Optima Company PC specifications 1660-IN-010-0-04

Page 8

2.Power up the OPtima. From Control Panel (in Settings) select Add/Remove Programs and click Install. Insert the SW-LNET-INT disk in the floppy drive and select “A:setup.exe.” Install the file to the C:\Modicon\WinConX\MBX Driver di- rectory. If the installer will not create this directory, create it first, and then perform the installation again. If you are prompted for a computer name and company, enter “Preferred Customer” and “Preferred Company” respectively. Restart the computer after the installation.

3.After restarting, go to MBX Driver Configuration (in the Start, Programs, WinConX, MBX Driver menu). Choose New and set the device type to SA85 and the device number to “0.” SelectSetup. Set the Device Name to ClMbx0 (this is a lower case “L,” not the number “1”). Change Operation to Interrupt Driven. Set the Memory Address to D0000, IRQ=5 and Bus Number = 0. (For a 2nd card the memory address and IRQ must be set to match the switch and jumper setting for that card - see Step 1.) Click OK and return to the main menu. Click OK again to initialize the card. Select Close and then restart the system.

4.After restarting, insert the SW-WVD-INT disk in the floppy drive and select “A:setup.exe.” This will install the WinConx Virtual MBX. Use the default settings for where to install. Exit after the installation is complete.

5.Edit the Config.nt file (in the winnt\system32 directory) by adding the following line (EXACTLY as it appears below) to the end of the file:

device=%SystemRoot%\System\mbp16.sys

(no spaces)

6.Edit the Autoexec.nt file (also in the winnt\system32 directory) by adding the following line (EXACTLY as it appears below) to the end of the file:

%SystemRoot%\System\mbp16vec 5d

(a space between “vec” and “5”)

Note that “5d” is the NetBIOS vector. It must match the setting in the Modicon.ini file created below.

7.Path to the \winnt directory. (If you have previously opened Concept and tried to connect to a PLC, the following file will already have been created.) Using Notepad, either modify or create the file “modicon.ini” and include the following information:

[Ports]

 

COM1=COM1:9600,e,8,1 RTU 1000

(a space between “1” and “R” and

MBP0=5d

also between “U” and “1”)

Note that the “5d” here matches the “5d” in the Autoexec.nt file. If, when connect- ing to a PLC, a resource violation error occurs change the Autoexec.nt file AND the modicon.ini file to “5c” and try again.

8. Install the ASB NT server (“MBPASB”).

Page 8

1660-IN-010-0-04

Image 8
Contents Contents FiguresInstallation WiringIntroduction CE EMC ComplianceModel DSA2 Dimensions for Flange Mount 550 450 Model DSB2 and11.640 the Remote I/O Station External Floppy Drive Adding Boards Installing the Modbus Plus SA85 BoardAdding Hardware 1660-IN-010-0-04 Bios Password Settings Adding MemoryPeripheral Devices Operating SystemSetup Windows NT Setup 5.1.1 Window Settings Regional Settings for DateDate/Time Zone FontsInstalling the Wonderware License Power Shutdown/Battery Backed Power SupplyBackups DisplayNumeric Keyboard Keyboard Functionality Model DSA2 onlyFunction Keys Environmental Specifications Special CasesLeft/Right Mouse Buttons Cursor KeysChanging the Username and Password Using the Registry EditorAutomatic Logon to Windows NT Disabling AutoLogon Bypassing AutoLogonTroubleshooting/Application Tips Front keypad or touchscreen stops workingDisconnecting the Display End User License AgreementDescription of Other Rights and Limitations Upgrades and Recovery Media 1660-IN-010-0-04 An Invensys Company