ERV / HRV
Connect Ducts to ERV/HRV
!CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in minor property damage from sweating duct or loss of unit efficiency and capacity.
If ERV/HRV duct work is installed in an unconditioned space, insulated flexible duct is required.
Insulated flexible duct is required on both
When connecting the ERV/HRV to a
RETURN
SUPPLY
FLEXIBLE DUCTS CONNECTING TO
A08102
Fig. 8 - Flexible Duct Fit-Up
Locate and Install Exterior Hoods
IMPORTANT: To prevent condensation problems, insulated flexible ducts are required on both
After selecting proper hood locations, make appropriate size hole through exterior wall, pass flexible duct through hole and insert hood tube into duct. Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely.
Condensate Drain
(For ERV, skip this step and continue to the next step.) To connect condensate drain, proceed as follows:
1.Punch out holes in foam insulation and door, then insert sleeved grommets into bottom of unit using the gasket washer and nut. (See Fig. 9.)
2.Cut two sections of plastic tubing, about 12” / 305mm long and attach them to each drain.
3.Join the two short sections of plastic tubing to the “T” con- nector and the main tube as shown.
4.Make a loop in the tubing below the “T” connector to create a trap to prevent sewer gases from entering the ventilation system. (See Fig. 9.)
5.Connect unit drain to building’s main drain. Provide slight slope from unit for
A99268
Fig. 9 - Condensate Drain With Loop Trap (HRV Only)
WALL CONTROL
Types
Four remote wall control options are available:
1.Basic Control (see Table 1).
2.OneTouch Control
3.Standard Control (includes dehumidistat)
4.Latent Control (includes humidistat for use with ERV’s only)
Table 1 – Basic Control
MODE | OPERATION | DAMPER | FAN | |
POSITION | SPEED | |||
|
| |||
|
|
|
| |
Off | Off | Closed to outside | Off | |
|
|
|
| |
Low | Air exchange with | Open to outside | Low | |
outside | ||||
|
|
| ||
|
|
|
| |
Intermittent | Air exchange with | Open to outside | Low | |
outside | ||||
|
|
| ||
|
|
|
| |
High | Air exchange with | Open to outside | High | |
outside | ||||
|
|
| ||
|
|
|
|
Table 2 – Recommended Humidity Levels
OUTSIDE | ||
TEMPERATURE | WINDOWS | WINDOWS |
50°F / 10°C | 55% | 65% |
32°F / 0°C | 45% | 55% |
14°F / | 35% | 45% |
30% | 45% | |
25% | 35% |
Location
The Standard Control and the Latent Control sense humidity and not temperature. They must be located in an area where they will continually monitor fresh air circulating within the home. Install ERV/HRV wall controls as close as possible to main system
4