Bertazzoni X486GGGVX dimensions Performance CHECKLlST

Page 10

f)The appliance must be isolated from the gas supply piping system by closing its individuai manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.45 kPa).

3.Flexible Connections:

a)If the unit is to be installed with flexible couplings and/or quick disconnect fittings, the installer must use a heavy-duty, AGA design-certified commerciai flexible connector of at least 1/2" (1.3 cm) ID NPT (with suitable strain reliefs) in compliance with ANSI Z21.41 and Z21.69 standards.

b)In Massachusetts: The unit must be installed with a 36" (3-foot) long flexible gas connector.

c)In Canada: CAN 1-6.10-88 metal connectors for gas appliances and CAN 1-6.9 M79 quick disconnect device for use with gas fuel.

CAUTlON: Leak testing of the appliance shall be conducted according to the manufacturer's instructions. Before placing the oven into operation, always check for leaks with a soapy water solution or other acceptable method. DO NOT USE AN OPEN FLAME TO CHECK FOR LEAKS!

A 2”( 5 cm)

B 3”(7,6 cm)

D 8”(20,3 cm)

A properly-grounded horizontally- mounted electrical receptacle should be installed no higher than 3" (7.6 cm) above the floor, no less than 2”( 5 cm) and no more than 8”(20,3 cm) from the right side (facing product). Check all local code requirements.

An agency-approved, properly-sized manual shut-off valve should be installed no higher than 3" (7.6 cm) above the floor and no less than 2”( 5 cm) and no more than 8”(20,3 cm) from the left side (facing product). To connect gas between shut-off valve and regulator, use agency-approved, properly sized flexible or rigid pipe. Check all local code requirements.

PERFORMANCE CHECKLlST

All burners are tested before leaving the factory. There are no adjustments for the burners if connected according to the information on the rating plate. Check each burner for proper operations. Flames should be blue in all settings. If service is required, contact your dealer for the name of their authorized service agency. Gas conversions and initial installation are not the responsibility of the manufacturer.

The installer should carry out the following performance checks. Refer to instructions below.

1.Check surface burner ignition.

2.Check air shutter adjustment (only for oven and broiler burner)- sharp blue flame, no yellow tipping, sooting or flame lifting

3.Check low flame adjustment

4.Check broiler and oven ignition - all burner ports.

5.Check for gas leaks (odors) at all gas connections.

6.Check oven bake and convection bake function.

10

Image 10
Contents Bertazzoni What to do if YOU Smell GAS Installation instructions Installation Manual Backguard Installation Instruction Height adjustable legsWorktop Frontguard Installation Instructions Installation SIDE-BY-SIDE to Kitchen Cabinet Cooker Hood Installation Electrical ConnectionGAS Connection Manual Shut-off ValvePerformance CHECKLlST Replacement Parts Final PreparationChanging the Nozzles for USE with Other Types of GAS Models X486GGGVX Regulation of BurnersService & Maintenance Instructions Important Instruction Descriptions Control Panel DescriptionUsing Burners Manual ignitionUsing the Electric Griddle Using the Left GAS Oven Table N7Fish Using the GAS Broiler only left oven Using the Right GAS Oven Table N8Cleaning the Appliance After Sale Service Spare Part List Oven Convection FAN Small Blue BUD Page Page Page Page Page Page Page