Cornelius UC 700 Series manual Expansion Valve, Adjustment and Troubleshooting

Page 17

EXPANSION VALVE

You will find a thermostatic expansion valve on icemakers, which is used to control the amount of refrigerant flowing through the evaporator. Improperly installed or defective expansion valves may cause low production, soft ice, squeaking from evaporator and excessive load inside evaporator.

By using general refrigeration system troubleshooting along with the pressure charts you can easily determine whether or not the expansion valve is working properly.

ADJUSTMENT AND TROUBLESHOOTING

When troubleshooting the expansion valve you must first be sure you have adequate water flowing into evapo- rator, a clean condenser, unit is properly ventilated, and system is properly charged and free from any restric- tions. Also be sure compressor is operating properly.

Second, take reservoir water temperature and air temperature from condenser inlet and determine at what pres- sure unit should be running. Machines are equipped with thermostatic valves, there is NO adjustment. If correct pressure cannot be obtained, first be sure system has time to stabilize 10-15 minutes. Second, be sure sensing bulb is located at 12:00 position on outlet side of evaporator about 3-4 inches away from evaporator and be sure to insulate well and clamp tightly to tubing. If system pressures are still not adequate, take a second water and air temperature reading and go over other parts of system for possible problems. If proper charge is question- able evacuate and recharge to nameplate and leak check. If valve still malfunctions replace valve.

When replacing valve be sure to bleed refrigerant gas from low side port so as not to lose refrigerant oil. Use general refrigerant system practices when replacing and recharging unit. After new valve is in place, go through previous monitored adjustments and troubleshooting to be sure valve is functioning properly.

NOTE: Units with thermostatic expansion valve—The valve is located on bottom refrigerant line. Sens- ing bulb is located on top refrigerant line. On water cooled units adjust condenser modulating valve before troubleshooting expansion valve.

CAUTION: Very high discharge pressure is present in system. Quick disconnects on your gauges will minimize danger and loss of refrigerant. Comply with federal regulations for reclaiming refrigerant.

CONDENSER MODULATING VALVE

The reason for using a water modulating valve is to supply the correct amount of water to the condenser. and to maintain a proper operating pressure to refrigeration system high side.

The flow of water through the valve is increased as the high side pressure rises and is decreased as high side pressure lowers.

To calibrate the amount of water flow with the refrigeration system high side pressure, turn adjustment screw located on end of valve opposite of bellows. See Figure 6. Turn screw counterclockwise to raise opening point or clockwise to lower opening point. Opening point of valve should be set to maintain proper operating pressure in refrigeration system high side. Refer to Pressure Chart on page 3. Closing point of valve should be set low enough to close valve during compressor stand-by periods.

NOTE: Cold water will absorb heat faster than warm water. The water flow will therefore automatically increase as inlet temperature increases.

630460127

14

Image 17
Contents UC 700 Series CONTINUOUS-FLOW Icemaker Table of Contents Table of Contents cont’d Recognize Safety Information Safety InformationUnderstand Signal Words Follow Safety InstructionsThis page Left Blank Intentionally To the User of this Manual General DescriptionDescription Claims InstructionsDesign Data cont’d Specification ChartClearance Requirements This page Left Blank Intentionally PRE-INSTALLATION InstallationSide Bracket Installation InstallationIcemaker Float Assembly Initial Start UP, Checks and Adjustment InstructionsThis page Left Blank Intentionally Icemaker Cleaning and Sanitizing Procedures Guide to ServiceMaintenance MonthlySemi-Annually Water Level ControlHow Water Level Control Works PurposeTo Replace Water Level Safety Switch Refrigeration System AdjustmentsRefrigeration System To Replace Water Level ControlCondenser Modulating Valve Adjustment and TroubleshootingExpansion Valve BIN Control Condenser Modulating Valve RemovalMotor Check GearmotorStart Relay To Replace Gearmotor AssemblyTo Replace Bearing Upper NUT and Bearing AssemblyAuger and Extruding Head Removal Capacitor Check Electrical CheckoutGear Motor Overload Safety ControlsGuide to Good ICE Wiring Diagram Troubleshooting Chart Icemaker not Operating Troubleshooting Compressors TroubleshootingParts List Name Panel ComponentsICE Chute Components Compressor Components Evaporator Components IMI Cornelius Certificate of WarrantyThis page Left Blank Intentionally IMI Cornelius INC