubricate fan shaft bearings. While rotating equipment by hand, grease the bearings until a bead forms around the seals—a maximum charge of 0.30 ounces (MHF702-MHF704) and 1.4 ounces (MHF706-MHF707) is recommended. Mobil SHC 460 grease is recommended.

Semi-Annually:If equipped, check the belt tension and condition.

If equipped, check Geareducer oil level. Shut down the unit and allow 5 minutes for the oil level to stabilize. Add oil if required.

If equipped with dampers, lubricate jack shaft bearings and tiebar linkage with silicone lubricant. If dampers are equipped with pneumatic or electric actuators, the manufacturer's recommended maintenance procedures should be observed. If dampers are exposed to heavy dust-laden air, oc- casional flushing of the bearings with water is recommended.

26

Image 26
Contents Marley MH Fluid Cooler Page Contents Safety First PreparationFluid Cooler Location Receiving Fluid Cooler InstallationTower Shipment Hoisting Fluid CoolerFluid Cooler Installation Motor Wiring When using a starterWhen using a two-speedstarter When using a VFDInstallation Mechanical Equipment Installation Water System OperationFluid Cooler Start-Up Operation Fluid Cooler Operation GeneralWintertime Operation Fan acceleration time of 30 seconds per hourOperation Intermittent Wintertime Operation Protection Against Coil FreezingModel Coil Volume Maintaining Water Quality MaintenanceWater Treatment and Blowdown Fluid Cooler Cleaning BlowdownBelt Tensioning Jacking Screws Straight Edge Sheave AlignmentFluid Cooler Maintenance Bushing Fastener Torque ValuesMaintenance Motor Relubrication Instructions Further instructionsSeasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies Services Maintenance Schedule Troubleshooting Trouble Cause RemedyTroubleshooting Additional Information Page SeaM05-116E

MHF702, MHF705 specifications

SPX Cooling Technologies has established itself as a leader in innovative cooling solutions, with the MHF705 and MHF702 units being prime examples of their commitment to efficiency and performance. These models are designed specifically for cooling processes in various industrial applications, providing reliable operation while minimizing energy consumption.

The MHF705 and MHF702 units are both equipped with advanced features that enhance their operational efficiency. One of the standout characteristics is their modular design, which allows for easy customization and scalability according to the system requirements. This flexibility makes them suitable for a wide range of applications, from HVAC systems to industrial cooling processes.

In terms of technology, both units utilize SPX’s proprietary air distribution system that optimizes airflow patterns within the unit. This ensures uniform cooling and reduces hot spots, contributing to enhanced overall performance. Additionally, the MHF series incorporates high-efficiency fans designed to reduce energy consumption while maximizing cooling output. These fans not only operate quietly but also have extended lifespans, reducing the need for frequent replacements.

Another significant feature of the MHF705 and MHF702 models is their robust construction. With materials designed to withstand harsh environmental conditions, including corrosion-resistant coatings, these units promise longevity and durability. This resilience is crucial for industries where reliability and minimal downtime are paramount.

The MHF series also excels in terms of maintainability. Features such as easily accessible components and modular serviceability make routine maintenance straightforward, which helps in limiting operational interruptions. Additionally, the units are designed with energy efficiency in mind, complying with various environmental standards, which reflects SPX's commitment to sustainability.

Both models also benefit from advanced control technologies, allowing for seamless integration with existing systems. Users can monitor and adjust settings easily via a user-friendly interface, ensuring optimal performance tailored to specific cooling demands.

In summary, SPX Cooling Technologies’ MHF705 and MHF702 units represent the pinnacle of modern cooling technology. With their advanced features, scalable design, high durability, and energy-efficient operation, these cooling solutions stand out as ideal choices for a diverse range of industrial applications, ensuring that businesses can rely on them for efficient and dependable cooling performance.