Monessen Hearth WC400 manual Installing the Firestop Spacer Ceiling Hole, Elbow Strap Angled Strap

Page 12

WR / WC Series Woodburning Fireplace

Continue installing the pipe as required until pipe is installed up through the ceiling. At this point, you must install a firestop spacer.

Installing the Firestop Spacer

in the Ceiling Hole

A firestop spacer is used to keep pipe spaced properly and required for safety.

Nail the firestop spacer (at each corner) to the framing members of the ceiling hole. NOTE: A firestop spacer is not required at the roof.

Hole sizes listed in Figure 13 for angled firestop spac- ers provide minimum required air space to chimney pipe for ceiling thickness up to 8" (203 mm). When combined thickness of ceiling material, ceiling joists and flooring material exceeds 8" (203 mm), adjustments must be made in framing to assure that minimum air spaces to chimney are maintained.

Pipe Section

Pipe

Rim

Hem

Lance

Pipe

Rim

FP558

Fig. 16 Install pipe, listening for the snap-lock to fasten.

Proper Firestop Spacer Installation

Figure 18 shows different installation procedures for both an area that is an attic and an area that is not an attic.

If the area above the ceiling is not an attic, position the firestop spacer with the flange on the ceiling side and the angled portion extending up into the hole.

If the area above the ceiling is an attic, position the firestop spacer with the flange on the top of the framed hole and the angled portion extending down into the hole.

Firestop spacers are not available for nor are they re- quired on vertical walls.

DO NOT put any sealant around the area where the outer pipe slides through the firestop spacer. If you seal this area, it may cause a fire hazard.

Elbow Strap

Angled Strap

FP270/271

Support Structure

Elbow Strap (must be tight)

Ceiling Hole

Framing

Angle Firestop

Chimney Support Strap (must be tight)

Canadian Requirements

for Insulation Shield

Fig. 17 Attach straps to a structural framing member.

In Canada, an attic insu- lation shield is required to prevent attic insulation

Attic Installation

Ceiling Installation

from contacting the chim- ney section. NOTE: If the attic insulation shield is used, the firestop is not required in the attic instal- lation. Framing dimen- sions for the chimney hole should measure

14¹⁄" x 14¹⁄" (368 x 368 mm). An attic shield MUST be installed on top of attic joists (above the floor level). (Fig. 19)

Nails (4)

Firestop

Spacer

Joist

NOTE: If the attic insulation shield is used, the firestop is not required in the attic installation.

Fig. 18 Installing firestop spacer.

Joist

Firestop

Spacer

Nails (4)

FP593

12

20014528

Image 12
Contents WR/WC Series Safety Information Table of ContentsWR400 Series Woodburning Fireplace WR500 Series Woodburning Fireplace Chase Installation Front Width Back Width Depth30˚ Elbow Offsets Illustration KeyRise OffsetPlanning Information Mounting the FireplacePlanning the Chimney Run Ten Foot RuleInstallation Chase InstallationChimney Supports Insulating Fireplace Enclosure For Cold ClimatesInstalling Electrical Wire For Circulator Models Install Fan Kit AssemblyChimney Setup FramingStraight-Up Chimney Installation Offset InstallationCeiling Chimney Hole Possible Obstructions Cutting the HolePositioning, Safety Strips Securing the Fireplace Installing Outside Air KitInstalling the Chimney System Angle of Chimney at CeilingInstalling the Firestop Spacer Ceiling Hole Proper Firestop Spacer InstallationAttic Installation Ceiling Installation Canadian Requirements For Insulation ShieldContinue Installing Pipe to Complete Run Install Remainder of Chimney SectionsAdditional Ceilings Penetrating the RoofInstalling Top Housing or Termination Installing Chimney In a ChaseFinishing Finish Wall Top View MaterialSide Wall Protection Hearth Installation Minimum Wall ClearancesFor On-Site Construction Noncombustible Surround FacingSide View EH2416 458Installing Line for Gas Logs Fireplace Top ViewWR400/500, WC400/500 Series Description WR/WC400 WR/WC500Accessories Accessory Description Model NumberChimney Components CCE-SK AIS-SKWhat is Not Covered Limitations and ExclusionsMhsc