LHE Series Natural Vent Insert

Troubleshooting the Gas Control System

SIT NOVA 820 Millivolt Valve

NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.

WARNING: Before doing any gas control service work, remove glass front.

SYMPTOM

POSSIBLE CAUSES

CORRECTIVE ACTION

 

 

 

 

1. Spark ignitor will not light

A. Defective or misaligned

Using a match, light pilot. If pilot lights, turn off

 

 

electrode at pilot.

pilot and push the red button again. If pilot will not

 

 

 

light - check gap at electrode and pilot-should be

 

 

 

1/8" to have a strong spark.

 

 

 

 

 

 

B. Defective ignitor (Push Button)

Push Piezo Ignitor Button. Check for spark at

 

 

 

electrode and pilot. If no spark to pilot, and elec

 

 

 

trode wire is properly connected, replace ignitor.

 

 

 

2. Pilot will not stay lit after

A. Defective pilot generator

Check pilot flame. Must impinge on thermo

carefully following lighting

(thermocouple), remote wall

couple/thermopile. Note: this pilot burner assem

instructions.

switch.

bly utilizes both-a thermocouple and a thermopile.

 

 

 

The thermocouple operates the main valve

 

 

 

operation (On and Off). Clean and or adjust pilot for

 

 

 

maximum flame impingement on thermopile and

 

 

 

thermocouple.

 

 

 

 

 

 

B. Defective automatic valve

Turn valve knob to “Pilot”. Maintain flow to pilot;

 

 

 

milivolt meter should read greater than 10 mV. If

 

 

 

the reading is okay and the pilot does not stay on,

 

 

 

replace the gas valve. Note: An interrupter block

 

 

 

(not supplied) must be used to conduct this test.

 

 

 

3. Pilot burning, no gas to

A. Wall switch or wires defective

Check wall switch and wires for proper connec

main burner

 

tions. Jumper wire accross terminals at wall

 

 

 

switch, if burner comes on, replace defective wall

 

 

 

switch. If okay, jumper wires across wall switch

 

 

 

wires at valve, if burner comes on, wires are faulty

 

 

 

or connections are bad.

 

 

 

 

 

 

B. Thermopile may not be

1. Be sure wire connections from thermopile at

 

 

generating sufficient

gas valve terminals are tight and thermopile is

 

 

millivoltage.

fully inserted into pilot bracket.

 

 

 

2. One of the wall switch wires may be grounded.

 

 

 

Remove wall switch wires from valve terminals if

 

 

 

pilot now stays lit, trace wall switch wiring for

 

 

 

ground. May be grounded to fireplace or gas

 

 

 

supply.

 

 

 

3. Check thermopile with millivolt meter. Take

 

 

 

reading at thermopile terminals of gas valve.

 

 

 

Should read 250-300 millivolts (minimum 150)

 

 

 

while holding valve knob depressed in pilot

 

 

 

position and wall switch “Off”. Replace faulty

 

 

 

thermopile if reading is below specified minimum.

 

 

 

 

 

 

C. Plugged burner orifice.

Check burner orifices for debris and remove.

 

 

 

 

 

 

D. Defective automatic valve

Turn valve knob to “On”, place wall switch to “On”

 

 

operator.

millivolt meter should read greater than 100 mV. If

 

 

 

the reading is okay and the burner does not come

 

 

 

on, replace the gas valve.

 

 

 

4. Frequent pilot outage

A. Pilot flame may be too low

Clean and/or adjust pilot flame for maximum flame

problem.

or blowing (high) causing the

impingement on thermopile and thermocouple.

 

 

pilot safety to drop out.

 

 

 

 

 

 

 

B. Possible blockage of the vent

Check the vent terminal for blockage (recycling the

 

 

terminal.

flue gases)

 

 

 

 

10005360

15

Image 15
Contents LHEC20 LHER30 LHEC30 Table of Contents Please Read the Following Carefully Installation & Operating InstructionsLocating Your Gas Fireplace Insert With Zero Clearance Kit Insert ApplicationsMinimum Fireplace Insert Opening Fireplace & Trim DimensionsAn alternate air supply is recommended with this component MantelsFraming & Finishing Zero Clearance ApplicationsHigh Elevations Gas Line InstallationGas Specifications Gas Inlet & Manifold PressuresFan Removal Instructions Installation of Trim Switch For RN/RP Gas ValvesGas Supply Pressures Fan KitFor left side installation, reverse switch position Venting InstallationTest Chimney Draw Common Flue InstallationsLiner Installation Draft Relief OpeningBlocked Flue Shut Off System Blocked Flue Shut Off Switch AccessCeramic Refractory Installation Access to the shut off switch from outside of the insertOperating Instructions First Firing Flame Adjustment RN/RP ModelsFlame Characteristics Large Lava Rock PlacementPSE Pilot What to do if YOU Smell GAS To Turn Off Gas To HeaterSymptom Possible Causes Corrective Action Troubleshooting the Gas Control SystemHoneywell Millivolt Valve Instructions for RF Comfort Control Valve Shut Off ProcedureTransmitter Operation Off Mode On Manual ModeChange Between F/C Temperature Units Delay Timer ModeAuto Mode Fan Override During Auto ModeAuto Path LED Count Service Action Replace valveLocal Path Burner and Burner Compartment MaintenanceTrim Cleaning Cleaning the Standing Pilot Control SystemLHE Series LHER20 LHEC20 LHER30 LHEC30 DescriptionRemote Switch for RN or RP Units Optional Accessories Remove the bottom door rail If Warranty Service is NEEDED… Product Covered by this WarrantyAFUE% Efficiency Ratings

LHER20 specifications

The Vermont Casting LHER20 is a premium wood-burning stove that combines efficiency, aesthetics, and environmentally responsible heating. Known for its high-quality construction and innovative technologies, this model is designed to provide optimal warmth while also enhancing any living space with its classic design.

One of the standout features of the LHER20 is its exceptional thermal efficiency. With an EPA-certified design, the stove meets stringent emissions standards, ensuring that it burns wood cleanly and efficiently. This not only helps in reducing environmental impact but also translates to longer burn times and less frequent reloading, providing convenience for users.

The LHER20 incorporates advanced air management systems that promote secondary combustion. This technology re-burns exit gases from the initial burn, maximizing fuel utilization and enhancing heat output. As a result, this stove delivers a remarkable heat output, making it ideal for heating medium to large spaces.

Crafted from high-quality cast iron, the Vermont Casting LHER20 offers both durability and aesthetic appeal. It comes in several attractive finishes, including matte black and classic enamel colors, allowing homeowners to choose a look that complements their decor. The traditional styling features large glass doors that provide a captivating view of the fire, creating a cozy atmosphere and enhancing the overall experience of wood-burning.

Another notable characteristic is its user-friendly operation. The LHER20 features a simple damper control system, allowing users to easily adjust airflow for controlling the burn rate. This ensures a steady and consistent heat output while allowing users to tailor the stove’s performance to their preferences.

In terms of size, the LHER20 is compact yet powerful, making it suitable for various spaces, including cabins, homes, or even larger open-plan areas. The stove's efficient heat delivery helps create a comfortable environment during the cold months, proving its worth as a reliable heating solution.

Overall, the Vermont Casting LHER20 is an exemplary wood stove that combines tradition with modern technology. Its outstanding features, environmental responsibility, and aesthetic appeal make it a sought-after choice for those seeking to embrace the warmth and charm of wood-burning stoves in their homes. Whether for aesthetics, efficiency, or performance, the LHER20 stands as a testament to Vermont Casting's commitment to quality.