Clearances and Requirements

WARNING

Before installation, careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler, operating at a higher static. After installation, the compatibility of the two pieces of equipment must be confirmed, by measuring the air flows of the ventilator, by using the balancing procedure found in this manual.

It is always important to assess how the operation of any HRV may interact with vented combustion equipment (i.e. Gas Furnaces, Oil Furnaces, Wood Stoves, etc.)

NEVER install a ventilator in a situation where its normal operation, lack of operation or partial failure may result in the backdrafting or improper functioning of vented combustion equipment!

Connecting Appliances to the HRV

The following appliances should not be connected to the HRV:

clothes dryer

range top

stovetop fan

central vacuum system

CAUTION

Lint, dust or grease will collect in the HRV damaging the unit.

NOTE: Connecting any of these to the HRV will

invalidate your warranty.

Installation

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a qualified installer or service agency.

The HRV unit must be installed in a horizontal position as shown in the illustration below. The unit should be sus- pended using the provided hanging straps. The unit must be level for proper condensate drainage. Sufficient clearance below the access door is required for servicing the air filters and core. A minimum of 25" (635mm) clear- ance is recommended so the door can be removed. Four PVC reinforced polyester hanging straps are provided for hanging the HRV.

WARNING

Electric shock hazard. Can cause injury or death. Before attempting to perform any service or maintenance, turn the electrical power to unit OFF at disconnect switch(es). Unit may have multiple power supplies.

Location Selection

The HRV must be located in a heated space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weather hoods will be mounted. If a basement area is not convenient or does not exist, a utility or laundry room may be used.

Attic installations are not normally recommended due to:

A)the complexity of work to install

B)freezing conditions in the attic

C)difficulty of access for service and cleaning

Suspending the Unit

The hanging straps should be attached to the unit at the top end corners (mounting screws are already located on the HRV case). Securely fasten the other end of the straps to the ceiling making sure the UNIT IS LEVEL. The straps are designed to reduce the possibility of noise, resonance or harmonics; therefore using the full length of the strap between the HRV and the floor joists is recommended.

Weatherhood Location and Installation

Weatherhood kit includes two fixed-cover hoods with a 1/4” (6mm) mesh screen.

Exhaust Weatherhood Requirements

At least 6' (2 m) from the ventilation air intake*

At least 18" (460mm) above ground or above the depth of expected snow accumulation*

At least 3' (1 m) away from the corner of the building*

At least 3’ away from gas meter, electric meter or a walkway where fog or ice could create a hazard*

Not into a garage, workshop or other unheated space

7

Image 7
Contents Shipping and Packing List Required Tools Installation ToolsOptional Accessories Table of ContentsHRV System Control Engineering Data Model RNC120FOption 2 Reverse Duct Configuration Dimensions inches Engineering Data Model 120ERV Latent Recovery/Moisture Transfer CoreOption 1 Duct Configuration Dimensions Cle Installation InstructionsThat the proper fan be plugged into the proper recepta Clearances and Requirements Connecting Appliances to the HRVInstallation Weatherhood Location and InstallationFasteners not supplied Intake Weatherhood RequirementsDetail Screws supplied Indirect Connection to Air Handler Duct System Installation Air Duct Design and InstallationFresh Air Ducting Direct Connection to Air Handler Duct SystemDrain Connection HRV Only Installation Stale Air Exhaust SystemApplication Illustrations HRV-Option Partially Dedicated System for HRVAir Handler Simplified Installation for HRVFully Dedicated System for HRV Unit is normally balanced on High speed Simplified Installation for HRV Field-supplied Balancing Damper optional Minute Timer Remote Control Devices Optional Main ControlsON/OFF Switch Optional TimersDehumidistat Ventilation Control 2040 ON/OFF Dehumidistat Wiring the ControlsMinute Timer Crank TimerElectrical Operation Mode DIP Switch SettingsIncreasing Low Speed to Medium Low Wiring Diagrams Interlocking HRV Operation to an Airhandler/Furnace Blower Defrost Operation Defrost Cycle DIP Switch SettingsFactory Setting Option Dehumidistat Operation HRV onlyAir Flow Balancing Balancing ProcedurePrior to balancing, ensure that Pitot Tube Air Flow DuctMent of air in the home Troubleshooting Symptom Cause SolutionTo install the clean core MaintenanceClean Air Filters Twice a Year Clean Core Twice a Year a open access doorMaintenance Record

120ERV, RNC120F specifications

The Lifebreath RNC120F,120ERV is a highly efficient energy recovery ventilator designed to promote better indoor air quality while minimizing energy consumption. This model is ideal for a variety of residential applications, providing a cost-effective solution for ensuring a continual supply of fresh outdoor air into living spaces. The RNC120F,120ERV features advanced technologies that allow it to operate efficiently, making it a favorable choice among homeowners and building professionals alike.

One of the standout features of the RNC120F,120ERV is its energy recovery capability. This system can recover up to 85% of the energy from the outgoing stale air and transfer it to the incoming fresh air, which significantly reduces heating and cooling costs. This is particularly advantageous in regions with extreme seasonal climates, as it minimizes the demand on HVAC systems.

The unit is equipped with a high-efficiency ECM motor that operates quietly and consumes less energy compared to traditional motors. This technology not only contributes to lower energy bills but also ensures a more comfortable and peaceful indoor environment. The RNC120F,120ERV has adjustable airflow settings, allowing users to customize the level of ventilation according to their specific needs.

Another important characteristic of the Lifebreath RNC120F,120ERV is its compact design. It can easily be installed in tight spaces, making it suitable for a variety of home layouts and sizes. This versatility allows homeowners to benefit from improved air quality without sacrificing valuable living space.

The system also features a built-in filter that helps remove airborne particles, allergens, and pollutants, enhancing the overall air quality in the home. Regular maintenance and replacement of the filters are simple, ensuring that the unit continues to perform at its best.

In addition to its functional attributes, the RNC120F,120ERV is designed with durability in mind. It is constructed from high-quality materials that can withstand the rigors of continuous operation in various environments. Furthermore, the unit meets strict energy efficiency standards, making it a responsible choice for environmentally conscious consumers.

Overall, the Lifebreath RNC120F,120ERV combines energy efficiency, advanced technology, and ease of use, making it an excellent investment for anyone looking to improve their indoor air quality while keeping energy costs low.