SPX Cooling Technologies 1200, 1000 manual Available Options, Plenum Walkway

Page 8

/ Available Options /

Accessory

Description and Remarks

 

 

Plywood Cold Water

Pressure-treated Douglas fir plywood collection

Collection Basin

basin for towers located above grade.

 

See page 11.

 

 

Bottom-Outlet Sump

Square-plan galvanized steel sump with bottom

 

outlet. Outlet connection is a hole and bolt circle

 

conforming to 125# ASME pipe connection.

 

Includes a plugged drain connection in sump

 

bottom.

 

 

Extended

Interior tower columns can be extended to

Columns for Deep

permit concrete basin depth of up to 5’-6”.

Collection Basin

Some exceptions apply, so consult your

 

Marley sales representative

 

 

Fan Cylinder

Optional flared fan cylinder extensions improve

Extensions

fan efficiency to reduce your operating costs.

 

Extensions on Sigma 1000 Series towers

 

conform to OSHA requirements without fan

 

guards.

 

 

Cell Partitions

Extra partitions between fan cells for specific

 

operating considerations. See page 9.

 

 

Vibration Limit

Robertshaw or Metrix single-pole, double-throw

Switch

vibration switches in NEMA 4 housing. Double-

 

pole, double-throw models are also available.

 

 

Oil Level Sight Glass

A brass-fitted oil level sight glass takes the place

 

of the dip stick on the external oil fill and drain

 

system. Permits easy reading of oil level and also

 

lets you change oil through the lube line.

 

 

Air Inlet Screens

Galvanized wire mesh screens over the air inlets

 

keep leaves and trash out of the tower. Easily

 

removable. Choose either treated fir frames or

 

galvanized steel U-edge frames.

 

 

Plywood

Removable, treated fir plywood covers keep

Distribution Basin

upper basins free of leaves and debris. They

Covers

also tend to retard growth of algae by keeping

 

ultraviolet radiation away from the warm

 

water in the basins. Covers may be used as a

 

working surface for tower maintenance.

Accessory

Description and Remarks

 

 

Additional Access

Extra access door on single-cell towers

Door

offers easy access through either endwall.

 

 

Wood Stairway

Pressure-treated Douglas fir 45° stairway located

 

at tower endwall provides access to the fan

 

deck. Choose a stairway in place of one endwall

 

ladder, or use both ladders as well as the

 

stairway. Handrails and kneerails are standard,

 

so design conforms to OSHA standards.

 

 

Steel Ladder

Galvanized steel ladder conforms to OSHA

 

standards. May be in place of or in addition to

 

standard aluminum ladders.

 

 

Ladder Safety Cage

Galvanized steel circular framework, bolts

 

to ladder siderails and conforms to OSHA

 

standards. Cages extend from the top of the

 

guardrail to about 7’ above the base of the

 

ladder. If the tower fan deck is more than 20'

 

above roof or grade, OSHA requires safety cages.

 

 

Plenum Walkway

Pressure-treated Douglas fir plenum walkways

 

extend the full length of the tower from access

 

door to access door above the water line.

 

Guardrails are optional. However, OSHA requires

 

guardrails if the walkway is 4'-0" or more above

 

the basin floor.

 

 

Ladder Extensions

Used when tower is elevated appreciably above

 

working level. Extensions attach to the normal

 

ladder and may require base anchorage

 

(depending on length).

 

 

Premium

Choose from several corrosion-resistant

Hardware

hardware options, providing different degrees of

 

protection.

 

 

Fire Protection

Sprinkler systems and overlay materials let you

 

choose from a range of fire protection options.

 

See page 10.

 

 

Redwood Fan Deck,

You can choose redwood instead of Douglas fir

Distribution Basin, or

for any or all of these tower elements.

Tower Structure

 

8

Image 8
Contents Marley Sigma 1000/1200 CoolingTower  Marley Difference Sigma Advantage Series 1000 Cross-SectionConstruction and Components Fill/Louvers/Drift EliminatorsMechanical Equipment Welded unitized hot-dip galvanized steel supportsWater Distribution System Structure and MaterialsCold Water Collection Basin Access and SafetyCasing Available Options Plenum WalkwayCell Partition Options Non-Standard Motors Special Component OptionsFire Protection Options Cold Water Collection Basins High Design LoadingsAdditional Services West 129 Street Overland PARK, Kansas 66213 United States
Related manuals
Manual 32 pages 15.22 Kb

1000, 1200 specifications

SPX Cooling Technologies, a prominent player in the cooling solutions market, is known for its cutting-edge designs and innovations in the field of cooling systems. Among its notable offerings are the SPX Cooling Technologies 1200 and 1000 series, which are engineered to meet the demands of various industrial applications.

The SPX Cooling Technologies 1200 series is renowned for its efficiency and robust construction. One of its main features is its modular design, allowing for easy installation and maintenance. This series is equipped with advanced cooling technology, enhancing energy efficiency while minimizing operating costs. The 1200 series utilizes a counterflow design, promoting improved heat exchange and a more direct airflow pattern. This results in higher thermal performance and reduced energy consumption, making it an ideal choice for operations that prioritize sustainability and cost-effectiveness.

On the other hand, the SPX Cooling Technologies 1000 series is tailored for versatility and reliability. This series boasts a design that accommodates a range of capacities and configurations, making it suitable for diverse applications, including HVAC, industrial processes, and power generation. One of the standout characteristics of the 1000 series is its handling of large thermal loads with minimal pressure drop, which ensures optimal performance in challenging conditions. Its corrosion-resistant materials enhance durability, making it resilient in harsh environments.

Both series incorporate advanced fan technology, which is designed to maximize airflow while minimizing noise levels. The fans are individually controllable, allowing for precise adjustments to meet specific cooling demands. Furthermore, these cooling towers are designed with user-friendly accessibility, simplifying maintenance and inspection processes, thereby reducing downtime.

SPX Cooling Technologies also places a significant emphasis on innovation. Both the 1200 and 1000 series are built with predictive maintenance capabilities, leveraging IoT technologies to monitor performance metrics in real time. This proactive approach enables facility managers to anticipate maintenance needs and address issues before they escalate into costly failures.

In summary, the SPX Cooling Technologies 1200 and 1000 series represent a substantial advancement in cooling technology, providing efficient, reliable, and modular solutions for various industrial applications. Their design, efficiency, and advanced features position them as leaders in the market, responding to the evolving needs of industries worldwide.