2nd Ave DVP-0204520-02 operation manual DeviceNet Network Scanner DVPDNET-SL

Page 17

DeviceNet Network Scanner DVPDNET-SL

Item

Function

Default

DIDO Output

The digital output points shall be 8’s multiple. The number will

 

be regarded as 8 when it is less than 8 and regarded as 16

N/A

Points (Y)

when it is bigger than 8 but less than 16.

 

 

 

 

 

 

AIAO Module

The number of special I/O modules connected to RTU-DNET.

N/A

Number

Range: 0 ~ 8

 

 

 

 

Diagnostic

The interval when RTU-DNET executes diagnosis. Range:

5 (sec)

Intervel Time

1~ 65 secs

 

 

 

 

IO Module

How RTU-DNET will react when the special I/O module

 

connected to it is offline. You can choose “Ignored”, "Alarm”

Alarm

Offine Treatment

or “stop DeviceNet IO".

 

 

 

 

 

 

IO Module

How RTU-DNET will react when it detects errors. You can

Alarm

Error Treatment

choose “Ignored”, “Alarm” or “Stop DeviceNet IO”.

 

 

 

 

 

For you to decide whether to add control word and status

 

 

word to I/O data. When you choose not to do it, the I/O data

 

Add control word

in RTU-DNET and DeviceNet master will not include control

Not to add

and status word to

IO data

word and status word. If you choose to add them in, the I/O

 

 

data in RTU-DNET and DeviceNet master will include control

 

 

word and status word.

 

 

 

 

(13)Confirm all the configurations are correct and click on “Download” to download the configurations to RTU-DNET. After the download is completed, click on “OK”.

(14)After the configuration o f RTU-DNET is completed, you will return to the main page.

(15) Double click on VFD-B Drives (node 03), and the “Node Configuration…” dialog box will appear.

DVP-PLC Operation Manual

15

Image 17
Contents DVP-0204520-02 DVPDNET-SLPage Table of Contents Configuration Basic Functions of DVPDNET-SL FeaturesIntroduction Can SpecificationsI/O Scan List Product Profiles DimensionProduct Profile & Outline DeviceNet Connection Port Address SwitchFunction Switch Connecting DVPDNET-SL to DVP-SV MPU Digital IndicatorInstalling DVPDNET-SL and DVP-SV MPU on DIN Rail Basic OperationCorresponding Relation between DVPDNET-SL and DVP-SV ConfigurationConnecting to DeviceNet Connection Port I/O Mapping Table How to Construct a DeviceNet NetworkConstructing DeviceNet Network RTU-DNET Ascii COM1DVP-SV DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DeviceNet Network Scanner DVPDNET-SL DVPDNET-SL DeviceNet Network Control MOV Structure of Explicit Message Sending Explicit Message from Ladder DiagramPrinciple of Explicit Message Sending MAC ID Node Address00 DeviceNet Node Address02 H0101 D6250 ReqID = 01, Command = DeviceNet Network Scanner DVPDNET-SL H0008 D6251 Port = 00, Size = Display of Node Status on Network Bit-Strobe CommandPrinciple of Bit-Strobe Display of Node Status in Scan ListStatus of DVPDNET-SL LED Indicator & Trouble-shootingNS LED MS LED Digital Indicator LEDMS LED Correction is needed Memo