Amana PGB58B, PGC(24-60)B Filter Access Door, Filters, Filter Installation

Page 15

Duct systems and register sizes must be properly de- signed for the C.F.M. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air Conditioning Con- tractors of America Manual D (Residential) or Manual Q (Commercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation.

A duct system should be installed in accordance with Standards of the National Board of Fire Underwriters for the Installation of Air Conditioning, Warm Air Heating and Ventilating Systems, pamphlets No. 90A and 90B.

The warm air supply duct from the unit through a wall fabricated of combustible material may be installed with- out clearance. However, minimum clearances for the unit must be observed as shown in Section III.

It is recommended that the outlet duct be provided with an access panel. This access should be large enough to inspect the air chamber downstream from the heat exchanger for any smoke or combustion gas leaks. A cover should be tightly attached to prevent air leaks.

For horizontal airflow, duct flange dimensions on the unit are shown in Section III.

For vertical airflow, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimen- sions are shown in the Amana PRC roof curb installa- tion manual.

If desired, supply and return duct connections to the unit may be made with flexible connections to reduce pos- sible noise transmission.

Filters

WARNING

Important: If you will be using the Over/Under Transition Kit, (PDTROU3A or PDTROU5A) you cannot use the unit filter rack.

If you are using the Over/Under transition kit or are sim- ply choosing not to use this filter rack, the filter(s) may be located in the return air duct(s) or return air filter grille(s). Filters installed external to the unit should be sized in accordance with their manufacturer recommen- dations. If you choose to use a throwaway filter it should be sized for a maximum face velocity of 300 feet per minute.

Important: The PGC 42 and 48 package units contain an evaporator drip pan installed on the return air side of the indoor coil.

If an economizer is to be installed on these units, the drip pan must be removed. The pan can be removed by cutting it away. It will not be needed when an econo- mizer is installed.

If filters are to be installed on these units, they must be from filter kit PFK5B1 or PFK5B6. The filters in these kits are sized to fit with the drip pan in place.

Filter Installation

Important: When installing a filter, always make certain the air flow arrows on the filter point toward the indoor blower.

To install a filter in the filter rack, proceed as follows:

1.Disconnect power to the unit.

2.Locate the filter access door above the return air opening. See Figure 9.

Filter Access Door

Never operate furnace without a filter in- stalled as dust and lint will build up on internal parts resulting in loss of effi- ciency, equipment damage, and possible fire.

A return air filter is not supplied with this unit; however, there must be a means of filtering all of the return air. For your convenience, this unit contains a factory in- stalled filter rack. If you choose to install the return air filter in the unit filter rack, use the appropriate Amana filter kit or a permanent filter that is properly sized as follows:

Model

Amana Kit #

Required Permanent

Filter Size

 

 

 

 

 

PGC24, 30, or 36

PFK3A1 or

26" x 20" x 1"

PFK3A6

 

 

PGC42, 48, 60

PFK5B1 or

32-5/8" x 22-3/8" x 1"

or PGB58

PFK5B6

 

The Amana filter kit includes a permanent filter, door label, and installation instructions. PFK3A1 and PFK5B1 contain filter, label, and instructions for one unit. PFK3A6 and PFK5B6 contain filters, labels, and instructions for six units.

Figure 9

Filter Access Door

3.Remove the four 5/16" sheet metal screws and set the filter access door aside.

4.Insert the filter into the filter rack channels and lower into place. Make sure the filter slides completely to the bottom so no part of the filter remains outside the back panel.

5.Return the filter access door to its original position and secure it with the four sheet metal screws.

6. a. If you are using an Amana filter kit, affix the FIL- TER ACCESS label to the filter access door.

b. If you are NOT using an Amana filter kit, clearly mark the filter access door “FILTER ACCESS”.

7. Reconnect the power.

NOTE: A clean permanent filter installed as described above will have a negligible effect on air flow.

15

Image 15
Contents PGB58B Table of ContentsGas Pack Specifications Unit SpecificationsHeating TEV PGB CFM& Temperature Rise vs. External Static Pressure Table PGC Temperature Rise TableIf you smell gas II. Safety InformationTo The Installer To The OwnerIII. General Information All InstallationsGround Level Installations Only Rooftop Installations OnlyRequired Clearances For All Installations IV. Rigging and Handling Transportation DamageLocating The Thermostat Connecting The Gas Piping Natural Gas Gas PipingGas Piping Proper Piping Practice Checking The Gas PipingTanks And Piping for Propane Gas Units Vl. Electrical Wiring Airflow Conversion Heat Anticipator SettingVll. Circulating Air and Filters Unit VoltageTypical Electrical Wiring Typical Wiring RooftopFilter Access Door Filter InstallationFilters Typical Condensate Drain VIII. Flue VentIX. Condensate Drain Air Inlet Hood and Flue HoodTiming Chart for Normal Robertshaw Operation PGB & PGC PGB Timing Chart for Normal Cooling OperationPGC Timing Chart for Normal Cooling Operation XIl. Startup and Adjustment Heating Sequence of Operations PGB & PGCXI. Cooling Sequence of Operations Operating Instructions Heating Reset After Lock-outRollout Protection Shown Without Heat Shield Position of Limit Control Gas ValveMeasuring Inlet Gas Pressure Alternate Method Check Limit And Fan Control Checking External Static PressureChanging Blower Speeds PGC Units Changing Blower Speeds PGB UnitsShort Cycle Protector Location Fan and Limit ControlOperating Instructions cooling High Pressure Protection DevicesScroll Compressors Reciprocating CompressorBlower Motor and Housing XIII. MaintenanceRemoval of Fan Motor Induced Draft MotorTransition Kit Pressure Drop XIV. Accessories and Functional PartsAccessory List Functional Parts ListPGC XV. Typical Cooling Performance DataPsig PGC24 XVI. Wiring DiagramPGC PGC Volt Installation G R PGB

PGB58B, PGC(24-60)B specifications

Amana, a trusted name in heating and cooling, offers several high-efficiency gas furnace models, including the PGC(24-60)B and PGB58B. These furnaces combine innovation, reliability, and advanced technology to provide an optimal heating solution for any home.

One of the standout features of the Amana PGC(24-60)B is its modulating heating capability. This technology allows the furnace to operate at different heating levels based on the home’s demands. Instead of simply turning on and off, the PGC adjusts its output to maintain a consistent temperature, promoting energy efficiency and comfort. This not only reduces energy consumption but also minimizes temperature fluctuations, providing a more comfortable indoor environment.

The PGB58B model is designed with a focus on efficiency, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96%. This means that a higher percentage of the fuel used is converted into heat, making it one of the most efficient choices available. The combination of high-efficiency design and advanced components makes the PGB58B an excellent option for homeowners looking to reduce their energy bills while enjoying reliable heating performance.

Both models come equipped with a durable casing, ensuring longevity and performance. The rust-resistant and heavy-gauge steel construction protects against harsh weather conditions, making them suitable for various climates. Additionally, they feature a multi-speed blower motor, which optimizes airflow and enhances comfort by evenly distributing warm air throughout the home.

Advanced diagnostics and self-monitoring capabilities are integral to these models. The built-in diagnostic system enables quick identification of performance issues, allowing for timely maintenance and reducing repair costs. Furthermore, these furnaces are designed to be compatible with smart home technology, allowing homeowners to control their heating systems remotely and maximize energy efficiency.

In summary, the Amana PGC(24-60)B and PGB58B gas furnaces stand out for their innovative features and commitment to energy efficiency. With modulating heating, high AFUE ratings, durable construction, and smart technology compatibility, they offer reliable heating solutions that ensure comfort while keeping energy costs low. Homeowners can feel confident in their investment, knowing they have chosen a furnace that prioritizes both performance and sustainability.