Duct Information

GENERAL

-When planning the path for ducting to the outside, keep in mind the following guidelines:

-Minimize use of elbows and transitions in ductwork as to maximize air flow to outside of building. An efficient airflow

path contributes to the overall efficiency of the Vent Hood.

-DCS recommends the use of smooth wall ducting, not flexible ductwork.

-Transitions are required from rectangular to round ducting

 

10"

 

11"

 

10-1/2"

18-5/8"

4-5/8"

 

Vertical Duct Transition

DCS-IB12 BLOWER Requires one of the following 4-1/2” x 18” to 10” round transitions (purchase separately)

Model 19052-01-Vertical discharge Model 19052-02-Rear discharge Model 19052-03-Left discharge

- Duct tape may be used at ducting joints.

DCS VH 48 / DCS VH12 36 REQUIREMENTS

-DCS recommends the use of 10” round ducting which provides 78.6 sq. In. of surface area.

-Alternate duct sizes in rectangular style may be used. If a rectangular duct style is used, the duct must equal at least 78.6 sq. In. for best results. (Example- 3-1/4” x 24” duct = 78 sq. In.)

-Maintain consistent ducting square area as to avoid reduced air flow. [ie.- With a VH-48 Hood, connecting a 4”x13” (52 sq. In.) to a 10” round (78.6 sq. In.) is not recommended]

DCS VH 36/30 REQUIREMENTS

-DCS recommends the use of 7” round ducting which provides 34.7 sq. In. of surface area.

-Alternate duct sizes in rectangular style may be used. If a rectangular duct style is used, the duct must equal at least 34.7 sq. In. for best results.

DUCT ACCESSORIES

-Wall Caps and Roof Caps must have free open area equal to duct size diameter.

-Note that a Sealed Back Draft Damper may reduce air delivery.

10

Image 11
Contents Dynamic Cooking Systems, Inc Message To Our Customers PrecautionTable Of Contents Ventilator Use Safety Practices & PrecautionsInner Liner Removal Planning The InstallationPlanning the Installation Backdraft DamperVent Hood Assembly Construct Soffit Framing Vent Hood Installation with soffitSite Preparation Install Vent Hood Into Soffit Wall Mounting Vent Hood Installation without soffitCare and USE Finishing The InstallationTo Finish the Installation DCS VH 48 / DCS VH12 36 Requirements Duct AccessoriesDuct Information GeneralDCS VH Series Specifications HOW to Obtain Service ServiceDCS will not PAY for WarrantyLength of Warranty DCS will PAY forDiagram DCS WiringVH 30/36 Wiring Diagram DCSPage Part No r4 Litho in USA 04/2001